Allen Bradley PowerFlex 523 Drive Fault Codes List

Complete guide to Allen Bradley PowerFlex 523 fault codes. Learn to read Fxxx codes, use Connected Components Workbench (CCW), and reset trips to restore operation.

PowerFlex 523 Fault Codes Reference Table

Fault Codes Cause & Solutions
F000
No Fault 
Cause: No fault present.
F002
Auxiliary
Input
Cause : External trip (Auxiliary) input.

Solution:

- Check remote wiring.
- Verify communications programming for intentional fault.
F003
Power Loss
Cause: Single-phase operation detected with excessive load.

Solution:

- Monitor the incoming AC line for low voltage or line power interruption.
- Check input fuses.
- Reduce load.
F004
UnderVoltage
Cause: DC bus voltage fell below the min value.

Solution: Monitor the incoming AC line for low voltage or line power interruption.
F005
OverVoltage
Cause: DC bus voltage exceeded max value.

Solution:

- Monitor the AC line for high line voltage or transient conditions.
- Bus overvoltage can also be caused by motor regeneration.
- Extend the decel time or install dynamic brake option.
F006
Motor
Stalled 
Cause: Drive is unable to accelerate or decelerate motor.

Solution:

- Increase P041, A442, A444, A446 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A484, A485 [Current Limit x] for too long.
- Check for overhauling load.
F007
Motor
Overload
Cause: Internal electronic overload trip.

Solution:

- An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current].
- Verify A530 [Boost Select] setting.
F008
Heatsink
OvrTmp
Cause: Heatsink/Power Module temperature exceeds a predefined value.

Solution:

- Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature.
- Check fan.
F009
CC OvrTmp
Cause: Control module temperature exceeds a predefined value.

Solution:

- Check product ambient temperature.
- Check for airflow obstruction.
- Check for dirt or debris.
- Check fan.
F012
HW
OverCurrent
Cause: The drive output current has exceeded the hardware current limit.

Solution:

- Check programming.
- Check for excess load, improper A530 [Boost Select] setting, DC brake volts set too high or other causes of excess current.
F013
Ground
Fault
Cause: A current path to earth ground has been detected at one or more of the drive output terminals.

Solution:

- Check the motor and external wiring to the drive output terminals for a grounded condition.
F015
Load Loss
Cause: The output torque current is below the value that is programmed in A490 [Load Loss Level] for a time period greater than the time programmed in A491 [Load Loss Time].

Solution:

- Verify connections between motor and load.
- Verify level and time requirements.
F021
Output Phase
Loss 
Cause: Output Phase Loss (if enabled). Configure with A557 [Out Phas Loss En].

Solution:

- Verify motor wiring.
- Verify motor.
F029
Analog In
Loss
Cause: An analog input is configured to fault on signal loss. A signal loss has occurred. Configure with t094 [Anlg In V Loss] or t097 [Anlg In mA Loss].

Solution:

- Check for broken/loose connections at inputs.
- Check parameters.
F033
Auto Rstrt
Tries
Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A541 [Auto Rstrt Tries].

Solution: Correct the cause of the fault and manually clear.
F038
Phase U
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F039
Phase V
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F040
Phase W
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F041
Phase
UV Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F042
Phase
UW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F043
Phase
VW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F048
Params
Defaulted 
Cause: The drive was commanded to write default values to EEPROM.

Solution:

- Clear the fault or cycle power to the drive.
- Program the drive parameters as needed.
F059
Safety
Open 1
Cause: Both of the safety inputs (Safety 1, Safety 2) are not enabled. Configure with t105 [Safety Open En].

Solution:

- Check safety input signals.
- If not using safety, verify and tighten jumper for I/O terminals S1, S2, and S+.
F063
SW
OverCurrent
Cause: Programmed A486, A488 [Shear Pinx Level] has been exceeded for a time period greater than the time programmed in A487, A489 [Shear Pin x Time].

Solution:

- Verify connections between motor and load.
- Verify level and time requirements.
F064
Drive
Overload
Cause: Drive overload rating has been exceeded.

Solution: Reduce load or extend Accel Time.
F070
Power Unit
Cause: Failure has been detected in the drive power section.

Solution:

- Check that max ambient temperature has not been exceeded.
- Cycle power.
- Replace drive if fault cannot be cleared.
F071
DSI Net
Loss 
Cause: Control over the Modbus or DSI communication link has been interrupted.

Solution:

- Cycle power.
- Check communications cabling.
- Check Modbus or DSI setting.
- Check Modbus or DSI status.
F072
Opt Net
Loss
Cause: Control over the network option card’s remote network has been interrupted.

Solution:

- Cycle power.
- Check communications cabling.
- Check network adapter setting.
- Check external network status.
F073
EN Net
Loss
Cause: Control through the embedded EtherNet/IP adapter has been interrupted.

Solution:

- Cycle power.
- Check communications cabling.
- Check EtherNet/IP setting.
- Check external network status.
F080
Autotune
Failure
Cause: The autotune function was either canceled by the user or failed.

Solution: Restart procedure.
F081
DSI Comm
Loss 
Cause: Communications between the drive and the Modbus or DSI master device have been interrupted.

Solution:

- Cycle power.
- Check communications cabling.
- Check Modbus or DSI setting.
- Check Modbus or DSI status.
- Modify using C125 [Comm Loss Action].
- Connecting I/O terminals C1 and C2 to ground may improve noise immunity.
- Replace wiring, Modbus master device, or control module.
F082
Opt Comm
Loss 
Cause: Communications between the drive and the network option card have been interrupted.

