Danfoss VACON NXP Air Cooled Fault Codes List
Access the complete reference guide for Danfoss VACON NXP Air Cooled drive fault codes. Learn to diagnose F1 Overcurrent subcodes, use VACON NCDrive, and troubleshoot system bus errors.
VACON NXP Fault Codes Reference Table
VACON NX All-in-One Faults and Alarms
VACON NX Fault Tracing Guide
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Fault 1, Subcode S1 Overcurrent - Hardware trip |
Cause: There is too high a current in the motor cable. Its cause can be 1 of the following:
Remedy:
|
| Fault 1, Subcode S2 Overcurrent - Current cutter supervision (VACON® NXS) |
Cause: There is too high a current in the motor cable. Its cause can be 1 of the following:
Remedy:
|
| Fault 1, Subcode S3 Overcurrent - Current limit controller supervision |
Cause: There is too high a current in the motor cable. Its cause can be 1 of the following:
Remedy:
|
| Fault 1, Subcode S4 Overcurrent - Software-based overcurrent fault |
Cause: There is too high a current in the motor cable. Its cause can be 1 of the following:
Remedy:
|
| Fault 2, Subcode S1 Overvoltage - Hardware trip |
Cause: The DC-link voltage is higher than the limits.
Remedy:
|
| Fault 2, Subcode S2 Overvoltage - Overvoltage control supervision |
Cause: The DC-link voltage is higher than the limits.
Remedy:
|
| Fault 2, Subcode S3 Overvoltage - LCL capacitor overvoltage ripple |
Cause: AFE LCL filter capacitor ripple voltage is too high. Remedy:
|
| Fault 3 Earth fault |
Cause: The measurement of current tells that the sum of the motor phase current is not zero.
Remedy:
|
| Fault 5 Charging switch |
Cause: The charging switch is open, when the START command is given.
Remedy:
|
| Fault 6 Emergency stop |
Cause: Stop signal has been given from the option board. Remedy:
|
| Fault 7 Saturation trip |
Cause:
Remedy: This fault cannot be reset from the control panel.
|
| Fault 8, Subcode S1 System fault - ASIC phase feedback |
Cause:
Remedy:
|
| Fault 8, Subcode S4 System fault - ASIC trip |
Cause:
Remedy:
|
| Fault 8, Subcode S5 System fault - Disturbance in VaconBus |
Cause:
Remedy:
|
| Fault 8, Subcode S6 System fault - Feedback of charging switch |
Cause:
Remedy:
|
| Fault 8, Subcode S7 System fault - Charging switch |
Cause:
Remedy:
|
| Fault 8, Subcode S8 System fault - No power to driver card |
Cause:
Remedy:
|
| Fault 8, Subcode S9 System fault - Power unit communication (TX) |
Cause:
Remedy:
|
| Fault 8, Subcode S10 System fault - Power unit communication (Trip) |
Cause:
Remedy:
|
| Fault 8, Subcode S11 System fault - Power unit comm. (Measurement) |
Cause:
Remedy:
|
| Fault 8, Subcode S12 System fault - System bus fault (slot D or E) |
Cause: Error in system bus option board (OPTD1 or OPTD2) in slot D or E.
