Emotron VS10 Drive Fault Codes List

Having trouble with an Emotron VS10 compact drive? Learn how to diagnose, troubleshoot, and reset common hexadecimal fault codes and status LEDs safely.

The Emotron VS10 (by CG Drives & Automation) is a highly flexible, compact AC motor drive designed for pumps, fans, compressors, and constant torque applications such as conveyors . Covering motors in the power range of 0.25 kW to 2.2 kW, this drive incorporates advanced control architectures and communication options in a small physical format.

Emotron VS10 Fault Codes Reference Table

Refer to your specific diagnostic tables to identify the exact 4-digit hexadecimal code currently active on your drive's display. Knowing the active hex code points you directly to the affected electrical circuit or parameter path.

Emotron VS10 Drive Fault Codes List

Emotron VS10 Drive Fault Codes List

Fault Code and Meaning Cause and Remedy
8784 | 0x2250

PU over current
CiA: Continuous over current (internal)
Cause:

This message contains three errors:
  • Continuous overcurrent on the inverter/motor side.
  • Overcurrent at the brake chopper (brake transistor).
  • DC bus relay has not been closed due to a malfunction.


Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
8992 | 0x2320

Earth leak
CiA: Short circuit/earth leakage (internal)
Cause:

Short circuit/earth leakage detected on the internal/motor side.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
9024 | 0x2340

Motor shorted
CiA: Short circuit (device internal)
Cause:

Device internal short circuit or short circuit of motor cable.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
9040 | 0x2350

Motor i2t OL
CiA: i²*t overload (thermal state)
Cause:

Thermal overload of the motor.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s.)
No adjustment parameters defined.
9090 | 0x2382

Ixt error
I*t error
Cause:

The device utilisation has exceeded the warning threshold set in 0x2D40:002 (default setting: 95 %).

Remedy:

Response: Fault (The error can only be reset after a blocking time of 3 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
Adjustable in: 0x2D40:005 (P135.05)
9091 | 0x2383

Ixt warning
I*t warning
Cause:

The device utilisation has exceeded the permanent error threshold of 100 %.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
9095 | 0x2387

Clamp timeout
Imax: Clamp responded too often
Cause:

"Clamp" = short-time inhibit of the inverter in V/f operation when the current limit shown in 0x2DDF:002 is reached.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
9096 | 0x2388

SLPSM stall det.
SLPSM stall detection active
Cause:

Stalling protection for the sensorless control for synchronous motors (SLPSM) is active.
  • Possible cause: Overload of the motor.


Remedy:

Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
12576 | 0x3120

Mains Phase fail
Mains phase fault
Cause:

Mains phase fault.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
12816 | 0x3210

DC Bus OV
DC bus overvoltage
Cause:

The DC-bus voltage of the inverter has exceeded the error threshold for overvoltage. The error threshold results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
12817 | 0x3211

Warn.DC Bus OV
DC bus overvoltage warning
Cause:

The DC-bus voltage of the inverter has exceeded the warning threshold for overvoltage set in 0x2540:005 (P208.05).

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
12832 | 0x3220

DC Bus UV
DC bus undervoltage
Cause:

The DC-bus voltage of the inverter has fallen below the error threshold for undervoltage. The error threshold results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Remedy:

Response: Trouble
No adjustment parameters defined.
12833 | 0x3221

Warn.DC Bus UV
DC bus undervoltage warning
Cause:

The DC-bus voltage of the inverter has fallen below the warning threshold for undervoltage set in 0x2540:002 (P208.02).

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
12834 | 0x3222

DC-bus on-UV
DC-bus voltage to low for power up
Cause:

DC-bus voltage is too low for power up.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
16912 | 0x4210

PU Overtemp.
PU: overtemperature fault
Cause:

Temperature monitoring of the power unit has been triggered.
  • Ambient temperature too high.
  • Fan or ventilation slots are polluted.
  • Fan is defective.


