Danfoss VACON 20 Cold Plate Fault Codes List
Access the complete reference guide for Danfoss VACON 20 Cold Plate drive fault codes. Learn to diagnose thermal faults (F13/F14), check mounting issues, and use VACON Live.
VACON 20 Cold Plate Fault Codes Reference Table
VACON Fault Tracing
VACON Fault Codes
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Overcurrent |
Cause: Frequency converter has detected too high a current (>4*In) in the motor cable:
Remedy:
|
| 2 Overvoltage |
Cause: The DC-link voltage has exceeded the internal safety limit:
Remedy:
|
| 3 Earth fault |
Cause: Current measurement has detected extra leakage current at start:
Remedy:
|
| 8 System fault |
Cause:
Remedy:
|
| 9 Under voltage |
Cause: The DC-link voltage has gone below the internal safety limit. Most probable cause: supply voltage is too low; frequency converter internal fault; Power outages.
Remedy:
|
| 10 Input phase fault |
Cause: Input phase is missing.
Remedy:
|
| 11 Output phase fault |
Cause: Current measurement has detected that there is no current in one motor phase.
Remedy:
|
| 13 Frequency converter under temperature |
Cause: Heat sink temperature is under -10 °C.
Remedy:
|
| 14 Frequency converter over temperature |
Cause: Heat sink is overheated.
Remedy:
|
| 15 Motor stalled |
Cause: Motor stall protection has tripped.
Remedy:
|
| 16 Motor over temperature |
Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded.
Remedy:
|
| 17 Motor underload |
Cause: Motor underload protection has tripped.
Remedy:
|
| 22 EEPROM checksum fault |
Cause: Parameter save fault:
Remedy:
|
| 25 Microcontroller watchdog fault |
Cause:
Remedy:
|
| 27 Back EMF protection |
Cause: Drive has detected that the magnetized motor is running in start situation.
Remedy:
|
| 29 Thermistor fault |
Cause: The thermistor input of option board has detected increase of the motor temperature.
Remedy:
|
| 34 Internal bus communication |
Cause: Ambient interference or defective hardware.
Remedy:
|
| 35 Application fault |
Cause: Application is not working properly.
Remedy:
|
| 41 IGBT Overtemperature |
Cause: Overtemperature alarm is issued when the IGBT switch temperature exceeds 110 °C.
Remedy:
|
| 50 Analog input select 20% - 100% |
Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V.
Remedy:
|
| 51 External fault |
Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active.
Remedy:
|
| 52 Door Panel fault |
Cause: Control place is keypad, but door panel has been disconnected.
Remedy:
|
| 53 Fieldbus fault |
Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken.
Remedy:
|
| 54 Slot fault |
Cause: The connection between optional board and API has been broken.
Remedy:
|
| 55 Wrong run fault (FWD/REV conflict) |
Cause: Run forward and backward are high at the same time.
Remedy:
|
| 57 Identification fault |
Cause: Identification run has failed.
Remedy:
|
| 111 Temperature fault |
Cause: Over low or over high temperature.
Remedy:
|
How to Read VACON 20 Faults via VACON Live
Because the VACON 20 Cold Plate is often buried deep inside machinery where the display is not visible, PC tools are essential for diagnostics in 2026:
- VACON Live (PC Software): Connect your laptop via the MCA Adapter (USB tool).
- Datalogger: VACON Live allows you to trigger a trace on specific events. For Cold Plate drives, graphing the Unit Temperature vs. Motor Current is vital to see if the drive heats up too quickly under load.
- Fault History: Navigate to the “Fault History” tab to see the sub-codes (Source Info) which pinpoint exactly which internal component triggered the alarm.
- Built-in Display: The drive features a standard 7-segment display or an optional text keypad.
- F (Fault): The drive stops.
- A (Alarm): The drive runs but warns of an issue.
- MCA ParamLoader: This battery-operated tool allows you to copy parameters from a failed drive to a replacement unit without mains power, which is critical for quick swaps in the field.
Frequently Asked Questions (FAQ)
Q: Why does my VACON 20 Cold Plate trip on “F13” or “F14” (Overtemperature)?
A: Unlike standard drives, the Cold Plate relies on your mounting surface.
- Surface Flatness: Ensure the mounting plate is perfectly flat and clean.
- Thermal Paste: Verify that thermal grease was applied correctly between the drive and the heatsink.
- Liquid Flow: If mounted on a liquid-cooled plate, check for blockages or air bubbles in the coolant line.
Q: How do I reset a VACON 20 fault?
A:
- Press the Stop/Reset button on the keypad.
- Toggle the Digital Input configured for Reset (Default is typically DI3).
- Cycle the 24V control power and main mains power.
Q: What does “F1” (Overcurrent) usually indicate?
A: This means the drive detected a current spike.
- Check for a short circuit in the motor cable.
- If the fault occurs during acceleration, increase the Ramp Time.
- Perform a Motor Identification Run (ID Run) to ensure the drive matches the motor characteristics.