Danfoss VLT Midi Drive FC280 Fault Codes List
Access the complete reference guide for Danfoss VLT Midi Drive FC 280 fault codes. Learn to diagnose Safe Stop (Alarm 68), use the Memory Module for cloning, and retrofit VLT 2800 units.
Danfoss FC 280 Fault Codes Reference Table
Danfoss VLT® Midi Drive FC 280 Faults and Alarms
Danfoss VLT® Midi Drive FC 280 Warnings and Alarms
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 2 Live zero error |
Cause: Signal on terminal 53 or 54 is less than 50% of value set in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54 Low Voltage, and parameter 6-22 Terminal 54 Low Current.
Remedy:
|
| 3 No motor |
Cause: No motor has been connected to the output of the drive.
Remedy:
|
| 4 Mains phase loss |
Cause: Missing phase on the supply side, or the voltage imbalance is too high. This can also indicate a fault in the input rectifier.
Remedy:
|
| 7 DC overvoltage |
Cause: DC-link voltage exceeds the limit.
Remedy:
|
| 8 DC undervoltage |
Cause: DC-link voltage drops below the voltage warning low limit.
Remedy:
|
| 9 Inverter overloaded |
Cause: More than 100% load for too long.
Remedy:
|
| 10 Motor ETR overtemperature |
Cause: The motor is too hot due to more than 100% load for too long.
Remedy:
|
| 11 Motor thermistor overtemperature |
Cause: Thermistor or thermistor connection is disconnected, or the motor is too hot.
Remedy:
|
| 12 Torque limit |
Cause: Torque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode.
Remedy:
|
| 13 Overcurrent |
Cause: Inverter peak current limit is exceeded. If this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
Remedy:
|
| 14 Ground fault |
Cause: Discharge from output phases to ground, either in the cable or the motor.
Remedy:
|
| 16 Short circuit |
Cause: Short circuit in the motor or on motor terminals.
Remedy:
|
| 17 Control word timeout |
Cause: No communication to the drive.
Remedy:
|
| 25 Brake resistor short-circuited |
Cause: Brake resistor is short-circuited, thus the brake function is disconnected.
Remedy:
|
| 26 Brake overload |
Cause: The power transmitted to the brake resistor over the last 120 s exceeds the limit.
Remedy:
|
| 27 Brake IGBT/Brake chopper short-circuited |
Cause: Brake transistor is short-circuited, thus the brake function is disconnected.
Remedy:
|
| 28 Brake check |
Cause: The brake resistor is not connected or not working.
Remedy:
|
| 30 U phase loss |
Cause: Motor phase U is missing.
Remedy:
|
| 31 V phase loss |
Cause: Motor phase V is missing.
Remedy:
|
| 32 W phase loss |
Cause: Motor phase W is missing.
Remedy:
|
| 34 Fieldbus fault |
Cause: Fieldbus communication issues have occurred.
Remedy:
|
| 35 Option fault |
Cause: Fieldbus detects internal faults.
Remedy:
|
| 36 Mains failure |
Cause: This warning/alarm is only active if the supply voltage to the drive is less than the value set in parameter 14-11 Mains Fault Voltage Level, and parameter 14-10 Mains Failure is NOT set to No Function.
Remedy:
|
| 38 Internal fault |
Cause: An internal fault has occurred.
Remedy:
|
| 40 Overload T27 |
Cause: Check the load connected to terminal 27 or remove short-circuit connection.
Remedy:
|
| 46 Gate drive voltage fault |
Cause: Internal power supply issue.
Remedy:
|
| 47 24 V supply low |
Cause: 24 V DC may be overloaded.
Remedy:
|
| 49 Speed limit |
Cause: The motor speed is below the specified limit in parameter 1-87 Trip Speed Low [Hz].
Remedy:
|
| 50 AMA calibration failed |
Cause: A calibration error has occurred.
Remedy:
|
| 51 AMA check Unom and Inom |
Cause: Wrong setting for motor voltage and/or motor current.
Remedy:
|
| 52 AMA low Inom |
Cause: Motor current is too low.
Remedy:
|
| 53 AMA big motor |
Cause: The power size of the motor is too large for the AMA to operate.
Remedy:
|
| 54 AMA small motor |
Cause: The power size of the motor is too small for the AMA to operate.
Remedy:
|
| 55 AMA parameter range |
Cause: The parameter values of the motor are outside of the acceptable range. AMA does not run.
Remedy:
|
| 56 AMA interrupt |
Cause: The AMA is interrupted by the user.
Remedy:
|
| 57 AMA timeout |
Cause: AMA is taking too long to complete.
Remedy:
|
| 58 AMA internal |
Cause: Internal fault during AMA.