Solution:

- Cycle power.
- Reinstall option card in drive.
- Modify using C125 [Comm Loss Action].
- Replace wiring, port expander, option card, or control module.
F083
EN Comm
Loss
Cause: Internal communications between the drive and the embedded EtherNet/IP adapter have been interrupted.

Solution:

- Cycle power.
- Check EtherNet/IP setting.
- Check drive’s Ethernet settings and diagnostic parameters.
- Modify using C125 [Comm Loss Action].
- Replace wiring, Ethernet switch, or control module.
F091
Encoder
Loss
Cause: Requires differential encoder. One of the 2 encoder channel signals is missing.

Solution:

- Check Wiring.
- If P047, P049, P051 [Speed Referencex] = 16 “Positioning” and A535 [Motor Fdbk Type] = 5 “Quad Check”, swap the Encoder channel inputs or swap any two motor leads.
- Replace encoder.
F094
Function
Loss
Cause: “Freeze-Fire” (Function Loss) input is inactive, input to the programmed terminal is open.

Solution: Close input to the terminal and cycle power.
F100
Parameter
Chksum
Cause: Drive parameter non-volatile storage is corrupted.

Solution: Set P053 [Reset To Defalts] to 2 “Factory Rset”.
F101
External
Storage 
Cause: External non-volatile storage has failed.

Solution: Set P053 [Reset To Defalts] to 2 “Factory Rset”.
F105
C Connect
Err 
Cause: Control module was disconnected while drive was powered.

Solution:

- Clear fault and verify all parameter settings.
- Do not remove or install the control module while power is applied.
F106
Incompat
C-P 
Cause: The PowerFlex 525 control module does not support power modules with 0.25 HP power rating.

Solution:

- Change to a different power module.
- Change to a PowerFlex 523 control module.
F107
Replaced
C-P 
Cause: The control module could not recognize the power module.
- Hardware failure.

Solution:

- Change to a different power module.
- Replace control module if changing power module does not work.
F109
Mismatch
C-P 
Cause: The control module was mounted to a different drive type power module.

Solution: Set P053 [Reset To Defalts] to 3 “Power Reset”.
F110
Keypad
Membrane 
Cause: Keypad membrane failure / disconnected.

Solution:

- Cycle power.
- Replace control module if fault cannot be cleared.
F111
Safety
Hardware
Cause: Safety input enable hardware malfunction. One of the safety inputs is not enabled.

Solution:

- Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2, and S+.
- Replace control module if fault cannot be cleared.
F114
uC Failure 
Cause: Microprocessor failure.

Solution:

- Cycle power.
- Verify grounding requirements.
- Replace control module if fault cannot be cleared.
F122
I/O Board
Fail
Cause: Failure has been detected in the drive control and I/O section.

Solution:

- Cycle power.
- Replace drive or control module if fault cannot be cleared.
F125
Flash
Update  Req
Cause: The firmware in the drive is corrupt, mismatched, or incompatible with the hardware.

Solution: Perform a firmware flash update operation to attempt to load a valid set of firmware.
F126
Non
Recoverablw
Err
Cause: A nonrecoverable firmware or hardware error was detected. The drive was automatically stopped and reset.

Solution:

- Clear fault or cycle power to the drive.
- Replace drive or control module if fault cannot be cleared.
F127
DSI Flash
UpdatReq
Cause: A critical problem with the firmware was detected and the drive is running using backup firmware that only supports DSI communications.

Solution: Perform a firmware flash update operation using DSI communications to attempt to load a valid set of firmware.

How to Read PowerFlex 523 Faults via Software

While the built-in LCD display provides basic codes, connecting your PC to the drive via USB allows for deeper analysis. For 2026 diagnostics, it is recommended to use Connected Components Workbench (CCW).

  • Fault History Parameters: Unlike some drives that store logs in a separate menu, the PowerFlex 523 stores the last three faults in specific parameters: b007 (Most Recent Fault), b008, and b009.
  • Drive Status Indicators: Using CCW, you can view live monitoring of the DC Bus Voltage, Output Current, and Logic Command status at the exact moment of operation to diagnose intermittent trips.
  • MainsFree™ Programming: The PowerFlex 523 allows you to upload fault data and parameters via USB even when the main power is disconnected, provided the control module is accessible.

Frequently Asked Questions (FAQ)

Q: What is the difference between a Fault and an Alarm?

A: A Fault (Fxxx) indicates a critical condition that stops the drive to protect equipment (e.g., F005 OverVoltage). An Alarm indicates a condition that may require attention but allows the drive to continue running. Alarms are split into Type 1 (txxx) and Type 2 (axxx).

Q: How do I reset a PowerFlex 523 fault?

A: You can reset the drive using one of the following methods:

  • Press the Stop/Clear key on the keypad.
  • Toggle a Digital Input configured for “Clear Fault” (typically configured in parameters t062-t063).
  • Cycle power to the drive (turn it off and back on).

Q: Why does my drive say “F013 Ground Fault”?

A: This is one of the most common faults. It detects a current path to the earth ground at one or more of the drive output terminals. Check your motor cabling for nicks, moisture in the motor peckerhead, or insulation failure using a Megger test.

Comments

Popular posts from this blog

Allen Bradley Kinetix 5500 Drive Fault Codes List

Danfoss VACON 100 FLOW Drive Fault Codes List

ABB ACH580 Drive Fault Codes List