Remedy:
|
| Fault 8, Subcode S30 System fault - OPTAF: STO channels are different from each other |
Cause: The Safe Disable inputs are in different states. It is not allowed according to EN954-1, category 3. This fault occurs when the Safe Disable inputs are in different states for more than 5 s. Remedy:
|
| Fault 8, Subcode S31 System fault - OPTAF: Thermistor short circuit detected |
Cause: Thermistor short circuit detected. Remedy:
|
| Fault 8, Subcode S32 System fault - OPTAF board has been removed |
Cause: OPTAF board has been removed. It is not allowed to remove the OPTAF board once the software has recognized it. Remedy:
|
| Fault 8, Subcode S33 System fault - OPTAF: EEPROM error |
Cause: OPTAF board EEPROM error (checksum, not answering and so on). Remedy:
|
| Fault 8, Subcode S34 System fault - OPTAF: Voltage problem |
Cause: OPTAF supply voltage hardware problem detected. Remedy:
|
| Fault 8, Subcode S35 System fault - OPTAF: Overvoltage |
Cause: OPTAF supply voltage hardware problem detected. Remedy:
|
| Fault 8, Subcode S36 OPTAF: Undervoltage |
Cause: OPTAF supply voltage hardware problem detected. Remedy:
|
| Fault 8, Subcode S37 OPTAF: Test pulse is not detected in both STO channels |
Cause: Single hardware problem detected in Safe Disable inputs. Remedy:
|
| Fault 8, Subcode S38 OPTAF: Test pulse is not detected in STO channel 1 |
Cause: Single hardware problem detected in Safe Disable inputs. Remedy:
|
| Fault 8, Subcode S39 OPTAF: Test pulse is not detected in STO channel 2 |
Cause: Single hardware problem detected in Safe Disable inputs. Remedy:
|
| Fault 8, Subcode S40 OPTAF: ASIC trip ETR is not set, even if STO channel 1 is active |
Cause: Single hardware problem detected in Safe Disable inputs. Remedy:
|
| Fault 8, Subcode S41 OPTAF: STO channels are not active when the thermistor trip is active |
Cause: Single hardware problem detected in the thermistor input. Remedy:
|
| Fault 8, Subcode S42 OPTAF: Test pulse low is not detected on thermistor |
Cause: Single hardware problem detected in the thermistor input. Remedy:
|
| Fault 8, Subcode S43 OPTAF: Test pulse high is not detected on thermistor |
Cause: Single hardware problem detected in the thermistor input. Remedy:
|
| Fault 8, Subcode S44 OPTAF: STO channel 1 is not active, even if the analog input supervision indicates |
Cause: Single hardware problem detected in Safe Disable inputs or in the thermistor input. Remedy:
|
| Fault 8, Subcode S45 OPTAF: STO channel 2 is not active, even if the analog input supervision indicates |
Cause: Single hardware problem detected in Safe Disable inputs or in the thermistor input. Remedy:
|
| Fault 8, Subcode S46 OPTAF: Thermistor or analog input is not set, even if STO is active |
Cause: Single hardware problem detected in Safe Disable inputs or in the thermistor input. Remedy:
|
| Fault 8, Subcode S47 OPTAF: Board mounted in old NXP control board with no safety hardware |
Cause: OPTAF board mounted in old VACON® NXP control board, which is not equipped with the Safe Disable function. Remedy:
|
| Fault 8, Subcode S48 OPTAF: Mismatch between Therm Trip (HW) parameter and jumper setting |
Cause: The parameter Expander boards/ SlotB/ Therm Trip(HW) is set to OFF even though the jumper X12 is not cut. Remedy:
|
| Fault 8, Subcode S49 OPTAF: Board mounted in VACON NXS control board |
Cause: OPTAF is only compatible with VACON® NXP. Remedy:
|
| Fault 8, Subcode S50 OPTAF: Filter discharge resistor fault |
Cause: Problem with the control board. Remedy:
|
| Fault 8, Subcode S70 False fault activated |
Cause: Fault in application. Remedy:
|
| Fault 9, Subcode S1 Undervoltage: DC-link too low during run |
Cause: The DC-link voltage is lower than the limits. Possible reasons:
Remedy:
|
| Fault 9, Subcode S2 Undervoltage: No data from power unit |
Cause: The DC-link voltage is lower than the limits. Possible reasons:
Remedy:
|
| Fault 9, Subcode S3 Undervoltage: Undervoltage control supervision |
Cause: The DC-link voltage is lower than the limits. Possible reasons:
Remedy:
|
| Fault 10, Subcode S1 Input line supervision: Phase supervision diode supply |
Cause: The input line phase is missing. Remedy:
|
| Fault 10, Subcode S2 Input line supervision: Phase supervision active front-end |
Cause: Line sync fault. AFE is not able to synchronize to line after five trials. Remedy:
|
| Fault 10, Subcode S3 Input line supervision: Phase supervision active front end, Microgrid |
Cause: Frequency exceeds the line frequency min/max limits. Underfrequency appears if: DC-link voltage is too low or not enough power in grid. Overfrequency appears if: Overvoltage control activates or too much power generation. Remedy:
|
| Fault 11, Subcode S1 Output phase supervision: Common output phase supervision |
Cause: The measurement of current tells that there is no current in 1 motor phase. Remedy:
|
| Fault 11, Subcode S2 Output phase supervision: Additional closed loop control output phase fault |
Cause: The measurement of current tells that there is no current in 1 motor phase. Remedy:
|
| Fault 11, Subcode S3 Output phase supervision: Additional open loop control output phase fault during start DC brake |
Cause: The measurement of current tells that there is no current in 1 motor phase. Remedy:
|
| Fault 11, Subcode S4 Output phase supervision: Additional closed loop output phase fault during PM StartAngleID run |
Cause: The measurement of current tells that there is no current in 1 motor phase. Remedy:
|
| Fault 12 Brake chopper supervision |
Cause:
Remedy:
|
| Fault 13 AC drive undertemperature |
Cause: Too low a temperature in the heat sink of the power unit or in the power board. The heat sink temperature is below -10 °C (14 °F). Remedy:
|
| Fault 14, Subcode S1 AC drive overtemperature: Overtemperature warning in unit, board, or phases |
Cause: Overheating detected in AC drive. Heat sink temperature is over 90 °C (194 °F). Alarm issued over 85 °C (185 °F). (Different limits apply for 525–690 V, FR6). Remedy:
|
| Fault 14, Subcode S2 AC drive overtemperature: Overtemperature in power board |
Cause: Overheating detected in AC drive. Heat sink temperature is over 90 °C (194 °F). Remedy:
|
| Fault 14, Subcode S3 AC drive overtemperature - Liquid flow |
Cause: Appears when the liquid flow supervision is activated, and problems in cooling liquid flow are detected.
