Hitachi L200 Fault Codes List
Troubleshoot your Hitachi L200 inverter with our updated guide. Learn to interpret E01-E60 trips, access the trip history via the d081 parameter, and reset faults to minimize downtime.
Hitachi L200 Fault Codes Reference Table
Below is the complete list of protective functions and trip codes. Please refer to this table to match the alphanumeric code on your inverter with the specific hardware or load issue.
L200 Inverter Fault Codes
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Over-current event while at constant speed |
Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly. Remedy:
|
| E02 Over-current event during deceleration |
Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Excessive current detected during deceleration).
Remedy:
|
| E03 Over-current event during acceleration |
Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Excessive current detected during acceleration).
Remedy:
|
| E04 Over-current event during other conditions |
Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Detected in conditions other than constant speed, accel, or decel).
Remedy:
|
| E05 Overload protection |
Cause: When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.
Remedy:
|
| E07 Over-voltage protection |
Cause: When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.
Remedy:
|
| E08 EEPROM error |
Cause: When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.
Remedy:
|
| E09 Under-voltage error |
Cause: A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque.
Remedy:
|
| E11 / E22 CPU error |
Cause: A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.
Remedy:
|
| E12 External trip |
Cause: A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.
Remedy:
|
| E13 USP (Unattended Start Protection) |
Cause: When USP is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode.
Remedy:
|
| E14 Ground fault |
Cause: The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests.
Remedy:
|
| E15 Input over-voltage |
Cause: The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state.
Remedy:
|
| E21 Inverter thermal trip |
Cause: When the inverter internal temperature is above the threshold, the thermal sensor detects excessive temperature of power devices and trips.
Remedy:
|
| E30 Driver error |
Cause: An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause.
Remedy:
|
| E35 Thermistor |
Cause: When a thermistor is connected to terminals [6] and [L] and the inverter has sensed the temperature is too high.
Remedy:
|
| E60 Communications error |
Cause: The inverter’s watchdog timer for the communications network has timed out.
Remedy:
|
| --- Under-voltage (brown-out) with output shutoff |
Cause: Due to low input voltage, the inverter turns its output OFF and tries to restart. If it fails to restart, the alarm trips.
Remedy:
|
How to Read L200 Faults via the Digital Operator
The Hitachi L200 stores detailed information about the last three trip events. In 2026, using the Monitor (d) parameters is the fastest way to troubleshoot without proprietary software.
- Trip History (d081 to d083): Parameter d081 shows the most recent fault. Parameters d082 and d083 store the two previous failures.
- Status Snapshot: When viewing a trip in d081, the display alternates between the error code and the inverter status (Output Frequency, Current, and DC Bus Voltage) at the time of the trip.
- Monitor Mode: Use the FUNC key to navigate to the “d” group to view real-time data such as d001 (Output frequency) or d002 (Output current) to identify spikes before a trip happens.
General Troubleshooting Steps
Before performing a manual reset on your Hitachi L200, perform these essential hardware checks:
- Overcurrent (E01 – E04): Check for short circuits in the motor wiring. If the trip happens only during acceleration, increase the Acceleration Time in parameter F002.
- Overvoltage (E07): Typically caused by a high-inertia load decelerating too quickly. Increase the Deceleration Time in parameter F003 or check for a spike in the input line voltage.
- Thermal Trip (E05): The inverter has detected a motor overload. Verify the motor’s rated current setting in parameter b012 (Electronic Thermal Level).
Frequently Asked Questions (FAQ)
Q: What is the difference between a Trip and a Warning?
A: A Trip (codes starting with ‘E’) immediately stops the inverter output to protect the motor and drive. A Warning (indicated by status LEDs or codes like ‘USP’) indicates an abnormal condition that may allow the drive to continue running or prevent it from starting.
Q: How do I reset a Hitachi L200 fault?
A: Once the cause is cleared, you can reset the drive by:
- Pressing the Stop/Reset key on the keypad.
- Closing the digital input terminal assigned as RS (Reset) (Terminal 5 is the default reset input).
- Performing a power cycle (Wait for the display to go completely dark before turning it back on).
Q: Why does my drive show “USP” on the display?
A: USP (Unattended Start Protection) is a safety error. It occurs if the Run command is active when the power is turned on. Turn off the Run command to clear the “USP” message.
Q: Where is the fault history stored?
A: The history of the last 3 faults is stored in Monitor Mode under parameters d081, d082, and d083. Each entry provides the fault code and the electrical conditions at the time of the event.