Remedy:

Response: Fault
  • Provide for a sufficient cooling of the device.
  • Clean fan and ventilation slots.
  • If required, replace fan.
  • Set a variable switching frequency in for the inverter. The switching frequency is then automatically reduced if the output current or temperature of the power unit are too high.
17024 | 0x4280

Heatsink sensor
Heat sink temperature sensor fault
Cause:

The sensor for temperature monitoring of the power unit provides implausible measured values. This indicates a hardware defect of the sensor. As a result of the failure of the temperature monitoring, there is a risk of fire by overheating!

Remedy:

Response: Fault
  • This error cannot be corrected by the user. Consultation with the manufacturer is required.
17025 | 0x4281

Heatsink fan
Heat sink fan warning
Cause:

Heat sink fan warning triggered.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
17029 | 0x4285

Warn.PU Overtemp
PU overtemperature warning
Cause:

The temperature of the power section has exceeded the warning threshold for overtemperature.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
17168 | 0x4310

Overtemp. motor
Motor temperature error
Cause:

Motor temperature error.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s.)
No adjustment parameters defined.
20754 | 0x5112

24V supply low
24 V supply critical
Cause:

24 V supply is critical.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
20864 | 0x5180

Overlaod 24V
Overload 24 V supply
Cause:

Overload on the 24 V supply.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
21376 | 0x5380

Incomp. OEM HW
OEM hardware incompatible
Cause:

OEM hardware incompatible.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24592 | 0x6010

Watchdog timeout
Watchdog time-out
Cause:

Watchdog time-out.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
24961 | 0x6181

Timeout-125usTsk
Time-out in 125 us task
Cause:

Time-out in 125 us task.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24962 | 0x6182

Timeout-250usTsk
Time-out in 250 us task
Cause:

Time-out in 250 us task.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24963 | 0x6183

Timeout-1ms-Task
Time-out in 1 ms task
Cause:

Time-out in 1 ms task.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24964 | 0x6184

Timeout-8ms-Task
Time-out in 8 ms task
Cause:

Time-out in 8 ms task.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24968 | 0x6188

Internal error
Internal error
Cause:

Internal system error.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
24969 | 0x6189

PU Prog. error
PU: programming fault
Cause:

PU: programming fault.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24970 | 0x618A

Internal fan
Internal fan warning
Cause:

Internal fan warning.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
24976 | 0x6190

PU comm mismatch
PU: communication mismatch
Cause:

PU: communication mismatch.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24977 | 0x6191

PU Sync. Fault
PU: communication not synchronous
Cause:

PU: communication not synchronous.

Remedy:

Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24978 | 0x6192

Comm.error PU-CU
Communication error PU-CU
Cause:

Communication error PU-CU.

Remedy:

Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24979 | 0x6193

PU comm error
PU: communication error
Cause:

If this error occurs, the motor may not be able to be brought to standstill anymore. If communication is lost completely, the power output stage will switch off.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24980 | 0x6194

PU SDO comm err.
SDO communication with PU aborted
Cause:

SDO communication with PU aborted.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
24981 | 0x6195

I2C conn. error
I2C connection lost
Cause:

I2C connection lost.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
24982 | 0x6196

I2C bus error
I2C bus error
Cause:

I2C bus error.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
25008 | 0x61B0

PU uC supply err
PU: uC supply voltage drop down
Cause:

A supply voltage drop for the microprocessor of the power unit has been detected.

Remedy:

Response: Fault
No adjustment parameters defined.
25009 | 0x61B1

PU general error
PU: general error
Cause:

PU: general error.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
No adjustment parameters defined.
25216 | 0x6280

P400 config err
Trigger/functions connected incorrectly
Cause:

The assignment directives have not been observed:
  • If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!
  • In case of keypad or network control, the two functions "Enable inverter" and "Run" can also be set to "Constant TRUE [1]" to start the motor.
  • The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" and viceversa.


