Danfoss VACON 20X Drive Fault Codes List
Access the complete reference guide for Danfoss VACON 20X decentralized drive fault codes. Learn to diagnose IP66 drive errors, use VACON Live, and troubleshoot F53 fieldbus faults.
VACON 20X Fault Codes Reference Table
VACON 20X Fault Codes Reference Table
VACON 20X Fault Codes Reference Table
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| F1 Overcurrent |
Cause: AC drive has detected too high a current (>4*IH) in the motor cable:
Remedy:
|
| F2 Overvoltage |
Cause: The DC-link voltage has exceeded the limits defined.
Remedy:
|
| F3 Earth fault |
Cause: Current measurement has detected that the sum of motor phase current is not zero.
Remedy: Check motor cables and motor. |
| F8 (Subcode 84) System Fault |
Cause: MPI communication crc error Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 89) System Fault |
Cause: HMI receives buffer overflow Remedy: Check PC-drive cable. Try to reduce ambient noise. |
| F8 (Subcode 90) System Fault |
Cause: Modbus receives buffer overflow Remedy:
|
| F8 (Subcode 93) System Fault |
Cause: Power identification error Remedy: Try to reduce ambient noise. Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 97) System Fault |
Cause: MPI off line error Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 98) System Fault |
Cause: MPI driver error Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 99) System Fault |
Cause: Option board driver error Remedy: Check contact in option board slot. Try to reduce ambient noise; Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 100) System Fault |
Cause: Option board configuration error Remedy: Check contact in option board slot. Try to reduce ambient noise; Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 101) System Fault |
Cause: Modbus buffer overflow Remedy:
|
| F8 (Subcode 104) System Fault |
Cause: Option board channel full Remedy: Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 105) System Fault |
Cause: Option board memory allocation fail Remedy: Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 106) System Fault |
Cause: Option board Object queue full Remedy: Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 107) System Fault |
Cause: Option board HMI queue full Remedy: Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 108) System Fault |
Cause: Option board SPI queue full Remedy: Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 111) System Fault |
Cause: Parameter copy error Remedy: Check if parameter set is compatible with drive. Do not remove Keypad until copy is finished. |
| F8 (Subcode 113) System Fault |
Cause: Frequency detective timer overflow Remedy: Check keypad contacts. Try to reduce ambient noise. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 114) System Fault |
Cause: PC control time out fault Remedy: Do not close VACON® Live when PC control is active. Check PC-Drive cable. Try to reduce ambient noise. |
| F8 (Subcode 115) System Fault |
Cause: DeviceProperty data format Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F8 (Subcode 120) System Fault |
Cause: Task stack overflow Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F9 Undervoltage |
Cause: DC-link voltage is under the voltage limits defined.
NOTE! This fault is activated only if the drive is in Run state. Remedy: In case of temporary supply voltage break reset the fault and restart the AC drive. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact the distributor near to you. |
| F10 Input phase |
Cause: Input line phase is missing. Remedy: Check supply voltage, fuses and cable. |
| F11 Output phase |
Cause: Current measurement has detected that there is no current in one motor phase. Remedy: Check motor cables and motor. |
| F13 AC drive undertemperature |
Cause: Too low temperature measured in power unit’s heatsink or board. Heatsink temperature is under -10°C. Remedy: Check the ambient temperature. |
| F14 AC drive overtemperature |
Cause: Too high temperature measured in power unit’s heatsink or board. Heatsink temperature is over 100°C. Remedy:
|
| F15 Motor stalled |
Cause: Motor is stalled. Remedy: Check motor and load. Insufficient motor power, check motor stall protection parametrization. |
| F16 Motor overtemperature |
Cause: Motor is overloaded. Remedy: Decrease motor load. If no motor overload exists, check the temperature model parameters. |
| F17 Motor underload |
Cause: Motor is under loaded Remedy: Check load. Check underload protection parametrization. |
| F19 Power overload |
Cause: Supervision for drive power Remedy: Drive power is too high: decrease load. |
| F25 Watchdog |
Cause: Error in the microprocessor monitoring. Malfunction. Component fault. Remedy: Reset the fault and restart. If the fault occurs again, please contact your closest VACON® representative. |
| F27 Back EMF |
Cause: Protection of unit when starting with rotating motor Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F30 STO fault |
