Danfoss VLT FC301 Drive Fault Codes List
Access the complete reference guide for Danfoss VLT Automation Drive FC 301 fault codes. Learn to diagnose Safe Stop (Alarm 68), Earth Faults (Alarm 14), and use MCT 10.
Danfoss FC 301 Fault Codes Reference Table
| Fault Code | Cause & Solution |
| Warning
1 10 Volts Low |
Cause: The control card voltage is less than 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V supply is overloaded.
Maximum 15 mA or minimum 590 Ω. - A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition. Troubleshooting: - Remove the wiring from terminal 50. - If the warning clears, the problem is with the wiring. If the warning does not clear, replace the control card. |
| WARNING
2 Live zero error |
Cause: This warning or alarm only appears if programmed in parameter
6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or faulty device sending the signal can cause this condition. Troubleshooting: 1. Check connections on all the analog input terminals. a. Control card terminals 53 and 54 for signals, terminal 55 common. b. VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common. c. VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common. Check that the drive programming and switch settings match the analog signal type. 2. Perform the input terminal signal test. |
| ALARM
2 Live zero error |
Cause: This warning or alarm only appears if programmed in parameter
6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or faulty device sending the signal can cause this condition. Troubleshooting: 1. Check connections on all the analog input terminals. a. Control card terminals 53 and 54 for signals, terminal 55 common. b. VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common. c. VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common. Check that the drive programming and switch settings match the analog signal type. 2. Perform the input terminal signal test. |
| WARNING
3 No motor |
Cause: No motor is connected to the output of the frequency
converter. Solution: - Check the cable connection between the frequency converter and the motor. |
| ALARM
3 No motor |
Cause: No motor is connected to the output of the frequency
converter. Solution: - Check the cable connection between the frequency converter and the motor. |
| WARNING
4 Mains phase loss |
Cause: A phase is missing on the supply side, or the mains voltage
imbalance is too high. This message also appears for a fault in the input
rectifier on the frequency converter. Options are programmed at parameter
14-12 Function at Mains Imbalance. Troubleshooting: - Check the supply voltage and supply currents to the frequency converter. |
| ALARM
4 Mains phase loss |
Cause: A phase is missing on the supply side, or the mains voltage
imbalance is too high. This message also appears for a fault in the input
rectifier on the frequency converter. Options are programmed at parameter
14-12 Function at Mains Imbalance. Troubleshooting: - Check the supply voltage and supply currents to the frequency converter. |
| Warning
5 DC Link Voltage High |
Cause: The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active. |
| WARNING
6 DC Link Voltage Low |
Cause: The DC-link voltage (DC) is lower than the low-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active. |
| WARNING
7 DC overvoltage |
Cause: If the DC-link voltage exceeds the limit, the frequency
converter trips after a time. Troubleshooting: - Extend the ramp time. - Change the ramp type. - Activate the functions in parameter 2-10 Brake Function. - Increase parameter 14-26 Trip Delay at Inverter Fault. - If the alarm/warning occurs during a power sag, use kinetic back-up (parameter 14-10 Mains Failure). - Connect a brake resistor. |
| ALARM
7 DC overvoltage |
Cause: If the DC-link voltage exceeds the limit, the frequency
converter trips after a time. Troubleshooting: - Extend the ramp time. - Change the ramp type. - Activate the functions in parameter 2-10 Brake Function. - Increase parameter 14-26 Trip Delay at Inverter Fault. - If the alarm/warning occurs during a power sag, use kinetic back-up (parameter 14-10 Mains Failure). - Connect a brake resistor. |
| WARNING
8 DC under voltage |
Cause: If the DC-link voltage drops below the undervoltage limit,
the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is
connected, the drive trips after a fixed time delay. The time delay varies
with unit size. Troubleshooting: - Check that the supply voltage matches the drive voltage. - Perform an input voltage test. - Perform a soft-charge circuit test. |
| ALARM
8 DC under voltage |
Cause: If the DC-link voltage drops below the undervoltage limit,
the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is
connected, the drive trips after a fixed time delay. The time delay varies
with unit size. Troubleshooting: - Check that the supply voltage matches the drive voltage. - Perform an input voltage test. - Perform a soft-charge circuit test. |
| WARNING
9 Inverter overload |
Cause: The drive has run with more than 100% overload for too long
and is about to cut out. The counter for electronic thermal inverter
protection issues a warning at 98% and trips at 100% with an alarm. The drive
cannot be reset until the counter is below 90%. Troubleshooting: - Compare the output current shown on the LCP with the drive rated current. - Compare the output current shown on the LCP with the measured motor current. - Show the thermal drive load on the LCP and monitor the value. - When running above the drive continuous current rating, the counter increases. - When running below the drive continuous current rating, the counter decreases. |
| ALARM
9 Inverter overload |
Cause: The drive has run with more than 100% overload for too long
and is about to cut out. The counter for electronic thermal inverter
protection issues a warning at 98% and trips at 100% with an alarm. The drive
