Mitsubishi FR-S500 Fault Codes List
Troubleshoot your Mitsubishi FR-S500 micro-drive using our fault code guide. Learn to use the Digital Dial for diagnostics, interpret E.OC1/E.OV1 errors, and clear alarm history.
FR-S500 Fault Codes Reference Table
Below is the complete list of fault codes and error messages for the S500 series. Please use the search function to find your specific code.
Mitsubishi FR-S500 Fault Codes List
| Fault Code and Meaning | Cause and Remedy |
|---|---|
|
OC1 (FR-PU04: OC During Acc) Overcurrent cut-off during acceleration |
Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during acceleration, the protective circuit is activated to stop the inverter output. Check points: Check for sudden acceleration. Check for output short-circuit/ground fault. Remedy:
|
|
OC2 (FR-PU04: Stedy Spd OC) Overcurrent cut-off during constant speed |
Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during constant-speed operation, the protective circuit is activated to stop the inverter output. Check points: Check for sudden load change. Check for output short-circuit/ground fault. Remedy:
|
|
OC3 (FR-PU04: OC During Dec) Overcurrent cut-off during deceleration |
Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during deceleration (other than acceleration or constant speed), the protective circuit is activated to stop the inverter output. Check points: Check for sudden speed reduction. Check for output short-circuit/ground fault. Check for too fast operation of motor's mechanical brake. Remedy:
|
|
OV1 (FR-PU04: OV During Acc) Regenerative overvoltage cut-off during acceleration |
Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during acceleration. May also be activated by surge voltage in power supply. Check points: Check for too slow acceleration. Remedy:
|
|
OV2 (FR-PU04: Stedy Spd OV) Regenerative overvoltage cut-off during constant speed |
Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during constant speed. May also be activated by surge voltage in power supply. Check points: Check for sudden load change. Remedy:
|
|
OV3 (FR-PU04: OV During Dec) Regenerative overvoltage cut-off during deceleration or stop |
Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during deceleration or stop. May also be activated by surge voltage in power supply. Check points: Check for sudden speed reduction. Remedy:
|
|
THM (FR-PU04: Motor Overload) Motor overload cut-off (electronic thermal overcurrent protection) |
Cause: The electronic overcurrent protection detects motor overheat due to overload or reduced cooling capability during low-speed operation. Check points: Check the motor for use under overload. Remedy:
|
|
THT (FR-PU04: Inv. Overload) Inverter overload cut-off (electronic thermal overcurrent protection) |
Cause: If a current of more than 150% of the rated output current flows and overcurrent shut-off does not occur (200% or less), inverse-time characteristics activate protection to stop the inverter output to protect output transistors. Check points: Check the motor for use under overload. Remedy:
|
|
FIN (FR-PU04: H/Sink O/Temp) Fin overheat |
Cause: If the cooling fin overheats, the overheat sensor is actuated to stop the inverter output. Check points: Check for too high ambient temperature. Check for cooling fin clogging. Remedy:
|
|
GF (FR-PU04: Ground Fault) Start-time output side ground fault overcurrent protection |
Cause: A ground fault overcurrent flowed due to a ground fault which occurred in the inverter's output (load) side. (Valid when Pr. 40 = "1"). Check points: Check for a ground fault in the motor and connection cable. Remedy:
|
|
OHT (FR-PU04: OH Fault) External thermal relay |
Cause: The external thermal relay (motor overheat protection) or internally mounted temperature relay in the motor switched on (contacts open). Check points: Check for motor overheating. Check that value of 7 (OH signal) is set correctly in Pr. 60 to Pr. 63. Remedy:
|
|
OLT (FR-PU04: Stll Prev STP) Stall prevention (overload) |
Cause: The running frequency has fallen to 0 by stall prevention operation activated. OL appears while stall prevention is being activated. Check points: Check the motor for use under overload. Remedy:
|
|
OPT (FR-PU04: Option Fault) Communication error |
Cause: A setting error or connection (connector) fault occurred during use of the RS-485 communication function. Check points: Check that the connector is plugged securely. Remedy:
|
|
PE (FR-PU04: Corrupt Memory) Parameter error |
Cause: A fault occurred in parameters stored (example: E2PROM fault). Check points: Check for too many number of parameter write times. Remedy:
|
| PUE PU disconnected |
Cause: Communication between inverter and PU is suspended (e.g., if the PU is disconnected with "1" set in parameter n17).