Remedy:
|
| Fault 14, Subcode S4 AC drive overtemperature on ASIC board or driver boards |
Cause: Overheating detected in AC drive. Heat sink temperature is over 90 °C (194 °F). Overtemperature alarm is issued when the heat sink temperature goes over 85 °C (185 °F). In 525–690 V, FR6: Heat sink temperature is over 77 ºC (170.6 °F). Alarm issued over 72 ºC (161.6 °F). Remedy:
|
| Fault 15 Motor stalled |
Cause: The motor stalled. It is possible to set different responses in the application for this fault. See parameter group Protections.
Remedy:
|
| Fault 16 Motor overtemperature |
Cause: There is too heavy a load on the motor. It is possible to set different responses in the application for this fault. See parameter group Protections.
Remedy:
|
| Fault 17 Motor underload |
Cause: Motor underload protection has tripped. It is possible to set different responses in the application for this fault. See parameter group Protections.
Remedy:
|
| Fault 18, Subcode S1 Unbalance - Current unbalance |
Cause: Unbalance between power modules in paralleled power units. This fault is type A fault (Alarm).
Remedy:
|
| Fault 18, Subcode S2 Unbalance - DC voltage unbalance |
Cause: Unbalance between power modules in paralleled power units. This fault is type A fault (Alarm).
Remedy:
|
| Fault 19 Current overload |
Cause: Motor current overload warning.
Remedy:
|
| Fault 22, Subcode S1 Parameter fault - Firmware interface power down variable checksum error |
Cause:
Remedy:
|
| Fault 22, Subcode S2 Parameter fault - Firmware interface variable check sum error |
Cause:
Remedy:
|
| Fault 22, Subcode S3 Parameter fault - System power down variable check sum error |
Cause:
Remedy:
|
| Fault 22, Subcode S4 Parameter fault - System parameter checksum error |
Cause:
Remedy:
|
| Fault 22, Subcode S5 Parameter fault - Application-defined power-down, variable checksum error |
Cause: Parameter save fault.
Remedy:
|
| Fault 22, Subcode S6 Parameter fault - Application-defined power-down, variable check sum |
Cause:
Remedy:
|
| Fault 22, Subcode S10 Parameter fault - System parameter checksum error |
Cause:
Remedy:
|
| Fault 22, Subcode S13 Parameter fault - Checksum error in application-specific parameter set |
Cause: Parameter save fault.
Remedy:
|
| Fault 24 Counter fault |
Cause: Values that showed on the counters are incorrect.
Remedy:
|
| Fault 25, Subcode S1 Microprocessor watchdog fault - CPU watchdog timer |
Cause:
Remedy:
|
| Fault 25, Subcode S2 Microprocessor watchdog fault - ASIC reset |
Cause:
Remedy:
|
| Fault 26, Subcode S1 Start-up prevented - Prevention of accidental start-up |
Cause: Start-up of the drive has been prevented. Run request is ON when new application is downloaded to the drive.
Remedy:
|
| Fault 26, Subcode S2 Start-up prevented - RUN request is kept active after drive returns to READY |
Cause: Start-up of the drive has been prevented. START command is ON when returning to READY state after Safe Disable has been active.