cannot be reset until the counter is below 90%. Troubleshooting: - Compare the output current shown on the LCP with the drive rated current. - Compare the output current shown on the LCP with the measured motor current. - Show the thermal drive load on the LCP and monitor the value. - When running above the drive continuous current rating, the counter increases. - When running below the drive continuous current rating, the counter decreases. |
| WARNING
10 Motor Overload Temperature |
Cause: According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the drive issues a warning or an alarm
when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long. Troubleshooting: - Check for motor overheating. - Check if the motor is mechanically overloaded. - Check that the motor current set in parameter 1-24 Motor Current is correct. - Ensure that the motor data in parameter 1-20 to parameter 1-25 is set correctly. - Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces thermal loading. |
| ALARM
10 Motor Overload Temperature |
Cause: According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the drive issues a warning or an alarm
when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long. Troubleshooting: - Check for motor overheating. - Check if the motor is mechanically overloaded. - Check that the motor current set in parameter 1-24 Motor Current is correct. - Ensure that the motor data in parameter 1-20 to parameter 1-25 is set correctly. - Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces thermal loading. |
| WARNING
11 Motor thermistor over temp |
Cause: The motor thermistor indicates that the motor temperature is
too high. Troubleshooting: - Check for motor overheating. - Check that the thermistor is securely connected. - Check whether the motor is mechanically overloaded. - When using terminal 53 or 54: - Check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). - Check that the terminal switch for 53 and 54 is set for voltage. - Check that parameter 1-93 Thermistor Resource selects 53 or 54. - When using terminal 18, 19, 31, 32, or 33 (digital inputs): - Check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. - Select the terminal to use in parameter 1-93 Thermistor Resource. |
| ALARM
11 Motor thermistor over temp |
Cause: The motor thermistor indicates that the motor temperature is
too high. Troubleshooting: - Check for motor overheating. - Check that the thermistor is securely connected. - Check whether the motor is mechanically overloaded. - When using terminal 53 or 54: - Check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). - Check that the terminal switch for 53 and 54 is set for voltage. - Check that parameter 1-93 Thermistor Resource selects 53 or 54. - When using terminal 18, 19, 31, 32, or 33 (digital inputs): - Check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. - Select the terminal to use in parameter 1-93 Thermistor Resource. |
| WARNING
12 Torque Limit |
Cause: The torque has exceeded the value in parameter 4-16 Torque
Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit can change this warning from a
warning-only condition to a warning followed by an alarm. Troubleshooting: - If the motor torque limit is exceeded during ramp-up, extend the ramp-up time. - If the generator torque limit is exceeded during ramp-down, extend the ramp-down time. - If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque. - Check the application for excessive current draw on the motor. |
| ALARM
12 Torque Limit |
Cause: The torque has exceeded the value in parameter 4-16 Torque
Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit can change this warning from a
warning-only condition to a warning followed by an alarm. Troubleshooting: - If the motor torque limit is exceeded during ramp-up, extend the ramp-up time. - If the generator torque limit is exceeded during ramp-down, extend the ramp-down time. - If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque. - Check the application for excessive current draw on the motor. |
| WARNING
13 Over current |
Cause: The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts about 1.5 s, then the drive
trips and issues an alarm. Shock loading or quick acceleration with
high-inertia loads can cause this fault. If the acceleration during ramp-up
is quick, the fault can also appear after kinetic backup. If extended
mechanical brake control is selected, a trip can be reset externally. Troubleshooting: - Remove power and check if the motor shaft can be turned. - Check that the motor size matches the drive. - Check that the motor data is correct in parameters 1-20 to 1-25. |
| ALARM
13 Over current |
Cause: The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts about 1.5 s, then the drive
trips and issues an alarm. Shock loading or quick acceleration with
high-inertia loads can cause this fault. If the acceleration during ramp-up
is quick, the fault can also appear after kinetic backup. If extended
mechanical brake control is selected, a trip can be reset externally. Troubleshooting: - Remove power and check if the motor shaft can be turned. - Check that the motor size matches the drive. - Check that the motor data is correct in parameters 1-20 to 1-25. |
| ALARM
14 Earth (ground) fault |
Cause: There is current from the output phase to ground, either in
the cable between the drive and the motor, or in the motor itself. The
current sensors detect the ground fault by measuring current going out from
the drive and current going into the drive from the motor. Ground fault is
issued if the deviation of the 2 currents is too large. The current going out
of the drive must be the same as the current going into the drive. Troubleshooting: - Remove power to the drive and repair the ground fault. - Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. - Reset any potential individual offset in the 3 current sensors in the drive. Perform a manual initialization or perform a complete AMA. This method is most relevant after changing the power card. |