Remedy:
|
| 59 Current limit |
Cause: Drive overload. The current is higher than the value in parameter 4-18 Current Limit.
Remedy:
|
| 60 External Interlock |
Cause: External interlock has been activated.
Remedy:
|
| 61 Encoder loss |
Cause: The drive is not receiving a signal from the encoder.
Remedy:
|
| 63 Mechanical brake low |
Cause: Actual motor current has not exceeded release brake current within the start delay time window.
Remedy:
|
| 65 Control card temp |
Cause: The cutout temperature of the control card has exceeded the upper limit.
Remedy:
|
| 67 Option change |
Cause: A new option is detected or a mounted option is removed.
Remedy:
|
| 68 Safe Torque Off |
Cause: STO is activated.
Remedy:
|
| 69 Power card temp |
Cause: The cutout temperature of the power card has exceeded the upper limit.
Remedy:
|
| 80 Drive initialized to default value |
Cause: All parameter settings are initialized to default settings.
Remedy:
|
| 87 Auto DC brake |
Cause: Occurs in IT mains when the drive coasts, and the DC voltage is higher than 830 V for 400 V units and 425 V for 200 V units. The motor consumes energy on the DC link.
Remedy:
|
| 88 Option detection |
Cause: The option is removed successfully.
Remedy:
|
| 95 Broken belt |
Cause: A broken belt has been detected.
Remedy:
|
| 99 Locked rotor |
Cause: Rotor is blocked.
Remedy:
|
| 120 Position control fault |
Cause: An error has occurred in the position control.
Remedy:
|
| 126 Motor rotating |
Cause: PM motor is rotating when AMA is performed.
Remedy:
|
| 127 Back EMF too high |
Cause: The back EMF of the PM motor is too high before starting.
Remedy:
|
| 188 STO internal fault |
Cause: 24 V DC supply is connected to only 1 of the 2 STO terminals (37 and 38), or a failure in STO channels is detected.
Remedy:
|
| nw run Not while running |
Cause: Parameters can only be changed when the motor is stopped.
Remedy:
|
| Err. A wrong password was entered |
Cause: Occurs when using a wrong password for changing a password-protected parameter.
Remedy:
|
How to Read FC 280 Faults via LCP & Memory Module
The FC 280 brings modern connectivity to the “Midi” drive segment. In 2026, diagnostics are streamlined using these tools:
- LCP Options (Numerical vs. Graphical):
- LCP 21 (Numerical): Standard on many units. Displays simple codes (e.g., “AL 13”).
- LCP 102 (Graphical): You can plug in the advanced LCP 102 from an FC 302 to get full-text error descriptions and a “Help” button feature during commissioning or troubleshooting.
- VLT Memory Module (MCM 102): The FC 280 stores its firmware and parameters on a removable memory module.
- Rapid Replacement: If a drive fails with a “Hardware Trip” (e.g., Alarm 16 Short Circuit), you can simply pull the MCM 102 module out and plug it into a new FC 280. The new drive will be up and running in seconds without needing a PC to reprogram it.
- Built-in USB Port: Unlike the older VLT 2800 which required RS-485 adapters, the FC 280 has a dedicated USB port. Connect MCT 10 software directly to view the Alarm Log and Scope real-time motor data.
Frequently Asked Questions (FAQ)
Q: What is “Alarm 68” (Safe Stop / Safe Torque Off)?
A: The FC 280 includes dual-channel Safe Torque Off (STO).
- Alarm 68: Indicates the 24V safety signal is missing on Terminal 37 (and Terminal 38 if dual-channel is used).
- Action: Check your safety relays, door switches, or E-Stops. If STO is not required, ensure the factory jumpers are installed correctly between 24V and the safety terminals.
Q: Can I replace a VLT 2800 with an FC 280 easily?
A: Yes. The FC 280 is designed as a retrofit solution.
- Danfoss offers adapter plates to fit the FC 280 into the exact footprint of the VLT 2800.
- You can use the VLT 2800 Conversion Tool in MCT 10 software to migrate your old parameter file to the new drive automatically.
Q: How do I reset a Danfoss FC 280 fault?
A:
- Press the Reset button on the LCP.
- Toggle the Digital Input configured for Reset (Default is Terminal 27).
- Trip Lock: For severe faults (Earth Fault, Short Circuit), you must disconnect mains power and wait for the LED to turn off before resetting.
Q: Why does the drive show “Warning 12” (Torque Limit)?
A: This means the motor requires more torque than the drive is allowed to deliver (based on current limits).
- Check for mechanical binding (jammed conveyor).
- Verify the Ramp Up Time is not too aggressive for the load.
- Ensure the motor data (AMA) has been performed.
Comments
Post a Comment