Remedy:

Response: Trouble
No adjustment parameters defined.
25217 | 0x6281

User fault 1
User-defined fault 1
Cause:

The "Activate fault 1" function was triggered via the flexible I/O configuration. The error can only be reset after the function has been deactivated again.

Remedy:

Response: Fault
No adjustment parameters defined.
25218 | 0x6282

User fault 2
User-defined fault 2
Cause:

The "Activate fault 2" function was triggered via the NetWordIN1 data word (or flexible I/O configuration). The error can only be reset after the function has been deactivated again.

Remedy:

Response: Fault
No adjustment parameters defined.
25232 | 0x6290

Invert rotation
Warning invert rotation
Cause:

The "Invert rotation" function was requested with an active limitation of rotation.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
25233 | 0x6291

Trouble overflow
Maximum allowed troubles exceeded
Cause:

Maximum allowed troubles exceeded.

Remedy:

Response: Fault
No adjustment parameters defined.
25248 | 0x62A0

AC Dr. UserFault
AC Drive: user fault
Cause:

The "Activate fault" function was triggered via the AC drive control word. The error can only be reset after the function has been deactivated again.

Remedy:

Response: Fault
No adjustment parameters defined.
25249 | 0x62A1

Netw.UserFault 1
Network: user fault 1
Cause:

The "Activate fault 1" function was triggered via the NetWordIN1 data word. The error can only be reset after the function has been deactivated again.

Remedy:

Response: Fault
No adjustment parameters defined.
25250 | 0x62A2

Netw.UserFault 2
Network: user fault 2
Cause:

The "Activate fault 2" function was triggered via the NetWordIN1 data word. The error can only be reset after the function has been deactivated again.

Remedy:

Response: Fault
No adjustment parameters defined.
25265 | 0x62B1

NetWordIN1 error
NetWordIN1 configuration incorrect
Cause:

Two bits of the NetWordIN1 data word were assigned to the same function.

Remedy:

Response: Trouble
Check and correct the NetWordIN1 data word. The functions that are to be triggered via bit 0 ... 15 of the NetWordIN1 data word, are defined in 0x400E:001 (P505.01) ... 0x400E:016 (P505.16).
25504 | 0x63A0

EEPROM fault
On-board EEPROM: access error
Cause:

On-board EEPROM: access error.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
25505 | 0x63A1

CU ID tag error
CU: load error ID tag
Cause:

CU: load error ID tag.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
25506 | 0x63A2

PU ID tag error
PU: load error ID tag
Cause:

PU: load error ID tag.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
25507 | 0x63A3

PU unknown
Power unit unknown
Cause:

Power unit unknown.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
25508 | 0x63A4

EEPROM overflow
On-board EEPROM: timer overflow
Cause:

On-board EEPROM: timer overflow.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
28800 | 0x7080

Assertionlevel
Assertion level monitoring (Low/High)
Cause:

The last setting of the connection level differs from the saved setting.

Remedy:

Response: Fault
Check setting in Assertationlevel. Execute device command "Save user data" 0x2022:003 (P700.03). Switch inverter off and on again.
28801 | 0x7081

AI1 fault
Analog input 1 fault
Cause:

The monitoring function of the input signal configured for the analog input 1 has been triggered.

Remedy:

Response: Fault
Adjustable in: 0x2636:010 (P430.10)
28802 | 0x7082

AI2 fault
Analog input 2 fault
Cause:

The monitoring function of the input signal configured for the analog input 2 has been triggered.

Remedy:

Response: Fault
Adjustable in: 0x2637:010 (P431.10)
28803 | 0x7083

HTL input fault
HTL input fault
Cause:

HTL input fault. Error message is not available for the inverter Emotron VS10/30.