| Alarm
15 Hardware Mismatch |
Cause: A fitted option is not operational with the present control
card hardware or software. Troubleshooting: Record the values of the following parameters and contact . - a. Parameter 15-40 FC Type - b. Parameter 15-41 Power Section - c. Parameter 15-42 Voltage - d. Parameter 15-43 Software Version - e. Parameter 15-45 Actual Typecode String - f. Parameter 15-49 SW ID Control Card - g. Parameter 15-50 SW ID Power Card - h. Parameter 15-60 Option Mounted - i. Parameter 15-61 Option SW Version (for each option slot). |
| ALARM
16 Short circuit |
Cause: There is short-circuiting in the motor or motor wiring. Solution: Remove power to the frequency converter and repair the short circuit. |
| WARNING
17 Control word timeout |
Cause: There is no communication to the drive. The warning is only
active when parameter 8-04 Control Word Timeout Function is NOT set to [0]
Off. - If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The drive then ramps down to stop and issues an alarm. Troubleshooting: - Check the connections on the serial communication cable. - Increase parameter 8-03 Control Word Timeout Time. - Check the operation of the communication equipment. - Verify that the installation adheres to the EMC requirements. |
| ALARM
17 Control word timeout |
Cause: There is no communication to the drive. The warning is only
active when parameter 8-04 Control Word Timeout Function is NOT set to [0]
Off. - If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The drive then ramps down to stop and issues an alarm. Troubleshooting: - Check the connections on the serial communication cable. - Increase parameter 8-03 Control Word Timeout Time. - Check the operation of the communication equipment. - Verify that the installation adheres to the EMC requirements. |
| WARNING
20 Temp. Input Error |
Cause: The temperature detected by VLT® Sensor Input Option MCB 114
exceeds the limit. - This warning/alarm is only active when [5] Stop and trip is selected in parameter 35-06 Temperature Sensor Alarm Function. Troubleshooting: 1. Check the settings of the following parameters: - a. Parameter group 35-1* Temp. Input X48/4 - b. Parameter group 35-2* Temp. Input X48/7 - c. Parameter group 35-3* Temp. Input X48/10 2. Check the feedback temperature from the following parameters: - a. Parameter 18-37 Temp. Input X48/4 - b. Parameter 18-38 Temp. Input X48/7Programming Guide | VLT® HVAC Drive FC 102 |
| ALARM
20 Temp. Input Error |
Cause: The temperature detected by VLT® Sensor Input Option MCB 114
exceeds the limit. - This warning/alarm is only active when [5] Stop and trip is selected in parameter 35-06 Temperature Sensor Alarm Function. Troubleshooting: 1. Check the settings of the following parameters: - a. Parameter group 35-1* Temp. Input X48/4 - b. Parameter group 35-2* Temp. Input X48/7 - c. Parameter group 35-3* Temp. Input X48/10 2. Check the feedback temperature from the following parameters: - a. Parameter 18-37 Temp. Input X48/4 - b. Parameter 18-38 Temp. Input X48/7 |
| WARNING
21 Parameter Error |
Cause: The parameter is out of range. The parameter number is shown
in the display. Troubleshooting: - Set the affected parameter to a valid value. |
| ALARM
21 Parameter Error |
Cause: The parameter is out of range. The parameter number is shown
in the display. Troubleshooting: - Set the affected parameter to a valid value. |
| Warning
22 Hoist Mechanical Brake |
Cause: The value of this warning/alarm shows the type of
warning/alarm. - 0 = The torque reference was not reached before timeout (parameter 2-27 Torque Ramp Up Time. - 1 = Expected brake feedback was not received before timeout (parameter 2-23 Activate Brake Delay, parameter 2-25 Brake Release Time. |
| Alarm
22 Hoist Mechanical Brake |
Cause: The value of this warning/alarm shows the type of
warning/alarm. - 0 = The torque reference was not reached before timeout (parameter 2-27 Torque Ramp Up Time. - 1 = Expected brake feedback was not received before timeout (parameter 2-23 Activate Brake Delay, parameter 2-25 Brake Release Time. |
| Warning
23 Internal Fan Fault |
Cause: The fan warning function is a protective function that checks
if the fan is running/mounted. The fan warning can be disabled in parameter
14-53 Fan Monitor by selecting [0] Disabled. For drives with DC fans, a
feedback sensor is mounted in the fan. If the fan is commanded to run and
there is no feedback from the sensor, this warning appears. For drives with
AC fans, the voltage to the fan is monitored. Troubleshooting: - Cycle for proper fan operation. - Cycle power to the drive and check that the fan operates briefly at start-up. - Check the sensors on the control card. |
| Warning
24 External Fan Fault |
Cause: The fan warning function is a protective function that checks
if the fan is running/mounted. The fan warning can be disabled in parameter
14-53 Fan Monitor by selecting [0] Disabled. For drives with DC fans, a
feedback sensor is mounted in the fan. If the fan is commanded to run and
there is no feedback from the sensor, this warning appears. For drives with
AC fans, the voltage to the fan is monitored. Troubleshooting: - Check for proper fan operation. - Cycle power to the drive and check that the fan operates briefly at start-up. - Check the sensors on the heat sink. |
| WARNING
25 Brake Resistor Short Circuit |
Cause: The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled, and the warning appears. The drive is still operational, but without the brake function. Troubleshooting: - Remove the power to the drive and replace the brake resistor (refer to parameter 2-15 Brake Check. |
| WARNING
26 Brake Resistor Power Limit |
