Schneider ATV212 Drive Fault Codes
Complete reference list of Schneider Altivar 212 (ATV212) fault codes. Learn to troubleshoot HVAC errors like OPF (Output Phase Loss), OHF, and Err5 (Comm Fault).
Schneider ATV212 Fault Codes Reference Table
Schneider ATV212 Fault Codes Reference Table
Schneider ATV212 Fault Codes Reference Table
Type a fault code or keyword to filter the list:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| CApF [Cavitation Error] |
Cause: Loss of speed due to overload or / and too much torque. Remedy:
|
| CFl2 [Download transfer fault] |
Cause: Invalid configuration. The configuration loaded in the drive via the bus or communication network is inconsistent. Transfer using PC soft has not been successful due to rating differences. Remedy:
|
| E-18 [VIA signal fault] |
Cause: The VIA analog signal is below the level set by parameter F633. Remedy:
|
| E-19 [CPU communications err.] |
Cause: Communication error between control CPUs. Remedy:
|
| E-20 [Excess torque boost flt] |
Cause: Torque boost parameter [Auto Torque Boost] (F402) is set too high. The motor impedance is too low. During deceleration when [Mot cont. mode sel.] = [Quadr. U/F] with specific stop/load/deceleration conditions. Remedy:
|
| E-21 [CPU error 2 fault] |
Cause: The control board CPU is inoperable. Remedy:
|
| E-38 [EEprom pwr incompat.] |
Cause: Eeprom power incompatible. Product hardware detected fault. Remedy:
|
| E-39 [InitPos Det] |
Cause: An Error is detected at the starting: The measured current at initial position detection is too small or large according to the inductance of motor or output phase loss. Remedy:
|
| EEP1 [EEPROM error 1 fault] |
Cause: A data writing error has occurred. Remedy:
|
| EEP2 [EEPROM error 2 fault] |
Cause: Power was removed from the drive during a parameter reset operation resulting in a data writing error. The measured current at initial position detection at the auto-tuning is too small or large. Remedy:
|
| EEP3 [EEPROM error 3 fault] |
Cause: A data reading error has occurred. Remedy:
|
| EF2 [Ground fault] |
Cause: Ground fault in motor or motor cables. Remedy:
|
| EPH0 [Output phase loss fault] |
Cause: Loss of one or more output phases. Remedy:
|
| EPH1 [Input phase loss fault] |
Cause: Loss of one input phase. Remedy:
|
| EPtF [Threshold Error] |
Cause: Condition for overheating reached, exceeded Threshold F353. Remedy:
|
| Err1 [Speed ref. error fault] |
Cause: Parameters F202, F203, F210, or F212 are set improperly. Remedy:
|
| Err2 [RAM fault] |
Cause: The control board RAM is inoperable. Remedy:
|
| Err3 [ROM fault] |
Cause: The control board ROM is inoperable. Remedy:
|
| Err4 [CPU fault 1] |
Cause: The control board CPU is inoperable. Remedy:
|
| Err5 [Com RJ45 fault] |
Cause: Serial communication error. Remedy:
|
| Err7 [Current sensor fault] |
Cause: A motor current sensor is inoperable. Remedy:
|
| Err8 [Network error fault] |
Cause: Network communication error. Remedy:
|
| Err9 [Remote keypad fault] |
Cause: Graphic display option cable disconnected. Remedy:
|
| Etn1 [Auto-tuning fault] |
Cause: Parameters F401 to F494 are incorrectly set. The motor is too large for the drive or cable gauge is too small. The motor is still rotating at the start of the auto-tune. The drive is not powering a 3-phase induction motor. Measured current at initial position detection is too small or large. Remedy:
|
| EtYP [Drive fault] |
Cause: The main control board is inoperable. Remedy:
|
| Fd1 [Closed damper 1 fault] |
Cause: Damper is locked in closed position. Remedy:
|
| Fd2 [Closed damper 2 fault] |
Cause: Damper blocked open or soldered. Remedy:
|
| nO20 [Total input power] |
Cause: The accumulated input power value is more than 999.999 kWh. Remedy:
|
| OC1 [Overcurrent acceleration] |
Cause: The acceleration time is too short. The setting of parameter [Mot cont. mode sel.] is incorrect. The drive is starting into a rotating load. The drive is powering a low impedance motor. Ground fault. Remedy:
|
| OC1P [SC or ground fault acc.] |
Cause: Short circuit or ground fault during acceleration. Remedy:
|
| OC2 [Overcurrent deceleration] |
Cause: The deceleration time is too short. Ground fault. Remedy:
|
| OC2P [SC or ground fault dec.] |
Cause: Short circuit or ground fault during deceleration. Remedy:
|
| OC3 [Overcurrent cont. speed] |
Cause: Abrupt fluctuations in load. Abnormal load condition. Remedy:
|
| OC3P [SC/ground flt cont. spd] |
Cause: Short circuit or ground fault during constant speed operation. The drive cooling fan is not working. Remedy:
|
| OCA [SC inverter at start] |
Cause: Ground fault. Remedy:
|
| OCL [SC mot. cable at start] |