Remedy:

Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)
No adjustment parameters defined.
28833 | 0x70A1

AO1 fault
Analog output 1 fault
Cause:

Analog output 1 fault.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
28834 | 0x70A2

AO2 fault
Analog output 2 fault
Cause:

Analog output 2 fault. Error message is not available for the inverter Emotron VS10/30.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
28961 | 0x7121

Pole pos. error
Pole position identification fault
Cause:

Pole position identification fault.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
Adjustable in: 0x2C60
29056 | 0x7180

Mot max current
Motor overcurrent
Cause:

Motor overcurrent threshold exceeded.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 1 s.)
Adjustable in: 0x2D46:002 (P353.02)
30336 | 0x7680

EPM full
Memory module is full
Cause:

The memory module contains too many parameter settings. The inverter copies the current backup to the user memory without overwriting the data in the RAM.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
Execute device command "Save user data" 0x2022:003 (P700.03) again. This reinitialises the user memory with the current parameter settings. By this means, parameter settings no longer required are deleted automatically.
30337 | 0x7681

EPM not present
Memory module not present
Cause:

The default setting saved in the inverter firmware is loaded. The error cannot be reset by the user.

Remedy:

Response: Fault
  • Switch off inverter.
  • Plug the memory module into the inverter.
  • Switch the inverter on again.
30338 | 0x7682

EPM invalid data
Memory module invalid user data
Cause:

The user parameter settings are invalid both in the user memory and in the backup. Thus, the user parameter settings are lost. The default setting is loaded automatically.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
  • Execute user parameter settings again.
  • Execute device command "Save user data" 0x2022:003 (P700.03).
30340 | 0x7684

Save incomplete
Data not compl. saved before powerdown
Cause:

Saving the parameter settings was interrupted by an unexpected disconnection. The user parameter settings were not saved completely. When the inverter is switched on the next time, the backup data is copied to the user memory.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
  • Check user parameter settings. (The loaded backup is an older version.)
  • If required, repeat the changes made last.
  • Execute device command "Save user data" 0x2022:003 (P700.03).
30342 | 0x7686

Net.config.error
Network: configuration error
Cause:

The expected network option is missing. This error can only occur if the control unit has been replaced by a control unit with different features.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
  • Switch off inverter.
  • Install control unit with matching network option.
  • Switch the inverter on again.
30343 | 0x7687

EPM timer overfl
Memory module: timer overflow
Cause:

During the read/write access to the memory module, a time-out has occurred, e.g. because the memory module has been removed.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
30345 | 0x7689

OEM data invalid
Memory module: invalid OEM data
Cause:

The OEM memory contains invalid parameter settings or is empty. The user parameter settings are loaded automatically.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
Execute device command "Save OEM data" 0x2022:006 (P700.06). Thus, the user parameter settings get lost!
30346 | 0x768A

Wrong EPM
Memory module: wrong type
Cause:

The plugged-in memory module is not supported by the inverter. The default setting saved in the inverter firmware is loaded. The error cannot be reset by the user.

Remedy:

Response: Fault
  • Switch off inverter.
  • Replace plugged-in memory module by a memory module that matches the inverter.
  • Switch the inverter on again.
30352 | 0x7690

EPM-FW incomp.
EPM firmware version incompatible
Cause:

The parameter settings saved in the memory module do not match the firmware version. The data are loaded into the RAM memory, but are incompatible.

Remedy:

Response: Fault
Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30353 | 0x7691

EPM: FW incomp.
EPM data: firmware type incompatible
Cause:

The parameter settings saved in the memory module do not match the firmware type. The data are loaded into the RAM memory, but are incompatible.

Remedy:

Response: Fault
Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30354 | 0x7692

UserCU not match
EPM data: new firmware type detected
Cause:

The parameter settings saved in the memory module do not match in the inverter hardware. The data is loaded into the RAM memory and is compatible. However, the settings must be accepted by the user.

Remedy:

Response: Fault
Reset error. Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on. Alternatively, the default setting can be loaded and then saved.
30355 | 0x7693

EPM PU size inco
EPM data: PU size incompatible
Cause:

The parameter settings saved in the memory module do not match the power unit. The data are loaded into the RAM memory, but are incompatible.