Cause: The power transmitted to the brake resistor is calculated as
an average value over the last 120 s of run time. The calculation is based on
the DC-link voltage and the brake resistor value set in parameter 2-16 Brake
Max. Current. The warning is active when the dissipated braking power is
higher than 90% of the brake resistor power. If [2] Trip is selected in
parameter 2-13 Brake Power Monitoring, the drive trips when the dissipated
braking power reached 100%. Troubleshooting: - Decrease brake energy via lower speed or longer ramp time. |
| ALARM
26 Brake Resistor Power Limit |
Cause: The power transmitted to the brake resistor is calculated as
an average value over the last 120 s of run time. The calculation is based on
the DC-link voltage and the brake resistor value set in parameter 2-16 Brake
Max. Current. The warning is active when the dissipated braking power is
higher than 90% of the brake resistor power. If [2] Trip is selected in
parameter 2-13 Brake Power Monitoring, the drive trips when the dissipated
braking power reached 100%. Troubleshooting: - Decrease brake energy via lower speed or longer ramp time. |
| WARNING
27 Brake Chopper Fault |
Cause: The brake transistor is monitored during operation. If a
short circuit occurs, the brake function is disabled, and a warning is
issued. The drive is still operational, but since the brake transistor has
short-circuited, substantial power is transmitted to the brake resistor, even
if it is inactive. Troubleshooting: - Remove the power to the drive, and remove the brake resistor. |
| ALARM
27 Brake Chopper Fault |
Cause: The brake transistor is monitored during operation. If a
short circuit occurs, the brake function is disabled, and a warning is
issued. The drive is still operational, but since the brake transistor has
short-circuited, substantial power is transmitted to the brake resistor, even
if it is inactive. Troubleshooting: - Remove the power to the drive, and remove the brake resistor. |
| WARNING
28 Brake Check Failed |
Cause: The brake resistor is not connected or not working. Troubleshooting: - Check parameter 2-15 Brake Check. |
| ALARM
28 Brake Check Failed |
Cause: The brake resistor is not connected or not working. Troubleshooting: - Check parameter 2-15 Brake Check. |
| ALARM
29 Heat Sink Temp |
Cause: The maximum temperature of the heat sink is exceeded. The
temperature fault is not reset until the temperature drops below a defined
heat sink temperature. The trip and reset points are different, based on the
drive power size. Troubleshooting: Check for the following conditions: - The ambient temperature is too high. - The motor cables are too long. - Incorrect airflow clearance above and below the drive. - Blocked airflow around the drive. - Damaged heat sink fan. - Dirty heat sink. |
| ALARM
30 Motor phase U missing |
Cause: Motor phase U between the frequency converter and the motor
is missing. Solution: Remove power from the frequency converter and check motor phase U. |
| ALARM
31 Motor phase V missing |
Cause: Motor phase V between the frequency converter and the motor
is missing. Solution: Remove power from the frequency converter and check motor phase V. |
| ALARM
32 Motor phase W missing |
Cause: Motor phase W between the frequency converter and the motor
is missing. Solution: Remove power from the frequency converter and check motor phase W. |
| ALARM
33 Inrush Fault |
Cause: Too many power-ups have occurred within a short time
period. Troubleshooting: - Let the unit cool to operating temperature. - Check potential DC-link fault to ground. |
| WARNING
34 Fieldbus Fault |
Cause: The fieldbus on the communication option card is not
working. Troubleshooting: - Check the fieldbus communication option card. |
| ALARM
34 Fieldbus Fault |
Cause: The fieldbus on the communication option card is not
working. Troubleshooting: - Check the fieldbus communication option card. |
| Warning
35 Option Fault |
Cause: An option alarm is received. The alarm is option-specific.
The most likely cause is a power-up or a communication fault. Troubleshooting: - There is an hardware or software issue in drive. Need to repair or replace drive. |
| ALARM
35 Option Fault |
Cause: An option alarm is received. The alarm is option-specific.
The most likely cause is a power-up or a communication fault. Troubleshooting: - There is an hardware or software issue in drive. Need to repair or replace drive. |
| WARNING
36 Mains Failure |
Cause: This warning/alarm is only active if the supply voltage to
the drive is lost and parameter 14-10 Mains Failure is not set to [0] No
function. Troubleshooting: - Check the fuses to the drive and mains supply to the unit. |
| Alarm
36 Mains Failure |
Cause: This warning/alarm is only active if the supply voltage to
the drive is lost and parameter 14-10 Mains Failure is not set to [0] No
function. Troubleshooting: - Check the fuses to the drive and mains supply to the unit. |
| ALARM
37 Phase Imbalance |
Cause: There is a current imbalance between the power units. |
| ALARM
38 Internal Fault |
Cause: When an internal fault occurs, a code number defined in below
