5681 PU Communication Fault in ABB ACS880 Drive
5681 PU Communication in the ABB ACS880 Drive indicates that the drive has detected a communication failure between the Control Unit (BCU) and the Power Unit (PU). The ACS880 continuously exchanges status, control, protection, and diagnostic information between the control board and the power unit through an internal communication link. If this communication is interrupted, corrupted, or does not match the configured hardware settings, the drive generates Fault 5681 to prevent unsafe operation.
This fault may also occur when the control unit power supply configuration does not match Parameter 95.04 – Control Board Supply, causing the control unit to operate in an unexpected power mode.
Possible Causes
- Incorrect setting of Parameter 95.04 – Control Board Supply.
- Communication failure between the control unit (BCU) and the power unit.
- Loose or damaged communication cable between the control unit and power unit.
- Faulty connector on the control board or power unit.
- Poor electrical contact in internal communication connectors.
- Control unit powered incorrectly or with an unstable auxiliary supply.
- Defective BCU (Bridge Control Unit).
- Faulty power unit communication interface.
- Internal communication bus failure.
- Defective xINT interface board.
- BAMU board not detected.
- Parallel-connected module communication failure.
- Communication link errors caused by electrical noise or interference.
- Internal transmitter FIFO errors.
- Firmware incompatibility between the control unit and power unit.
- Hardware failure after replacement of the control board or power unit.
- Internal PCB damage caused by electrical surge or aging components.
Solutions
- Cycle power to the drive and verify whether the fault clears.
- Verify the setting of Parameter 95.04 – Control Board Supply matches the actual control unit power configuration.
- Inspect all communication cables between the control unit and the power unit.
- Ensure all internal connectors are securely connected.
- Check the control unit for proper auxiliary power supply.
- Inspect communication connectors for bent pins or corrosion.
- Verify the power unit is operating normally.
- Check for damaged or loose internal wiring.
- Review the auxiliary fault code to identify the exact communication error source.
- Inspect the xINT interface board if the auxiliary code indicates it is missing.
- Verify the BAMU board is correctly installed and functioning.
- Update the drive firmware if recommended by ABB.
- Replace defective communication cables or connectors.
- Replace the faulty control board if communication hardware has failed.
- Replace the power unit if its communication interface is defective.
- Contact ABB technical support if the fault persists after hardware inspection.
Additional Information
The ABB ACS880 uses a high-speed internal communication link between the BCU (Bridge Control Unit) and the Power Unit (PU) to exchange operating commands, measurement data, status information, and protection signals.
If this communication is interrupted, the drive can no longer safely control the power electronics and immediately generates Fault 5681 to prevent unpredictable operation.
In addition to communication failures, this fault can also occur when the Control Board Supply configuration (Parameter 95.04) does not correspond to the actual hardware wiring. This mismatch prevents proper initialization and communication between the control unit and the power unit.
The drive provides an auxiliary fault code (format XXXY YYZZ) to help identify the exact source of the communication problem.
Auxiliary Code Interpretation
For parallel-connected power modules, the auxiliary code has the format XXXY YYZZ:
-
YYY – Identifies the affected BCU control unit channel.
- 0 – Broadcast communication.
- Other values identify the specific communication channel.
-
ZZ – Identifies the communication error source:
- 01 – Transmitter side link error.
- 02 – Transmitter side no communication.
- 03 – Receiver side link error.
- 04 – Receiver side no communication.
- 05 – Transmitter FIFO error (see XXX).
- 06 – xINT interface board not found.
- 07 – BAMU board not found.
-
XXX – FIFO transmitter error code (used only when ZZ = 05):
- 001 – Internal error (invalid call parameter).
- 002 – Internal error (configuration not supported).
- 003 – Transmission buffer full.
These auxiliary codes significantly simplify troubleshooting by identifying the exact location and type of communication failure.
Common Symptoms
- Drive trips with Fault 5681.
- Drive will not start.
- Fault appears immediately after power-up.
- Communication between the control unit and power unit is lost.
- Drive remains in fault state after reset.
- Control unit fails to detect the power unit.
- Fault occurs after replacing the control board or power unit.
- Fault appears intermittently due to loose communication connections.
- Auxiliary communication error code is displayed.
- Drive may stop unexpectedly during operation.
Recommended Troubleshooting Sequence
- Cycle power to the drive.
- Verify Parameter 95.04 – Control Board Supply.
- Check the control unit auxiliary power supply.
- Inspect communication cables between the control unit and power unit.
- Verify all internal connectors are securely connected.
- Inspect connectors for damaged pins or corrosion.
- Read and interpret the auxiliary fault code.
- Check the identified BCU communication channel (if applicable).
- Inspect the xINT interface board.
- Verify the BAMU board is installed correctly.
- Inspect the power unit communication interface.
- Update firmware if recommended by ABB.
- Replace defective communication hardware if necessary.
- Replace the control board or power unit if hardware failure is confirmed.
- Contact ABB technical support if the fault persists.
PU Communication Check Table
| Check Point | Action |
|---|---|
| Power cycle | Restart the drive |
| Parameter 95.04 | Verify Control Board Supply setting |
| Control unit power supply | Confirm correct auxiliary power |
| Communication cable | Inspect for loose or damaged connections |
| Internal connectors | Ensure secure connections |
| Connector pins | Check for bent pins or corrosion |
| Auxiliary fault code | Identify communication error source |
| BCU communication channel | Verify affected channel (parallel systems) |
| xINT board | Verify installation and operation |
| BAMU board | Confirm board is detected |
| Power unit | Inspect communication interface |
| Firmware | Update if recommended by ABB |
| Control board | Replace if communication hardware has failed |
| ABB technical support | Contact if the fault remains after inspection |
Preventive Maintenance Tips
- Inspect internal communication connectors during scheduled maintenance.
- Keep communication cables securely fastened and free from mechanical stress.
- Verify Parameter 95.04 after commissioning or hardware replacement.
- Protect the drive from electrical noise using proper grounding and shielding.
- Inspect internal boards for signs of overheating or contamination.
- Periodically check connector pins for corrosion or looseness.
- Ensure stable auxiliary power to the control unit.
- Update firmware according to ABB service recommendations.
- Use only ABB-approved replacement boards and communication components.
- Record recurring communication faults and auxiliary codes to assist long-term diagnostics.
Proper configuration of the Control Board Supply, secure communication connections between the control unit and power unit, careful interpretation of the auxiliary fault code, and routine inspection of the BCU, xINT board, BAMU board, and communication hardware will help prevent recurring 5681 PU Communication faults in ABB ACS880 drives, ensuring reliable internal communication, dependable drive operation, and long-term system availability.