Remedy:
|
| RET Retry count |
Cause: If operation cannot be resumed properly within the number of retries set, this function stops the inverter output.
Remedy:
|
| CPU CPU error |
Cause: If the arithmetic operation of the built-in CPU does not end within a predetermined period, the inverter self-determines it as an alarm.
Remedy:
|
| FN Fan trouble |
Cause: The cooling fan stops due to a fault or operates differently from the setting of Pr. 76 "cooling fan operation selection".
Remedy:
|
| OL Stall prevention (overcurrent) |
Cause: Current of more than 150% of the rated inverter current flows in the motor during acceleration, constant speed, or deceleration. The function stops frequency change to prevent overcurrent shut-off.
Remedy:
|
| oL Stall prevention (overvoltage) |
Cause: During deceleration, if regenerative energy increases too much to exceed brake capability, this function stops the decrease in frequency to prevent overvoltage shut-off.
Remedy:
|
| PS PU stop (Stopped with PU STOP key) |
Cause: Pr. 75 "reset selection/PU stop selection" had been set and a stop was made by pressing the STOP/RESET key during external operation mode.
Remedy:
|
| UV Undervoltage |
Cause: Power supply voltage reduced below about 115VAC (230VAC for 400V series) resulting in control circuit issues.
Remedy:
|
| Er1 Write disable error |
Cause:
Remedy:
|
| Er2 Write-while-running / mode designation error |
Cause:
Remedy:
|
| Er3 Calibration error |
Cause: Analog input bias and gain calibration values are too close.
Remedy:
|
How to Read FR-S500 Faults via the Digital Dial
The FR-S500 is unique because it relies on a central Digital Setting Dial for both operation and diagnostics. Here is how to use the built-in interface to troubleshoot issues effectively:
- Active Fault Display: When the drive trips, the
display automatically switches to the Alarm Indication mode. It will
alternate between the fault code (e.g.,
E.THT) and the output frequency at the time of the trip (e.g.,0.0). - Accessing Alarm History: The S500 memory retains the last 4 alarms. To retrieve them:
- Press the MODE button until the display shows the parameter setting mode.
- Turn the Digital Dial to locate the alarm history parameters (often automated in the monitoring loop).
- The most recent alarm is displayed first. Turning the dial further will show older alarms (indicated as dot suffixes like
E.OC1.).
- Using External Keypads: If the onboard display is difficult to access, the FR-S500 is compatible with the FR-PU04 or FR-PU07 parameter units (connected via cable), which display full text descriptions of the faults rather than just codes.
Frequently Asked Questions (FAQ)
Q: What does a flashing “OL” mean on the FR-S500?
A: OL stands for Overload (Stall
Prevention). This is a Warning, not a Fault. It means the motor is
drawing too much current, and the drive is actively lowering the
frequency to prevent a full trip. If the load isn’t reduced, it will
eventually trip on E.THM (Thermal Overload).
Q: How do I reset the FR-S500 after a fault?
A: You can reset the drive using one of the following methods:
- Press the STOP/RESET button on the front panel.
- Cycle the main power (Wait for the LED display to fully extinguish before turning power back on).
- Connect the RES (Reset) terminal to the SD (Common) terminal for at least 0.1 seconds.
Q: Can I clear the fault history?
A: Yes. You can
clear the stored alarm history by performing an “All Clear” or
“Parameter Clear” operation using the parameter settings, usually found
under parameter Pr.CL (Parameter Clear) in the setup menu.