table. Troubleshooting: - Cycle power. - Check that the option is properly installed. - Check for loose or missing wiring. - It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting directions. - 0: The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department. - 256–258: The power EEPROM data is defective or too old. Replace the power card. - 512–519: Internal fault. Contact the Danfoss supplier or Danfoss service department. - 783: Parameter value outside of minimum/maximum limits. - 1024–1284: Internal fault. Contact the Danfoss supplier or Danfoss service department. - 1299: The option software in slot A is too old. - 1300: The option software in slot B is too old. - 1302: The option software in slot C1 is too old. - 1315: The option software in slot A is not supported/allowed. - 1316: The option software in slot B is not supported/ allowed. - 1318: The option software in slot C1 is not supported/ allowed. - 1379–2819: Internal fault. Contact the Danfoss supplier or Danfoss service department. - 1792: Hardware reset of digital signal processor. - 1793: Motor-derived parameters not transferred correctly to the digital signal processor. - 1794: Power data not transferred correctly at power-up to the digital signal processor. - 1795: The digital signal processor has received too many unknown SPI telegrams. The AC drive also uses this fault code if - the: MCO does not power up correctly. This situation can occur due to poor EMC protection or improper grounding. - 1796: RAM copy error. - 2561: Replace the control card. - 2820: LCP stack overflow. - 2821: Serial port overflow. - 2822: USB port overflow. - 3072–5122: Parameter value is outside its limits. - 5123: Option in slot A: Hardware incompatible with the control board hardware. - 5124: Option in slot B: Hardware incompatible with the control board hardware. - 5125: Option in slot C0: Hardware incompatible with the control board hardware. - 5126: Option in slot C1: Hardware incompatible with the control board hardware. - 5376– 6231: Internal fault. Contact the Danfoss supplier or Danfoss service department. |
| ALARM
39 Heat Sink Sensor |
Cause: There is no feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power
card. Troubleshooting: - Check the ribbon cable between the power card and the gate drive card. - Check for a defective power card. - Check for a defective gate drive card. |
| WARNING
40 Overload of digital output terminal 27 |
Troubleshooting: - Check the load connected to terminal 27 or remove the short-circuit connection. - Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode. |
| WARNING
41 Overload of digital output terminal 29 |
Troubleshooting: - Check the load connected to terminal 29 or remove the short-circuit connection. - Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode. |
| WARNING
42 Ovrld X30/6-7 |
Cause: Overload of digital output on X30/6 or overload of digital
output on X30/7. Troubleshooting, X30/6: - Check the load connected to the terminal or remove the short-circuit connection. - Check parameter 5-32 Term X30/6 Digi Out (MCB 101)(VLT® General Purpose I/O MCB 101). Troubleshooting, X30/7: - Check the load connected to the terminal or remove the short-circuit connection. - Check parameter 5-33 Term X30/7 Digi Out (MCB 101)(VLT® General Purpose I/O MCB 101). |
| WARNING
43 Ext. Supply |
Cause: VLT® Extended Relay Option MCB 113 is mounted without 24 V
DC. Select 1 of the options in the troubleshooting list. Troubleshooting: - Connect a 24 V DC external supply. - Specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC set to [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle. |
| ALARM
45 Earth (Ground) Fault 2 |
Cause: A ground fault has occurred. Troubleshooting: - Check for proper grounding and loose connections. - Check for proper wire size. - Check the motor cables for short circuits or leakage currents. |
| ALARM
46 Power Card Supply |
Cause: The supply on the power card is out of range. Another reason
can be a defective heat sink fan. There are 3 supplies generated by the
switch mode supply (SMPS) on the power card: - 24 V. - 5 V. - ±18 V. When powered with VLT® 24 V DC Supply MCB 107, only 24 V and 5 V supplies are monitored. When powered with 3-phase mains voltage, all 3 supplies are monitored. Troubleshooting: - Check for a defective power card. - Check for a defective control card. - Check for a defective option card. - If 24 V DC is used, verify proper supply power. - Check for a defective heat sink fan. |
| ALARM
47 24 V Supply Low |
Cause: The supply on the power card is out of range. There are 3 supplies generated by the switch mode supply (SMPS) on the power card: - 44 V - 5 V - ±18 V Troubleshooting: - Check for a defective power card. |
| ALARM
48 1.8 V Supply Low |
Cause: The 1.8 V DC supply used on the control card is outside of
the allowed limits. The supply is measured on the control card. Troubleshooting: - Check for a defective control card. - If an option is installed, check for overvoltage. |
| WARNING
49 SPEED LIMIT |
Cause: The warning is shown when the speed is outside of the specified range in parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13 Motor Speed High Limit [RPM]. When the speed is below the specified limit in parameter 1-86 Trip Speed Low [RPM] (except when starting or stopping), the drive trips. |
| FAULT
50 AMA Calibration Failed |
Solution: There is an hardware or software issue in drive. Need to repair or replace drive. |
| ALARM
51 AMA check Unom and Inom |
Cause: The setting of motor voltage, motor current, and motor power
is presumably wrong. Solution: Check the settings in parameter 1-20 to parameter 1-25. |
| ALARM
52 AMA low Inom |
Cause: The motor current is too low. - Check the setting in parameter 1-24 Motor Current. |
| ALARM
53 AMA motor too big |
Cause: The motor is too large for the AMA to be performed. Troubleshooting: - Check the settings in parameter group 1-2* Motor Data. |
| ALARM
54 AMA motor too small |
Cause: The motor is too small for the AMA to be performed. Troubleshooting: - Check the settings in parameter group 1-2* Motor Data. |
| ALARM
55 AMA Parameter out of range |
Cause: The parameter values found from the motor are outside the acceptable range. |
| ALARM
56 AMA interrupted by user |
Cause: The AMA is interrupted. Troubleshooting - Re-run the AMA calibration. |
| ALARM
57 AMA Internal Fault |
Cause: Internal fault. Troubleshooting: - Try to restart the AMA. Repeated restarts can overheat the motor. |
| ALARM
58 AMA internal fault |