Cause: Phase to phase output short circuit. The motor impedance is too low. Remedy:
|
| OH [Drive overtemperature] |
Cause: The drive cooling fan is not working. The ambient temperature is too high. An enclosure air vent is blocked. A heat source is too close to the drive. The drive heatsink temperature sensor is malfunctioning. Remedy:
|
| OH2 [PTC overheating] |
Cause: The external PTC embedded in the motor windings indicates a motor overtemperature condition. Remedy:
|
| OL1 [Drive overload] |
Cause: The acceleration time is too short. The DC injection current level is too high. The setting of parameter [Mot cont. mode sel.] is incorrect. The drive is starting into a rotating load. The load is too large. Remedy:
|
| OL2 [Motor overload] |
Cause: The setting of parameter [Mot cont. mode sel.] is incorrect. The motor is jammed. Low-speed operation is performed continuously. Excessive load is applied to the motor. Remedy:
|
| OP1 [Overvoltage acceleration] |
Cause: The input voltage is fluctuating abnormally. Power network is greater than 200 kVA. Power factor capacitor switching. SCR switching on power network. The drive is starting into a rotating load. Intermittent output phase fault. Remedy:
|
| OP2 [Overvolt. deceleration] |
Cause: The deceleration time is too short. Overhauling load. The input voltage is fluctuating abnormally. Power network is greater than 200 kVA. Power factor capacitor switching. The drive is starting into a rotating load. Remedy:
|
| OP3 [Overvoltage cont. speed] |
Cause:
Remedy:
|
| Ot [Overtorque] |
Cause:
Remedy:
|
| pSrF [Prst Spd Error] |
Cause:
Remedy:
|
| SOUt [PM motor step-out] (permanent magnet motor pulls out of synchronism) |
Cause:
Remedy:
|
| UC [Underload] |
Cause:
Remedy:
|
| UPI [Undervoltage] |
Cause:
Remedy:
|
| Atn1 [Auto tune] |
Cause:
Remedy:
|
| CLr [Reset active] |
Cause:
Remedy:
|
| db [DC braking] |
Cause:
Remedy:
|
| dbOn [dbOn] |
Cause:
Remedy:
|
| E-17 [HMI error] |
Cause:
Remedy:
|
| EI [Excess value] |
Cause:
Remedy:
|
| EOFF [Loc. Stop en.] |
Cause:
Remedy:
|
| Err1 [Speed ref alarm] |
Cause:
Remedy:
|
| h999 [Pin&1MWh] Integral input power |
Cause:
Remedy:
|
| H999 [Pout&1MWh] Integral output power |
Cause:
Remedy:
|
| HEAd / End [Head] / [End] |
Cause:
Remedy:
|
| HI / LO [High] / [Low] Parameter adjustment error |
Cause:
Remedy:
|
| InIt [Initialization] |
Cause:
Remedy:
|
| LStP [Low speed stop] Auto-stop |
Cause:
Remedy:
|
| NOFF [Line undervolt flt] |
Cause:
Remedy:
|
| OFF [Drive stop] |
Cause:
Remedy:
|
| nSt [Lock State] |
Cause:
Remedy:
|
| rtrY [Auto reset] |
Cause:
Remedy:
|
| StOp [Stop supply] Momentary power loss slowdown stop |
Cause:
Remedy:
|
| C [Current alarm] |
Cause:
Remedy:
|
| P [DC bus alarm] |
Cause:
Remedy:
|
| L [Motor overload al] |
Cause:
Remedy:
|
| H [Drv overheat alrm] |
Cause:
Remedy:
|
Troubleshooting ATV212: HVAC Specifics
The ATV212 interface relies on a 4-digit 7-segment LED display. Troubleshooting often requires distinguishing between motor faults and external control issues.
- OPF (Output Phase Loss): This is the most common fault in HVAC. It typically occurs when a maintenance technician opens the Local Disconnect Switch at the motor while the drive is still running. The drive senses the open circuit and trips to protect itself.
- Communication Errors (Err5/Err8): Since ATV212s are usually connected to a BMS (Building Management System), these codes indicate a loss of data traffic. Check your RS485 wiring, termination resistors, and baud rate settings in the COM menu.
- Fault History (F8-00): You can access the last 4 faults via the parameter list.
- F800: Most recent fault.
- F801: 2nd most recent fault.
- F802: 3rd most recent fault.
Frequently Asked Questions (FAQ)
Q: What causes “OPF” (Output Phase Loss)?
A:
1. Disconnect Switch: Someone turned off the isolator switch near the motor while the VFD was running.
2. Broken Belt: If
the motor is running with no load (belt snapped), the current drops so
low the drive thinks the motor is disconnected (if “Output Phase Loss”
sensitivity is set high).
3. Loose Wire: Check the T1/T2/T3 terminals.
Q: How do I reset the ATV212?
A:
1. Power Cycle: Turn off main power, wait for the screen to go black, turn on.
2. Stop/Reset: Press the red STOP/RESET button (if enabled in parameters).
3. Logic Input: Trigger the input assigned to “Fault Reset” (RES).
Q: The drive shows “OFF” and won’t start. Is it broken?
A: No. OFF indicates a “Hard Stop” condition.
This happens if the Safety Input (P24 to VIA jumper) is removed, or if a specific Logic Input assigned to “External Fault” is active. Check your safety interlocks and freeze-stats.