Remedy:
|
| Fault 26, Subcode S30 Start-up prevented - RUN request given too quickly |
Cause: Start-up of the drive has been prevented. START command is ON after system software or application was downloaded, or after application was changed.
Remedy:
|
| Fault 29, Subcode S1 Thermistor fault - Thermistor input activated on OPTAF board |
Cause: The thermistor input of option board has detected increase of the motor temperature. It is possible to set different responses in the application for this fault.
Remedy:
|
| Fault 29, Subcode S2 Thermistor fault - Special application |
Cause: The thermistor input of option board has detected increase of the motor temperature. It is possible to set different responses in the application for this fault.
Remedy:
|
| Fault 30 Safe disable |
Cause: The input on OPTAF board has opened. STO inputs SD1 and SD2 are activated through the OPTAF option board.
Remedy:
|
| Fault 31 IGBT temperature (hardware) |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 32 Fan cooling |
Cause: Cooling fan of the AC drive does not start, when ON command is given.
Remedy:
|
| Fault 34 CAN bus communication |
Cause: Sent message not acknowledged.
Remedy:
|
| Fault 35 Application |
Cause: Problem in application software.
Remedy:
|
| Fault 36 Control unit |
Cause: The software needs newer version of the control unit.
Remedy:
|
| Fault 37, Subcode S1 Device changed (same type) - Control board |
Cause: A new option board has replaced the old one in the same slot. The parameters are available in the drive.
Remedy:
|
| Fault 38, Subcode S1 Device added (same type) - Control board |
Cause: The option board was added. The same option board has been used in the same slot before. The parameters are available in the drive.
Remedy:
|
| Fault 39 Device removed |
Cause: An option board was removed from the slot.
Remedy:
|
| Fault 40, Subcode S1 Device unknown |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S2 Device unknown - StarCoupler: power sub units are not identical |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S3 Device unknown - StarCoupler is not compatible with the control board |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S4 Device unknown - Wrong PropertiesType in control board EEPROM |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S5 Device unknown - Wrong VACON NXP control board EEPROM size detected |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S6 Device unknown - Old power unit (Asic) and new software mismatch |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 40, Subcode S7 Device unknown - Old ASIC detected |
Cause: An unknown or mismatching device was connected (the power unit or option board).
Remedy:
|
| Fault 41, Subcode S1 IGBT temperature - Calculated IGBT temperature too high |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 41, Subcode S2 IGBT temperature - AFE current is higher than defined EON current limit during the grid fault |
Cause: AFE EON-function current limiter (cutter) has been active longer than 50 ms during the grid fault.
Remedy:
|
| Fault 41, Subcode S3 IGBT temperature - Calculated IGBT temperature too high (long-term protection) |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 41, Subcode S4 IGBT temperature - Peak current too high |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 41, Subcode S5 IGBT temperature - BCU: Filtered current too high for some time |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 41, Subcode S6 IGBT temperature - BCU: Current momentarily too high |
Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
Remedy:
|
| Fault 42, Subcode S1 Brake resistor overtemperature - Internal brake chopper overtemperature |
Cause: Brake resistor overtemperature protection has detected too heavy braking.
Remedy:
|
| Fault 42, Subcode S2 Brake resistor overtemperature - Brake resistance too high (BCU) |
Cause: Brake resistor overtemperature protection has detected too heavy braking.
Remedy:
|
| Fault 42, Subcode S3 Brake resistor overtemperature - Brake resistance too low (BCU) |
Cause: Brake resistor overtemperature protection has detected too heavy braking.
Remedy:
|
| Fault 42, Subcode S4 Brake resistor overtemperature - Brake resistance not detected (BCU) |
Cause: Brake resistor overtemperature protection has detected too heavy braking.
Remedy:
|
| Fault 42, Subcode S5 Brake resistor overtemperature - Brake resistance leakage (earth fault) (BCU) |
Cause: Brake resistor overtemperature protection has detected too heavy braking.
Remedy:
|
| Fault 43, Subcode S1 Encoder fault - Encoder 1 channel A is missing |
Cause: Problem detected in encoder signals. Encoder channel A is missing.
Remedy:
|
| Fault 43, Subcode S2 Encoder fault - Encoder 1 channel B is missing |
Cause: Problem detected in encoder signals. Encoder channel B is missing.