Cause: AMA internal fault. Solution: There is an hardware or software issue in drive. Need to repair or replace drive. |
| WARNING
59 Current limit |
Cause: The current is higher than the value in parameter 4-18
Current Limit. Troubleshooting: - Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. - Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit. |
| ALARM
60 External interlock |
Cause: A digital input signal indicates a fault condition external to the frequency converter. An external interlock has commanded the frequency converter to trip. Clear the external fault condition. To resume normal operation, apply 24 V DC to the terminal programmed for external interlock, and reset the frequency converter. |
| WARNING
61 Feedback Error |
Cause: An error between calculated speed and speed measurement from
feedback device. Troubleshooting: - Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function. - Set the tolerable error in parameter 4-31 Motor Feedback Speed Error. - Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout. |
| ALARM
61 Feedback Error |
Cause: An error between calculated speed and speed measurement from
feedback device. Troubleshooting: - Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function. - Set the tolerable error in parameter 4-31 Motor Feedback Speed Error. - Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout. |
| WARNING
62 Output Frequency at Maximum Limit |
Cause: The output frequency has reached the value set in parameter
4-19 Max Output Frequency. Troubleshooting: - Check the application for possible causes. - Increase the output frequency limit. Be sure that the system can operate safely at a higher output frequency. - The warning clears when the output drops below the maximum limit. |
| Alarm
62 Output Frequency at Maximum Limit |
Cause: The output frequency has reached the value set in parameter
4-19 Max Output Frequency. Troubleshooting: - Check the application for possible causes. - Increase the output frequency limit. Be sure that the system can operate safely at a higher output frequency. - The warning clears when the output drops below the maximum limit. |
| ALARM
63 Mechanical Brake Low |
Cause: The actual motor current has not exceeded the release brake current within the start delay time window. |
| WARNING
64 VOLTAGE LIMIT |
Cause: The load and speed combination demands a motor voltage higher
than the actual DC-link voltage. Troubleshooting: - Check if the mains input is not high enough. - Check if the output frequency is too high above motor nominal frequency. |
| WARNING
65 Control card over temperature |
Cause: The cutout temperature of the control card has exceeded the
upper limit. Troubleshooting: - Check that the ambient operating temperature is within the limits. - Check the fan operation. - Check the control card. |
| ALARM
65 Control card over temperature |
Cause: The cutout temperature of the control card has exceeded the
upper limit. Troubleshooting: - Check that the ambient operating temperature is within the limits. - Check the fan operation. - Check the control card. |
| Warning
66 Heat Sink Temperature Low |
Cause: The drive is too cold to operate. This warning is based on
the temperature sensor in the IGBT module. Troubleshooting: - Increase the ambient temperature of the unit. - Supply a trickle amount of current to the drive whenever the motor is stopped by setting parameter 2-00 DC Hold/Preheat Current to 5% and parameter 1-80 Function at Stop. |
| ALARM
67 Option Module Configuration Has Changed |
Cause: One or more options have either been added or removed since
the last power-down. Troubleshooting: - Check that the configuration change is intentional and reset the unit. |
| ALARM
68 Safe Stop Activated |
Cause: The Safe Torque Off (STO) has been activated. Troubleshooting: - To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal via bus, digital I/O, or by pressing [Reset]. |
| ALARM
69 Power card temperature |
Cause: The temperature sensor on the power card is either too hot or
too cold. Troubleshooting: - Check that the ambient operating temperature is within limits. - Check for clogged filters. - Check fan operation. - Check the power card. |
| ALARM
70 Illegal FC Configuration |
Cause: The control card and power card are incompatible. Troubleshooting: - To check compatibility, contact the supplier with the type code from the unit nameplate and the part numbers on the cards |
| ALARM
71 PTC 1 Safe Stop |
Cause: Because the motor is too warm, the VLT® PTC Thermistor Card
MCB 112 activated Safe Torque Off (STO). Troubleshooting Once the motor temperature reaches an acceptable level, and the digital input from MCB 112 is deactivated, perform 1 of the following: – Send a reset signal via bus or digital I/O. – Press [Reset]. |
| ALARM
72 Dangerous Failure |
Cause: Safe Torque Off (STO) with trip lock. An unexpected
combination of STO commands has occurred. Troubleshooting: - VLT® PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled. - MCB 112 is the only device using STO (specified via [4] PTC 1 alarm or [5] PTC 12 warning in parameter 5-19 Terminal 37 Safe Stop). STO is activated, but X44/10 is not. |
| WARNING
73 Safe Stop Auto Restart |
Cause: STO is activated. Troubleshooting: - With automatic restart enabled, the motor can start when the fault is cleared. |
| ALARM
74 PTC Thermistor |
Cause: The PTC is not working. Alarm is related to VLTÆ PTC Thermistor Card MCB 112. |
| ALARM
75 Illegal Profile Sel |
Cause: There was an attempt to write the parameter value while the
motor was running. Troubleshooting: - Stop the motor before writing the MCO profile to parameter 8-10 Control Word Profile. |
| WARNING
76 Power Unit Setup |
Cause: The required number of power units does not match the