Cause: Safe torque off signal does not allow drive to be set as ready Remedy: Reset the fault and restart. Should the fault re-occur, contact the distributor near to you. |
| F35 (Subcode 0) Application error |
Cause: Firmware Interface version between Application and Control not matching Remedy: Load a compatible application. Please contact your closest VACON® representative. |
| F35 (Subcode 1) Application error |
Cause: Application software flash error Remedy: Reload Application. |
| F35 (Subcode 2) Application error |
Cause: Application header error Remedy: Load a compatible application. Please contact your closest VACON® representative. |
| F41 IGBT temp |
Cause: IGBT temperature (UnitTemperature + I2T) too high Remedy:
|
| F50 4 mA fault (Analog input) |
Cause: Selected signal range: 4...20 mA (see Application Manual). Current less than 4 mA. Signal line broken/detached. The signal source is faulty. Remedy: Check the analog input’s current source and circuit. |
| F51 External fault |
Cause: Error message on digital input. The digital input was programmed as an input for external error messages. The input is active. Remedy: Check the programming and check the device indicated by the error message. Check the cabling for the respective device as well. |
| F52 Keypad Communication fault |
Cause: The connection between the control keypad and the AC drive is broken. Remedy: Check keypad connection and keypad cable. |
| F53 Fieldbus communication fault |
Cause: The data connection between the fieldbus master and fieldbus board is broken. Remedy: Check installation and fieldbus master. |
| F54 Fieldbus Interface error |
Cause: Defective option board or slot Remedy: Check board and slot. |
| F55 Wrong run command |
Cause: Wrong run alarm and stop command. Run forward and backward are activated at the same time. Remedy: Run forward and backward are activated at the same time |
| F56 Temperature |
Cause: Temperature fault. Board OPTBH is installed and measured temperature is above (or below) the limit. Remedy: Board OPTBH is installed and measured temperature is above (or below) the limit |
| F57 Identification |
Cause: Identification alarm. Motor identification has not been successfully completed. Remedy: Motor identification has not been successfully completed |
| F63 Quick Stop |
Cause: Quick Stop activated. Remedy: The drive has been stopped with Quick Stop digital input or Quick Stop command by fieldbus. |
How to Read VACON 20X Faults via Keypad & VACON Live
Because the VACON 20X is often mounted in hard-to-reach locations (e.g., high on a conveyor or under a machine), diagnostics in 2026 require specific tools:
- Membrane Keypad (LCD): The built-in display is the primary status indicator.
- Active Faults: If the drive trips, the display flashes the Fault Code (e.g., F1) and the Fault ID (sub-code).
- Fault History: Navigate to Menu M4 to view the history. This is critical for intermittent issues like “Motor Stall” or “Under Voltage” that may clear before you arrive at the machine.
- VACON Live (PC Software): Unlike VLT drives that use MCT 10, VACON drives utilize VACON Live. Connect your laptop via the USB/RS-485 adapter cable (VACON serial interface).
- Datalogger: Use the software to trigger recordings based on fault events. This allows you to see the DC Bus Voltage and Motor Current exactly when the trip occurred.
- Mains Switch: Many VACON 20X units feature a large black mains isolator switch on the front. If the display is dead, ensure this switch hasn’t been locked out during maintenance.
Frequently Asked Questions (FAQ)
Q: What is the difference between a Fault (F) and an Alarm (A)?
A:
- Fault (F): The drive stops modulation immediately. The motor coasts to a stop. You must acknowledge the fault to restart.
- Alarm (A): The drive continues running but warns of an abnormal condition (e.g., A50 “Over Temperature”). If the issue is not resolved, it usually escalates to a Fault.
Q: How do I reset a VACON 20X fault?
A:
- Press the Reset button on the membrane keypad.
- Toggle the Digital Input assigned to “Fault Reset” (typically DIN3 or DIN4).
- Cycle the main power (turn the front isolator switch to OFF, wait for the screen to die, then turn ON).
Q: Why do I get “F53” (Fieldbus Fault)?
A: The VACON 20X is often networked via PROFINET or EtherNet/IP.
- F53 means the drive lost communication with the PLC.
- Check the M12 communication cables; vibrations on conveyors can loosen these connectors.
- Verify the PLC is in “Run” mode.
Q: What does “F1” (Overcurrent) usually mean at startup?
A: F1 is a hard trip indicating current exceeded the hardware limit.
- Check for a short circuit in the motor cable (water ingress is common in IP66 applications).
- Ensure the Acceleration Time is not too short for the load.
- If the motor is spinning when the drive starts (windmilling fan), enable the “Flying Start” function.
Comments