Danfoss VLT 3000 Drive Fault Codes List
Access the complete reference guide for the obsolete Danfoss VLT 3000 drive. Learn to diagnose Trip Lock errors, reform aging capacitors, and plan retrofits to FC 302.
Danfoss VLT 3000 Fault Codes Reference Table
Danfoss VLT Frequency Converter Faults and Alarms
Danfoss VLT Faults and Alarms
| Fault Code and Meaning | Cause and Remedy |
|---|---|
|
Inverter fault (INVERTER FAULT) Fault code 1 A fault in the VLT frequency converter's power section. |
Cause: Internal failure within the power section of the drive. Remedy:
|
|
Overvoltage (OVER VOLTAGE) Fault code 2 The intermediate circuit voltage (DC link) is above the inverter's overvoltage limit. |
Cause: The intermediate circuit voltage is too high. This can happen if:
Remedy:
|
|
Undervoltage (UNDER VOLTAGE) Fault code 3 The intermediate circuit voltage is below the inverter's undervoltage limit. |
Cause: The intermediate circuit voltage is too low.
Remedy:
|
|
Overcurrent (OVER CURRENT) Fault code 4 The inverter's peak current limit (approx. 250% of rated current) has been exceeded for more than 7-11 seconds. |
Cause:
Remedy:
|
|
Earth fault (GROUND FAULT) Fault code 5 Discharge from the output phases to earth. |
Cause: Leakage current detected either in the cable between the VLT frequency converter and the motor, or within the motor itself. Remedy:
|
|
Overtemperature (OVER TEMP.) Fault code 6 An excess temperature has been measured inside the VLT frequency converter. |
Cause: Internal overheating. This may be due to ambient temperature being too high or fan failure. Remedy:
|
|
Inverter overloaded (OVER LOAD) Fault code 7 The electronic thermal inverter protection reports that the drive has cut out due to overload. |
Cause: Excessive current for too long. The protection counter reached 100%. Remedy:
|
|
Motor overloaded (MOTOR TRIP) Fault code 8 and 15 According to the electronic thermal motor protection, the motor is too hot. |
Cause: Motor is drawing high current for an extended period, or low speed operation without sufficient cooling. Remedy:
|
|
Current limit (CURRENT LIMIT) Fault code 9 The motor current has exceeded the value in parameter 209 for longer than permitted in parameter 310. |
Cause: Mechanical overload or incorrect current limit settings. Remedy:
|
|
Auto optimization fault (TUNING. FAULT) Fault code 13 Failure during the Adaptive Motor Tuning (AMT) process. |
Cause:
Remedy:
|
|
Reference faults (REF. FAULT) Warning Fault to the analogue input signal (terminal 53 or 60) with "live zero" selected. |
Cause: Signal level is below half of the zero level (e.g., below 2mA on a 4-20mA signal). Remedy:
|
|
No motor (NO MOTOR) Warning The motor check function (parameter 313) detects that no motor is connected. |
Cause: Missing motor connection on the output phases. Remedy:
|
|
EEPROM fault (EEPROM ERROR) Warning/Error EEPROM fault detected. |
Cause: Data changes are not saved when mains voltage is switched off. Remedy:
|
|
24 V fault (NO 24 VOLT) Warning 24 V voltage supply from power section to control card is absent. |
Cause: Internal power supply failure. Remedy:
|
|
Key Disabled (KEY DISABLED) Error Message Keypad interaction attempted but keys are locked. |
Cause: Factory setup is active, or keys disabled via parameters 006-009, or Lock switch is open. Remedy:
|
| Inverter fault The VLT power section is defective. |
Cause: Defect in the power section. Remedy:
|
| Overvoltage The voltage of the VLT frequency converter's intermediate circuit (DC-voltage) is too high. |
Cause: Line voltage too high, transients on the line voltage, or regenerative motor operation. Remedy:
|
| Undervoltage The voltage of the VLT frequency converter's intermediate circuit (DC-voltage) is too low. |
Cause: Line voltage too low or defect in the VLT frequency converter's charging circuit/rectifier. Remedy:
|
| Overcurrent The peak current limit of the inverter has been reached. |
Cause: This may be due to a short-circuit in the output of the VLT frequency converter or ground failure. Remedy:
|
| Ground fault Ground failure on the VLT frequency converter output. |
Cause: Earth leakage or the motor cable is too long. Remedy:
|
| Over-temp The temperature inside the VLT frequency converter is too high. |
Cause: Ambient temperature is too high (max. 40/45 °C), cooling ribs are covered, or the fan is defective. Remedy:
|
| Overload The electronic VLT protection is active. The motor has consumed more than 105% of rated current for too long. |
Cause: Motor has consumed excessive current for an extended period. Remedy:
|
| Motor trip The electronic motor protection is active. Current consumed at low speed has been too high for too long. |
Cause: The motor has been loaded excessively at low speed. Remedy:
|
How to Read VLT 3000 Faults (Manual Diagnostics)
The VLT 3000 does not support modern MCT 10 software via USB. Troubleshooting in 2026 involves physical inspection and interpreting the front panel:
- LED Indicators: The front panel has specific LEDs.
- Yellow (Warning): A limit is reached (e.g., Current Limit), but the drive is still running.
- Red (Alarm): The drive has tripped. If the Red LED is flashing, it is a standard trip. If it is solid or accompanied by a “Locked” message, it is a Trip Lock.
- Display Messages: The small LCD (on equipped models) displays text codes like “OVT” (Over Voltage), “OC” (Over Current), or “EARTH FAULT”. Unlike modern drives, these messages are often abbreviated.
- Capacitor Reforming (Critical): If you have a spare VLT 3000 that has been sitting on a shelf for more than 2 years, do not power it up immediately. The DC bus electrolytic capacitors have likely dried out. You must apply voltage gradually using a Variac over several hours, or the capacitors will explode.
Frequently Asked Questions (FAQ)
Q: What is the difference between “Trip” and “Trip Locked”?
A:
- Trip: The drive stops, but you can reset it immediately by pressing the Reset button (e.g., for Overload).
- Trip Locked: A severe hardware fault (e.g., Short Circuit or Earth Fault). You must cycle the main power (turn off, wait for display to discharge, turn on) to reset the logic.
Q: How do I reset a Danfoss VLT 3000?
A:
- Press the RESET button on the keypad.
- Toggle the Digital Input (usually Terminal 16 or 17, depending on programming).
- If the drive is “Trip Locked,” you must cycle the mains power.
Q: What is the modern replacement for the VLT 3000?
A: The direct successor is the Danfoss VLT AutomationDrive FC 302.
- The mounting footprints are different, so you will likely need a retrofit backplate.
- The parameter structures differ significantly, so you cannot simply “copy/paste” the settings; a manual conversion of motor data and I/O logic is required.
Q: Why does the drive trip on “OVT” (Over Voltage) at stop?
A: This is common in aging VLT 3000 units.
- The internal braking circuit may have failed.
- The DC bus capacitors may have lost capacity due to age, reducing their ability to absorb regenerative energy during deceleration.
- Fix: Increase the ramp-down time or replace the drive.