detected number of active power units. Troubleshooting: - When replacing a drive module, this warning can occur if the power-specific data in the module power card does not match the rest of the drive. Confirm that the spare part and its power card are the correct code number. |
| WARNING
77 Reduced Power Mode |
Cause: The drive is operating in reduced power mode (less than allowed number of inverter sections). The warning is generated on power cycle when the drive is set to run with fewer inverters and remains on. |
| ALARM
78 Tracking Error |
Cause: The difference between setpoint value and actual value
exceeds the value in parameter 4-35 Tracking Error. Troubleshooting: - Disable the function or select an alarm/warning in parameter 4-34 Tracking Error Function. - Investigate the mechanics around the load and motor. Check feedback connections from motor encoder to drive. - Select motor feedback function in parameter 4-30 Motor Feedback Loss Function. - Adjust the tracking error band in parameter 4-35 Tracking Error and parameter 4-37 Tracking Error Ramping. |
| ALARM
79 Illegal Power Section Configuration |
Cause: The scaling card has an incorrect code number or is not installed. The MK102 connector on the power card could not be installed. |
| ALARM
80 Drive Initialized to Default Value |
Cause: Parameter settings are initialized to default settings after
a manual reset. Troubleshooting: - To clear the alarm, reset the unit. |
| ALARM
81 CSIV Corrupt |
Cause: The CSIV file has syntax errors. |
| ALARM
82 CSIV Parameter Error |
Cause: CSIV failed to initialize a parameter. |
| ALARM
83 Illegal Option Combination |
Cause: The mounted options are incompatible. |
| ALARM
84 No Safety Option |
Cause: The safety option was removed without applying a general
reset. Troubleshooting: - Reconnect the safety option. |
| ALARM
88 Option Detection |
Cause: A change in the option layout is detected. Parameter 14-89
Option Detection is set to [0] Frozen configuration and the option layout has
been changed. Troubleshooting: - To apply the change, enable option layout changes in parameter 14-89 Option Detection. - Alternatively, restore the correct option configuration. |
| WARNING
89 Mechanical Brake Sliding |
Cause: The hoist brake monitor detects a motor speed exceeding 10 RPM. |
| WARNING
90 Feedback Monitor |
Cause: A feedback fault is detected. Solution: Check the connection to the encoder/resolver option and, if necessary, replace the VLTÆ Encoder Input MCB 102 or VLTÆ Resolver Input MCB 103. |
| ALARM
91 Analog Input 54 Wrong Settings |
Troubleshooting: - Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54. |
| ALARM
99 Locked Rotor |
Cause: The rotor is blocked. Troubleshooting: - Check if the motor shaft is locked. - Check if the start current triggers the current limit set in parameter 4-18 Current Limit. - Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s]. |
| WARNING
101 Speed monitor |
Cause: The motor speed monitor value is out of range. See parameter 4-43 Motor Speed Monitor Function. |
| ALARM
101 Speed monitor |
Cause: The motor speed monitor value is out of range. See parameter 4-43 Motor Speed Monitor Function. |
| WARNING
104 Mixing Fan Fault |
Cause: The fan is not operating. The fan monitor checks that the fan
is spinning at power-up or whenever the mixing fan is turned on. The mixing
fan fault can be configured as a warning or an alarm in parameter 14-53 Fan
Monitor. Troubleshooting: - Cycle power to the drive to determine if the warning/alarm returns. |
| ALARM
104 Mixing Fan Fault |
Cause: The fan is not operating. The fan monitor checks that the fan
is spinning at power-up or whenever the mixing fan is turned on. The mixing
fan fault can be configured as a warning or an alarm in parameter 14-53 Fan
Monitor. Troubleshooting: - Cycle power to the drive to determine if the warning/alarm returns. |
| WARNING
122 Mot. Rotat. Unexp. |
Cause: The drive performs a function that requires the motor to be at a standstill, for example, DC hold for PM motors. |
| ALARM
122, Mot. Rotat. Unexp. |
Cause: The drive performs a function that requires the motor to be at a standstill, for example, DC hold for PM motors. |
| WARNING
123 Motor Mod. Changed |
Cause: The motor selected in parameter 1-11 Motor Model is not correct. Check the motor model. |
| WARNING
128 Enc. Inc/Abs Res |
Cause: Mismatch between incremental and absolute encoder channels. |
| WARNING
157 Power Limit Mot. |
Cause: The output power exceeds the value defined in parameter 4-82 Power Limit Motor Mode. |
| ALARM
157 Power Limit Mot. |
Cause: The output power exceeds the value defined in parameter 4-82 Power Limit Motor Mode. |
| WARNING
158 Power Limit Gen. |
Cause: The generating power exceeds the value defined in parameter 4-83 Power Limit Generator Mode. |
| ALARM
158 Power Limit Gen. |
Cause: The generating power exceeds the value defined in parameter 4-83 Power Limit Generator Mode. |
| WARNING
163 ATEX ETR Cur.Lim. Warning |
Cause: The drive has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 65% of the allowed thermal overload. |
| Alarm
164 ATEX ETR Cur.Lim. Alarm |
Cause: Running above the characteristic curve for more than 60 s within a period of 600 s activated the alarm, and the drive trips. |
| WARNING
165 ATEX ETR Freq.Lim. Warning |
Cause: The drive has run for more than 50 s below the allowed minimum frequency as set in parameter 1-98 ATEX ETR Interpol. Points.Freq.). |
| ALARM
166 ATEX ETR Freq.Lim. Alarm |
Cause: The drive has run for more than 60 s in a period of 600 s below the allowed minimum frequency as set in parameter 1-98 ATEX ETR Interpol. Points. Freq.). |
| WARNING
210 Position tracking |
Cause: The actual position error exceeds the value in parameter 4-71 Maximum Position Error. Parameter 4-70 Position Error Function defines whether this is a warning or an alarm. |
| ALARM
210 Position tracking |
Cause: The actual position error exceeds the value in parameter 4-71 Maximum Position Error. Parameter 4-70 Position Error Function defines whether this is a warning or an alarm. |