Remedy:

Response: Fault
Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30356 | 0x7694

EPM new PU size
EPM data: new PU size detected
Cause:

The parameter settings saved in the memory module do not match in the inverter hardware. The data is loaded into the RAM memory and is compatible. However, the settings must be accepted by the user.

Remedy:

Response: Fault
Reset error. Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on. Alternatively, the default setting can be loaded and then saved.
30357 | 0x7695

InvalidChgovrCfg
Invalid parameter changeover configuration
Cause:

One or several parameters cannot be used for the "parameter change-over" function. The parameter change-over is deactivated.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
Check error message for parameter change-over in 0x4047:001 (P756.01) and correct the list entry displayed in 0x4047:002 (P756.02).
30358 | 0x7696

Unkn. Par in EPM
EPM data: unknown parameter found
Cause:

The memory module contains parameter settings for one or several parameters that are not known to the inverter.

Remedy:

Response: Info (Information only)
Execute device command "Save user data" 0x2022:003 (P700.03). This reinitialises the user memory with the current parameter settings. By this means, parameter settings no longer required are deleted automatically.
30359 | 0x7697

Parameter loss
Parameter changes lost
Cause:

Changed parameter settings got lost due to the removal of the 24-V voltage supply.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)
In order to reset the error, there are the following options: Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03). Switch inverter off and on again without plugged-in USB module.
33045 | 0x8115

Time-out (PAM)
Time-out (PAM)
Cause:

The parameter access monitoring has been triggered.

Remedy:

Response: No response
Adjustable in: 0x2552:004 (P595.04)
33154 | 0x8182

CAN bus off
CAN: bus off
Cause:

A change to the "Bus-Off" state has been made.

Remedy:

Response: Trouble
Adjustable in: 0x2857:010
33155 | 0x8183

CAN bus warning
CAN: warning
Cause:

CAN bus warning level reached.

Remedy:

Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)
Adjustable in: 0x2857:011
33156 | 0x8184

CAN heartb. C1
CAN: heartbeat time-out consumer 1
Cause:

Heartbeat time-out consumer 1 triggered.

Remedy:

Response: Fault
Adjustable in: 0x2857:005
33157 | 0x8185

CAN heartb. C2
CAN: heartbeat time-out consumer 2
Cause:

Heartbeat time-out consumer 2 triggered.

Remedy:

Response: Fault
Adjustable in: 0x2857:006
33158 | 0x8186

CAN heartb. C3
CAN: heartbeat time-out consumer 3
Cause:

Heartbeat time-out consumer 3 triggered.

Remedy:

Response: Fault
Adjustable in: 0x2857:007
33159 | 0x8187

CAN heartb. C4
CAN: heartbeat time-out consumer 4
Cause:

Heartbeat time-out consumer 4 triggered.

Remedy:

Response: Fault
Adjustable in: 0x2857:008
33168 | 0x8190

Watchdog timeout
Network: watchdog timeout
Cause:

Network watchdog timeout triggered.

Remedy:

Response: Fault
No adjustment parameters defined.
33170 | 0x8192

Net. Init. error
Network: initialisation error
Cause:

Network communication stack initialisation failed.

Remedy:

Response: Fault
No adjustment parameters defined.
33171 | 0x8193

Inv. cyclic data
Network: invalid cyclic process data
Cause:

Invalid cyclic process data packets received.

Remedy:

Response: Trouble
No adjustment parameters defined.
33184 | 0x81A0

Modbus TX error
Modbus transmit message error
Cause:

Modbus transmit message error.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
33185 | 0x81A1

Modbus time-out
Modbus: network time-out
Cause:

No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2858:002 (P515.02).

