Inovance MD290 Drive Fault Codes List

A comprehensive guide to Inovance MD290 general-purpose drive fault codes. Learn to interpret Err codes, troubleshoot conveyor/pump issues, and use InoDriveShop.

Inovance MD290 Fault Codes Reference Table

Below is the complete list of fault codes, descriptions, and potential solutions associated with the MD290 series.

Fault Codes Cause & Solution
Err02
Overcurrent
during
acceleration
Cause & Solution:

1.
Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, the motor cable or contactor.
2.
Acceleration time is too short.
- Increase acceleration time.
3.
Customized torque boost or V/F curve is not appropriate.
- Adjust the customized torque boost or V/F curve.
4.
The voltage is too low.
- Adjust the voltage to normal range.
5.
The spinning motor is started.
- Enable the catching a spinning motor function or start the motor after it stops.
6.
A load is applied suddenly during acceleration.
- Cancel the suddenly added load.
7.
The rated AC drive power is low.
- Replace the drive by one with higher rated power.
8.
The braking resistor resistance is small.
- The braking resistor is short circuited.
- Replace a new braking resistor.
Err03
Overcurrent
during
deceleration
Cause & Solution:

1.
Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on motor, motor cable or contactor.

2.
Acceleration time is too short.
- Increase acceleration time.

3.
The voltage is too low.
- Adjust the voltage to normal range.

4.
A load is added suddenly during deceleration.
- Cancel the suddenly added load.

5.
Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

6.
The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err04
Overcurrent
at constant
speed
Cause & Solution:

1.
Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, motor cable or contactor

2.
The voltage is too low.
- Adjust the voltage to normal range.

3.
A load is added suddenly during running.
- Cancel the suddenly added load.

4.
The rated AC drive power is low.
- Replace the drive by one with higher rated power.

5.
The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err05
Overvoltage
during
acceleration
Cause & Solution:

1.
Input voltage is too high.
- Adjust input voltage to normal range.

2.
An external force drives motor during acceleration.
- Cancel the external force.

3.
Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

4.
Acceleration time is too short.
- Increase acceleration time.
Err06
Overvoltage
during
deceleration
Cause & Solution:

1.
Input voltage is too high.
- Adjust input voltage to normal range.

2.
An external force drives motor during deceleration.
- Cancel the external force or install the braking resistor.

3.
Deceleration time is too short.
- Increase deceleration time.

4.
Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.
Err07
Overvoltage
at constant
speed
Cause & Solution:

1.
Input voltage is too high.
- Adjust input voltage to normal range.

2.
An external force drives motor during running.
- Cancel the external force or install a braking resistor.
Err08
Pre-charge
resistor
fault
Cause: Bus voltage fluctuates around undervoltage threshold continuously

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
Err09
Undervoltage
Cause & Solution:

1.
An instantaneous power failure occurs.
- Reset the fault

2.
The AC drive's input voltage is not within the permissible range.
- Adjust the voltage to normal range.

3.
The bus voltage is abnormal.
- Replace the AC drive.

4.
The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal.
- Replace the AC drive.
Err10
Drive
overload
Cause & Solution:

1.
The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2.
The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err11
Motor
overload
Cause & Solution:

1.
F9-01 (Motor overload protection gain) is set improperly.
- Set F9-01 correctly.

2.
The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

3.
The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err12
Input phase
loss
Cause & Solution:

1.
Three phase input is abnormal.
- Eliminate faults in external circuitry

2.
Drive board is abnormal.
- Eliminate faults in external circuitry

3.
Lightning protection board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.


4.
Control board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err13
Output phase
loss
Cause & Solution:

1.
Motor winding is damaged. Check resistance between motor cables.
- Replace motor is winding is damaged.

2.
The cable connecting the AC drive and the motor is abnormal.
- Check for wiring errors and ensure the output cable is connected properly

3.
The AC drive's three-phase outputs are unbalanced when the motor is running.
- Check whether the motor three-phase winding is normal.

4.
The drive board or the IGBT is abnormal.
- Replace the AC drive.
Err14
IGBT
overheat
Cause & Solution:

1.
The ambient temperature is too high.
- Lower the ambient temperature.

2.
The ventilation is clogged.
- Clean the ventilation.

3.
The fan is damaged.
- Replace the cooling fan.

4.
The thermally sensitive resistor of IGBT is damaged.
- Replace the AC drive.

5.
The AC drive IGBT is damaged.
- Replace the AC drive.
Err15
External
fault
Cause & Solution:

1.
External fault signal is input via DI.
- Confirm that the mechanical condition allows restart (F8-18)and reset the operation.
2.
External fault signal is input via virtual I/O.
- Confirm that the virtual I/O parameters in group A1 are setcorrectly and reset the operation.
Err16
Communication
fault
Cause & Solution:

1.
The host controller is in abnormal state.
- Check the cable of the host controller.

2.
Communication cable is abnormal.
- Check the communication cables.

3.
Communication parameters in group Fd are set improperly.
- Set communication parameters in group Fd properly.

4. After all the preceding checkings are done but the fault still exists,
restore the default settings.
Err17
Contactor
fault
Cause & Solution:

1.
Drive board and power supply are abnormal.
- Replace drive board or power supply board.

2.
Contactor is abnormal.
- Replace contactor.

3.
The lightning protection board is abnormal.
- Replace the lightning protection board.
Err18
Current
detection
fault
Cause: The drive board is abnormal.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
Err19
Motor
auto-tuning
fault
Cause & Solution:

1.
Motor parameters are not set according to nameplate.
- Set motor parameters correctly according to nameplate.

2.
Motor auto-tuning times out.
- Check the cable connecting AC drive and motor.
Err21
EEPROM read-
write fault 
Cause: EEPROM chip is damaged.

Solution: Replace the AC drive.
Err23
Short
circuit to
ground
Cause & Solution:

1.
The motor is short circuited to the ground.
- Replace cable or motor.

2.
The upper IGBT is damaged.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err26
Accumulative
running time
reached
Cause: Accumulative running time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err27
User-defined
fault 1 
Cause: User-defined fault 1 is input via DI.

Solution: Reset the operation.
Err28
User-defined
fault 2 
Cause: User-defined fault 2 is input via DI.

Solution: Reset the operation.
Err29
Accumulative
power-on
time reached
Cause: Accumulative power-on time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err30
Off load
fault
Cause: The output current of AC drive is smaller than F9-64 (load loss detection level).

Solution: Check whether the load is disconnected or the setting of F9-64 and F9-65 (load lost detection time) satisfies actual running conditions.
Err31
PID
feedback
lost
during
running
Cause: PID feedback is smaller than the setting value of FA-26 (detection level of PID feedback loss).

Solution: Check PID feedback or set FA-26 properly.
Err40
Pulse-by-
pulse
current limit
fault
Cause & Solution:

1.
The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2.
The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err41
Motor
switchover
fault during
running
Cause: Motor switchover via terminal during drive running of the AC drive.

Solution: Perform motor switchover after the AC drive stops.
Err45
Motor
overtemperature
Cause & Solution:

1.
Cable connection of temperature sensor becomes loose
- Check cable connection of temperature sensor.

2
. The motor temperature is too high.
- Decrease carrier frequency or take other measures to cool the motor.
Err61
Braking
unit
overload
Cause: Resistance of braking resistor is too small.

Solution: Replace a braking resistor of larger resistance.
Err62
Short-circuit
of braking
circuit
Cause: Braking IGBT is abnormal.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
HC Fault Cause & Solution:

1.
The cable between the drive board and control board is in poor contact.

2.
The control board is damaged.
- Replace the AC drive.

3.
The motor or motor cable is short circuited to ground.
- Check whether short-circuit occurs on motor, motor cable or contactor.

4.
The mains voltage is too low.
- Check the power supply.

 

How to Read MD290 Faults via InoDriveShop

While the MD290 features a user-friendly keypad, diagnosing intermittent or complex faults is much easier using the InoDriveShop PC software. In 2026, this digital approach is the standard for efficient maintenance.

  • Fault Snapshot Data: When an “Err” code is triggered, the MD290 freezes its status parameters. Via the software or keypad group U0, you can review the exact Output Frequency, Current, and DC Bus Voltage at the moment of the trip. This is crucial for distinguishing between input power issues (like surges) and load issues.
  • I/O Verification: Many MD290 faults stem from external wiring (e.g., a missing Enable signal or a tripped external sensor). InoDriveShop allows you to visualize the state of all Digital Inputs (DI) and Outputs (DO) to confirm if the PLC signals are valid.
  • Trend Monitoring: For applications like fans or pumps, load fluctuates over time. The software’s oscilloscope function allows you to record long-term trends to see if a specific time of day or process stage is causing thermal overloads or over-current trips.

Frequently Asked Questions (FAQ)

Q: What is the difference between an Alarm and a Fault?

A: An Alarm (typically displayed as ‘A’ or ‘ALm’) serves as a warning—such as “Drive Overload Pre-alarm”—but the motor continues to run. A Fault (displayed as ‘Err’) is a protective stop that immediately disables the output to prevent hardware failure.

Q: How do I reset an Inovance MD290 fault?

A: You can reset the drive using the following methods:

  1. Pressing the STOP/RESET button on the keypad.
  2. Activating a Digital Input (DI) terminal programmed for the “Reset” function (Function 9).
  3. Cycling the power (turning the main breaker off, waiting for the LED to extinguish, and powering on again).

Q: Where is the fault history stored?

A: The MD290 stores the last 3 fault codes in parameters U0-00 (most recent), U0-01, and U0-02. The specific running parameters (volts, amps, etc.) recorded at the time of the most recent fault are stored in U0-03 through U0-17.