Remedy:
|
| Fault 43, Subcode S3 Encoder fault - Both encoder 1 channels are missing |
Cause: Problem detected in encoder signals. Encoder channels A and B are missing.
Remedy:
|
| Fault 43, Subcode S4 Encoder fault - Encoder reversed |
Cause: Problem detected in encoder signals. The encoder is reversed. The output frequency has been set to the positive value, but the encoder signal is negative.
Remedy:
|
| Fault 43, Subcode S5 Encoder fault - Encoder board missing |
Cause: The encoder board is missing.
Remedy:
|
| Fault 43, Subcode S6 Encoder fault - Serial communication fault |
Cause: Problem detected in encoder signals. Serial communication fault. The encoder cable is not connected or there are interferences in the cable.
Remedy:
|
| Fault 43, Subcode S7 Encoder fault - Ch A / Ch B Mismatch |
Cause: Problem detected in encoder signals. Encoder channels A and B are mismatched.
Remedy:
|
| Fault 43, Subcode S8 Encoder fault - Resolver/Motor pole pair mismatch |
Cause: Problem detected in parameterization of option board. There is a mismatch of the resolver/motor pole pair number.
Remedy:
|
| Fault 43, Subcode S9 Encoder fault - Missed Start Angle |
Cause: Encoder zero positioning identification run has not been made. The encoder start angle is missing.
Remedy:
|
| Fault 43, Subcode S10 Encoder fault - Sin/Cos encoder feedback is missing |
Cause: Problem detected in encoder signals. For the closed loop control, encoder modes "EnDat only" or "SSI only" (absolute channel only) are not allowed.
Remedy:
|
| Fault 43, Subcode S11 Encoder fault - Encoder angle is drifting |
Cause: Error angle between the angle read from the absolute channel and the angle calculated from the incremental channels.
Remedy:
|
| Fault 43, Subcode S12 Encoder fault - Dual speed supervision fault |
Cause: Encoder speed supervision. The difference between the encoder speed and estimated speed is too large.
Remedy:
|
| Fault 43, Subcode S13 Encoder fault - Encoder angle supervision fault |
Cause: The estimated shaft position error (estimated angle - encoder angle) is more than 90° electrical.
Remedy:
|
| Fault 43, Subcode S14 Encoder fault - Encoder estimated missing pulse fault, switch from the CL ctrl to the OL sensorl |
Cause: Problem detected in encoder signals. Software has detected too many missing pulses in the encoder.
Remedy:
|
| Fault 44, Subcode S1 Device changed (different type) - Control board |
Cause: Option board or power unit changed. New device of different type or different power rating.
Remedy:
|
| Fault 45, Subcode S1 Device added (different type) - Control board |
Cause: Option board of different type added.
Remedy:
|
| Fault 49 Division by zero in application |
Cause: Division by zero has occurred in application program.
Remedy:
|
| Fault 50 Analogue input Iin < 4 mA (sel. signal range 4 to 20 mA) |
Cause: Current at the analog input is < 4 mA. Control cable is broken or loose, or signal source has failed.
Remedy:
|
| Fault 51 External fault |
Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active.
Remedy:
|
| Fault 52 Keypad communication fault |
Cause: The connection between the control panel (or VACON NCDrive) and the drive is defective.
Remedy:
|
| Fault 53 Fieldbus fault |
Cause: The data connection between the fieldbus master and the fieldbus board is defective.
Remedy:
|
| Fault 54 Slot fault |
Cause: Defective option board or slot.
Remedy:
|
| Fault 56 Measured Temperature |
Cause: Shows temperature measurement fault for option board OPTBH or OPTB8. Temperature exceeded set limit, Sensor disconnected, or Short circuit.
Remedy:
|
| Fault 57 Identification |
Cause: Identification run has failed. This fault is type A fault (Alarm).
Remedy:
|
| Fault 58 Brake |
Cause: Actual status of the brake is different from the control signal. It is possible to set different responses in the application for this fault.
Remedy:
|
| Fault 59 Follower communication |
Cause: SystemBus or CAN communication is broken between Master and Follower.
Remedy:
|
| Fault 60 Cooling |
Cause: External cooling has failed. Normally this fault comes from the heat exchanger unit.
Remedy:
|
| Fault 61 Speed error |
Cause: Motor speed is unequal to reference.
Remedy:
|
| Fault 62 Run disable |
Cause: Run enable signal is low.