Remedy:

Response: Fault
Adjustable in: 0x2858:001 (P515.01)
33186 | 0x81A2

Modbus request
Modbus: incorrect request by master
Cause:

Modbus: incorrect request sent by master.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
33414 | 0x8286

PDO map error
Network: PDO mapping error
Cause:

Network: PDO mapping configuration error.

Remedy:

Response: Fault
No adjustment parameters defined.
33425 | 0x8291

Timeout RPDO1
CAN: RPDO1 time-out
Cause:

The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.

Remedy:

Response: Fault
Adjustable in: 0x2857:001
33426 | 0x8292

Timeout RPDO2
CAN: RPDO2 time-out
Cause:

The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.

Remedy:

Response: Fault
Adjustable in: 0x2857:002
33427 | 0x8293

Timeout RPDO3
CAN: RPDO3 time-out
Cause:

The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.

Remedy:

Response: Fault
Adjustable in: 0x2857:003
33553 | 0x8311

Torque limit
Torque limit reached
Cause:

The maximum possible torque has been reached and the deceleration time set in 0x2D67:002 (P329.02) has elapsed.

Remedy:

Response: No response
Adjustable in: 0x2D67:001 (P329.01)
36992 | 0x9080

Keypad removed
Keypad removed
Cause:

The keypad was removed while the keypad control was activated.

Remedy:

Response: Fault
Plug on the keypad again or activate another control source.
65282 | 0xFF02

BrkResistor OL.F
Brake resistor: overload fault
Cause:

Brake resistor overload fault. Error message is not available for the inverter Emotron VS10/30.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 5 s.)
No adjustment parameters defined.
65285 | 0xFF05

STO error
Safe Torque Off error
Cause:

Safe Torque Off error detected.

Remedy:

Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)
No adjustment parameters defined.
65286 | 0xFF06

Motor overspeed
Motor overspeed
Cause:

The motor speed has reached the error threshold for overspeed.

Remedy:

Response: Fault (The error can only be reset after a blocking time of 1 s.)
Adjustable in: 0x2D44:002 (P350.02)
65289 | 0xFF09

Mot.Phase miss.
Motor phase missing
Cause:

A failure of several motor phases has been detected.

Remedy:

Response: No response (The error can only be reset after a blocking time of 2 s.)
Adjustable in: 0x2D45:001 (P310.01)
Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65290 | 0xFF0A

Phase U failure
Motor phase failure phase U
Cause:

A failure of the motor phase U has been detected.

Remedy:

Response: No response (The error can only be reset after a blocking time of 2 s.)
Adjustable in: 0x2D45:001 (P310.01)
Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65291 | 0xFF0B

Phase V failure
Motor phase failure phase V
Cause:

A failure of the motor phase V has been detected.

Remedy:

Response: No response (The error can only be reset after a blocking time of 2 s.)
Adjustable in: 0x2D45:001 (P310.01)
Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65292 | 0xFF0C

Phase W failure
Motor phase failure phase W
Cause:

A failure of the motor phase W has been detected.

Remedy:

Response: No response (The error can only be reset after a blocking time of 2 s.)
Adjustable in: 0x2D45:001 (P310.01)
Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65305 | 0xFF19

Motor ID fault
Motor parameter identification fault
Cause:

During the automatic identification of the motor, an error has occurred.

Remedy:

Response: Fault
No adjustment parameters defined.
65334 | 0xFF36

BrkResistor OL.W
Brake resistor: overload warning
Cause:

Brake resistor overload warning. Error message is not available for the inverter Emotron VS10/30.

Remedy:

Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)
No adjustment parameters defined.
65335 | 0xFF37

Auto start disab
Automatic start disabled
Cause:

When the mains power was switched on, there was already a start command and the automatic start at power-up is set to "Off [0]" in 0x2838:002 (P203.02).