| WARNING
211 Position limit |
Cause: The position is outside the limits defined in parameter 3-06 Minimum Position and parameter 3-07 Maximum Position. Parameter 4-73 Position Limit Function defines the function for this warning/alarm. |
| ALARM
211 Position limit |
Cause: The position is outside the limits defined in parameter 3-06 Minimum Position and parameter 3-07 Maximum Position. Parameter 4-73 Position Limit Function defines the function for this warning/alarm. |
| WARNING
212 Homing not done |
Cause: A homing function is selected in parameter 17-80 Homing Function and absolute positioning is executed before homing is completed. |
| ALARM
212 Homing not done |
Cause: A homing function is selected in parameter 17-80 Homing Function and absolute positioning is executed before homing is completed. |
| ALARM
213 Homing timeout |
Cause: Homing was started but did not finish within the time defined in parameter 17-85 Homing Timout. |
| ALARM
214 No sensor input |
Cause: A homing process with a homing function that requires a sensor, or touch probe positioning is started with no input defined for the sensor. |
| WARNING
215 Start Fwd/Rev |
Cause: One of the hardware end-limit options, [12] Enable Start Forward or [13] Enable Start Reverse is active. |
| ALARM
215 Start Fwd/Rev |
Cause: One of the hardware end-limit options, [12] Enable Start Forward or [13] Enable Start Reverse is active. |
| WARNING
216 Touch Timeout |
Cause: A touch probe sensor is not found within the time in parameter 4-75 Touch Timout. The timeout timer is started as soon as the touch probe positioning is activated even if the application is not moving. |
| ALARM
216 Touch Timeout |
Cause: A touch probe sensor is not found within the time in parameter 4-75 Touch Timout. The timeout timer is started as soon as the touch probe positioning is activated even if the application is not moving. |
| WARNING
220 Configuration file version not supported |
Cause: The frequency converter does not support the current configuration file version. Customization is aborted. |
| ALARM
246 Power card supply |
Cause: This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 46, Power card supply. The report value in the alarm log indicates which power module generated the alarm: - 1 = Inverter module to the far left. - 2 = Middle inverter module in F2 or F4 frequency converter. - 2 = Right inverter module in F1 or F3 frequency converter. - 3 = Right inverter module in F2 or F4 frequency converter. - 5 = Rectifier module. |
| WARNING
249 Rect. low temperature |
Cause: The temperature of the rectifier heat sink is lower than
expected. Troubleshooting: - Check the temperature sensor. |
| WARNING
250 New spare part |
Cause: The power or switch mode supply has been exchanged. Restore the drive type code in the EEPROM. Select the correct type code in parameter 14-23 Typecode Setting according to the label on the drive. Remember to select Save to EEPROM at the end. |
| WARNING
251 New Typecode |
Cause: The power card or other components have been replaced, and
the type code has changed. Troubleshooting: - Reset the drive for normal operation. |
| WARNING
253 Digital output X49/9 overload |
Cause: Digital output X49/9 is overloaded. |
| WARNING
254 Digital output X49/11 overload |
Cause: Digital output X49/11 is overloaded. |
| WARNING
255 Digital output X49/7 overload |
Cause: Digital output X49/7 is overloaded. |
| ALARM
430 PWM Disabled |
Cause: The PWM on the power card is disabled. |
How to Read FC 301 Faults via LCP & MCT 10
The Automation Drive series offers one of the best user interfaces in the industry. In 2026, you can diagnose issues quickly using the onboard tools or PC software:
- LCP 102 (Graphical Display): The detachable panel is your primary tool.
- Info Button: When an alarm appears (e.g., Alarm 13 Overcurrent), pressing the [Info] button provides an on-screen explanation of the fault and troubleshooting steps without needing the manual.
- Alarm Log: Navigate to Main Menu > 15-** Drive Information > 15-3* Alarm Log. This stores the last 10 alarms with timestamps and the values of the DC Bus and Current at the moment of the trip.
- MCT 10 (Motion Control Tool): Connect your PC via the USB port on the front (or via Fieldbus). MCT 10 allows you to use the Scope function to trace complex motion issues, such as following errors in positioning applications (common on FC 301).
- Trip vs. Trip Lock:
- Trip: The drive stops, but can be reset via the panel or digital input.
- Trip Lock: A severe fault (like Ground Fault or Short Circuit). The drive protects itself by requiring you to disconnect main power and wait for the display to turn off before a reset is possible.
Frequently Asked Questions (FAQ)
Q: What is “Alarm 68” (Safe Stop / Safe Torque Off)?
A: This is the most common inquiry for the FC 301.
- Safe Stop is activated via Terminal 37 (Yellow terminal).
- If you see Alarm 68, it means the 24V signal to Terminal 37 is missing. Check your emergency stop button, safety relay, or door interlock.
- To reset, restore 24V to Terminal 37 and send a Reset signal.
Q: How do I reset a Danfoss FC 301 fault?
A:
- Press the Reset button on the LCP 102.
- Toggle the Digital Input configured for “Reset” (Default is often Terminal 27).
- Send the Reset Word via Fieldbus (Profinet, Ethernet/IP, etc.).
- For Trip Lock faults, power cycle the drive.
Q: Why does the drive trip on “Alarm 14” (Earth Fault)?
A: The FC 301 has very sensitive ground fault detection.
- Disconnect the motor leads (U, V, W) and run the drive empty. If it does not trip, the issue is in the motor or cable.
- If using a very long motor cable (over 150m), capacitive leakage to the ground can trigger this alarm. You may need an output filter (dC/dt or Sine Wave).