Remedy:
|
| Fault 63 Quick stop |
Cause: Command for quick stop received from digital input or fieldbus.
Remedy:
|
| Fault 64 Input switch open |
Cause: Drive input switch is open.
Remedy:
|
| Fault 65 Measured Temperature |
Cause: Shows temperature measurement fault for option board OPTBH or OPTB8. Temperature exceeded set limit, Sensor disconnected, or Short circuit.
Remedy:
|
| Fault 70 Active filter fault |
Cause: Fault triggered by digital input.
Remedy:
|
| Fault 74 Follower fault |
Cause: When using normal Master Follower function this fault code is given if one or more follower drives trips to fault.
Remedy:
|
| Fault 85 Baseline Run |
Cause: There was a failure during the baseline run.
Remedy:
|
| Fault 86, Subcode A1 Condition-based Monitoring - Motor Stator Winding Current Fault |
Cause: Current unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A2 Condition-based Monitoring - Motor Stator Winding Voltage Fault |
Cause: Voltage unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A3 Condition-based Monitoring - Motor Stator Winding Current Warning S2 |
Cause: Current unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A4 Condition-based Monitoring - Motor Stator Winding Voltage Warning S2 |
Cause: Voltage unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A5 Condition-based Monitoring - Motor Stator Winding Current Warning S1 |
Cause: Current unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A6 Condition-based Monitoring - Motor Stator Winding Voltage Warning S1 |
Cause: Voltage unbalance has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A7 Condition-based Monitoring - Vibration Fault |
Cause: Vibration has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A8 Condition-based Monitoring - Vibration Warning S2 |
Cause: Vibration has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A9 Condition-based Monitoring - Vibration Warning S1 |
Cause: Vibration has exceeded the detection high limit.
Remedy:
|
| Fault 86, Subcode A10 Condition-based Monitoring - Load Fault |
Cause: Load outside of the window limits.
Remedy:
|
| Fault 86, Subcode A11 Condition-based Monitoring - Load Warning S2 |
Cause: Load outside of the window limits.
Remedy:
|
| Fault 86, Subcode A12 Condition-based Monitoring - Load Warning S1 |
Cause: Load outside of the window limits.
Remedy:
|
How to Read VACON NXP Faults via NCDrive
The VACON NXP is a complex drive often used in closed-loop control. In 2026, relying on the keypad is rarely enough; you need to analyze the subcodes and data logs:
- VACON NCDrive (PC Software): This is the dedicated engineering tool for the NXP family. Connect your PC via the RS-232 service cable or USB adapter.
- Fault History: Unlike the basic list, NCDrive displays the Fault Time (operating hours), Subcode, and the state of the drive (Frequency, Current, Voltage) at the exact moment of the trip.
- Datalogger: The NXP has an internal datalogger. You can trigger it to record signals before a fault occurs, allowing you to see if a torque spike caused an “F1 Overcurrent” trip.
- Control Panel (Keypad):
- Navigate to Menu M4 (Fault History).
- Active Faults (F): Issues currently stopping the drive.
- Fault History (H): The last 30 faults stored in memory.
- Fault Subcodes (ID): This is critical for NXP drives. For example, an F1 (Overcurrent) fault will have a subcode (e.g., S1 = Output Phase U, S2 = Output Phase V). This tells you exactly which IGBT or cable to check.
Frequently Asked Questions (FAQ)
Q: What is the difference between an Alarm (A) and a Fault (F)?
A:
- Alarm (A-Codes): The drive indicates a warning (e.g., A16 “Motor Overtemperature Calculated”) but continues modulation. The yellow “Ready” LED blinks.
- Fault (F-Codes): The drive stops modulation immediately (e.g., F31 “IGBT Temperature”). The red “Fault” LED is lit solid.
Q: How do I reset a VACON NXP fault?
A:
- Press the Reset button on the control panel (Keypad).
- Toggle the I/O Input programmed for “Fault Reset” (typically DIN3 or DIN4).
- Send a Reset command via the Fieldbus (Profibus, Profinet, Modbus).
Q: Why do I get “F54” (Slot Fault) or “F53” (Fieldbus Fault)?
A: The NXP is modular and uses option cards in slots A, B, C, D, and E.
- F54: Indicates a configuration mismatch between the option card installed and the application software expectation.
- F53: Indicates communication loss. Check the terminating resistors on your fieldbus plug or the fiber optic cables if using System Bus.
Comments