Remedy:

Response: Fault
Deactivate start command and reset error.
65366 | 0xFF56

Max. motor freq.
Maximum motor frequency reached
Cause:

The maximum motor speed set in 0x6080 (P322.00) is active.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.
65413 | 0xFF85

Keypad full ctrl
Keypad full control active
Cause:

The "Keypad Full Control" control mode is active. Both the control and the setpoint selection are made via the keypad. A renewed click of the keypad key CTRL serves to stop the control mode again.

Remedy:

Response: Warning (Logging only inside Error history buffer/Logbook)
No adjustment parameters defined.

How to Safely Reset an Emotron VS10 Fault

Before initiating a reset, ensure that the underlying issue causing the trip is resolved. The VS10 provides three main pathways to clear an active fault :

  1. Keypad Reset: Press the stop/reset key directly on the front panel of the attached graphic HMI .
  2. Digital Input Reset: By default, Digital Input 3 (DI3) on the control terminal strip is assigned to the "Reset fault" function . Applying a momentary 24V signal to DI3 will clear the active trip .
  3. Power Cycle (Power-On Reset): Disconnect the incoming AC power lines . Safety Requirement: High residual DC bus voltage remains stored in the capacitors . You must wait a minimum of 5 to 10 minutes to allow the internal capacitors to discharge below dangerous levels before handling wiring or restoring power.

Most Common VS10 Faults and Diagnostic Steps

While the diagnostic system covers a wide range of protections, several common hexadecimal faults account for the majority of industrial trips :

1. 0x3210 / 0x3211 (DC Link Overvoltage)

This code triggers when the voltage on the intermediate DC bus rises above the drive's safe operating limit . This typically occurs during rapid deceleration of high-inertia loads when the motor regenerates kinetic energy back into the drive .

  • Diagnostic: Try increasing the deceleration ramp time (Parameter P221.00) . If the application requires fast stops, ensure a dynamic braking module is configured .

2. 0x3220 / 0x3221 (DC Link Undervoltage)

This fault indicates that the DC bus voltage has dropped below the minimum operating limit . It is typically caused by a sag in input line voltage, a tripped upstream breaker, or a blown mains fuse .

  • Diagnostic: Check the incoming utility line voltages with a digital multimeter under load conditions. Verify that all power connections are tight .

3. 0x4210 (Power Unit Overtemperature)

This protection triggers when the drive's internal power assembly temperature (heatsink) exceeds its maximum safe limit .

  • Diagnostic: Check that the drive's cooling fan is spinning freely and clean any dust or debris accumulation from the heatsink fins and ventilation slots . Ensure that the mounting clearances around the drive housing follow the recommendations in the manual .

4. 0x2382 / 0x2383 (Inverter Output Current Overload - ixt)

This thermal trip is triggered if the output current exceeds the drive’s nominal rating for too long, heating the internal power modules .

  • Diagnostic: Check for a mechanical jam in the fan or conveyor system . Verify the motor’s nominal settings in the parameter configuration menu and ensure the motor is not overloaded .

5. 0x6280 (Incompatible Configuration)

This code appears if parameters are configured in an incompatible layout . For example, if you set the drive to "Flexible" control mode, you must ensure that either "Inverter Enable" or "Run/Stop" is assigned to a digital input .

  • Diagnostic: Re-verify that all interdependent control and run parameters are correctly mapped in Group 4 (I/O settings) .

Best Practices to Avoid VS10 Drive Trips

Implementing basic preventive practices helps ensure consistent operations and prevents premature component failure:

  • Utilize the Keyhole Mounting & Memory Module: The VS10 features a hot-pluggable HMI and a dedicated memory module for parameter backup . Saving your custom configuration onto the backup module ensures that if a drive ever needs to be replaced, you can copy the parameter set to the new unit immediately .
  • Verify Wiring Torques: Thermal cycling can loosen terminal screws on main input and motor output lines over time. Periodically check and retorque all power connections to prevent phase loss or high-resistance joints.

By understanding what the Emotron VS10 is communicating and following a proactive maintenance routine, you can ensure reliable operation and minimize process interruptions .

Comments