Danfoss VACON 10 Fault Codes List
Access the complete reference guide for Danfoss VACON 10 micro drive fault codes. Learn to diagnose F1 Overcurrent, reset trips, and back up parameters via Vacon Live.
VACON 10 Fault Codes Reference Table
VACON 10 Fault Codes Reference Table
VACON 10 Fault Codes Reference Table
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Overcurrent |
Cause: Frequency converter has detected too high a current (>4*IN) in the motor cable.
Remedy:
|
| 2 Overvoltage |
Cause: The DC-link voltage has exceeded the internal safety limit.
Remedy:
|
| 3 Earth fault |
Cause: Current measurement has detected extra leakage current at start.
Remedy:
|
| 8 System fault |
Cause:
Remedy:
|
| 9 Undervoltage |
Cause: The DC-link voltage has gone below the internal safety limit.
Remedy:
|
| 11 Output phase fault |
Cause: Current measurement has detected that there is no current in one motor phase.
Remedy:
|
| 13 Frequency converter undertemperature |
Cause: Heat sink temperature is under -10 °C.
Remedy:
|
| 14 Frequency converter overtemperature |
Cause: Heat sink is overheated.
Remedy:
|
| 15 Motor stalled |
Cause: Motor stall protection has tripped.
Remedy:
|
| 16 Motor overtemperature |
Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded.
Remedy:
|
| 17 Motor underload |
Cause: Motor underload protection has tripped.
Remedy:
|
| 22 EEPROM check sum fault |
Cause: Parameter save fault.
Remedy:
|
| 25 Microcontroller watchdog fault |
Cause:
Remedy:
|
| 27 Back EMF protection |
Cause: Drive has detected that the magnetized motor is running in start situation.
Remedy:
|
| 29 Thermistor fault |
Cause: The thermistor input of option board has detected increase.
Remedy:
|
| 34 Internal bus communication |
Cause: Ambient interference or defective hardware.
Remedy:
|
| 35 Application fault |
Cause: Application is not working properly.
Remedy:
|
| 41 IGBT Overtemperature |
Cause: Over temperature alarm is issued when the IGBT switch temperature exceeds 110 °C.
Remedy:
|
| 50 Analog input select |
Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V (selected signal range 4 to 20 mA or 2 to 10 V).
Remedy:
|
| 51 External fault |
Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active.
Remedy:
|
| 53 Fieldbus fault |
Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken.
Remedy:
|
| 55 Wrong run fault (FWD/REV conflict) |
Cause: Run forward and backward at the same time.
Remedy:
|
| 57 Identification fault |
Cause: Identification run has failed.
Remedy:
|
| 111 Temperature fault |
Cause: Over low or over high temperature.
Remedy:
|
How to Read VACON 10 Faults via Keypad & Vacon Live
The VACON 10 is designed for simplicity, but accessing deep diagnostics in 2026 requires specific tools:
- The Built-in Display: The drive features a basic LED/LCD screen.
- Active Faults: When the drive trips, the “F” code flashes. You can navigate to the Monitor Menu (M3) to view the “Fault History” (V3.4) which stores the last 9 faults.
- Status LEDs: The drive face has three LEDs. A blinking Red LED indicates an active fault that stops the motor.
- Vacon Live (PC Software): To connect a PC, you need the optional MCA Adapter (Micro Communications Adapter) and a USB cable.
- Parameter Backup: Since VACON 10 drives are cost-effective, they are often replaced rather than repaired. Using Vacon Live to save a parameter file (.vc1) allows you to clone the settings to a new drive in minutes.
- Diagnostics: The software allows you to see the drive status word and internal DC bus voltage, helping rule out external power supply issues.
Frequently Asked Questions (FAQ)
Q: What is the difference between a Fault (F) and an Alarm (A)?
A:
- Alarm (A-Code): The drive detects an abnormal condition (e.g., A50 “Analog Input Low”) but continues to run. This acts as a warning.
- Fault (F-Code): The drive stops modulation immediately (Trips) to protect the hardware (e.g., F1 “Overcurrent”). You must fix the issue and manually reset the drive.
Q: How do I reset a VACON 10 fault?
A:
- Press the Stop/Reset button on the keypad (if Keypad Control is active or configured).
- Toggle the Digital Input assigned to “Fault Reset” (typically DIN3 in the standard API).
- Cycle the mains power (wait for the display to turn off completely).
Q: Why does the drive trip on “F2” (Overvoltage) during stopping?
A: The VACON 10 has a small internal DC bus capacitance.
- If you try to stop a high-inertia load (like a fan) too quickly, the energy regenerates back into the drive.
- Fix: Increase the Deceleration Time (Parameter P1.4).
Q: Is the VACON 10 compatible with VACON 20 parts?
A: They are very similar, but the VACON 20 has more advanced features (like built-in PLC functionality). While connection cables (MCA) are often shared, parameter files may not be directly transferable without conversion tools.