Schneider ATV310 Drive Fault Codes
Complete reference list of Schneider Altivar Easy 310 (ATV310) fault codes. Learn to interpret F-codes like F010 (Overcurrent), F025 (Overvoltage), and F019.
Schneider ATV310 Fault Codes Reference Table
Schneider ATV310 Fault Codes Reference Table
Schneider ATV310 Fault Codes Reference Table
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| ---- Problem with application firmware |
Cause: Invalid application firmware update using the Multi-Loader tool.
Remedy:
|
| F001 Precharge |
Cause: Charging relay control fault or charging resistor damaged.
Remedy:
|
| F002 Unknown drive rating |
Cause: Power card and stored card versions different.
Remedy:
|
| F003 Unknown or incompatible power board |
Cause: The power card is incompatible with the control card.
Remedy:
|
| F004 Internal serial link fault |
Cause: Communication interruption between the internal cards.
Remedy:
|
| F005 Invalid industrialization zone |
Cause: Internal data inconsistent.
Remedy:
|
| F006 Current measurement circuit |
Cause: Current measurement is not correct due to hardware circuit fault.
Remedy:
|
| F007 Internal thermal sensor detected fault |
Cause:
Remedy:
|
| F008 Internal CPU |
Cause: Internal microprocessor fault.
Remedy:
|
| F010 Overcurrent |
Cause:
Remedy:
|
| F018 Motor short-circuit |
Cause:
Remedy:
|
| F019 Ground short-circuit |
Cause:
Remedy:
|
| F020 IGBT short circuit |
Cause: Internal power component short circuit detected at power on.
Remedy:
|
| F025 Overspeed |
Cause:
Remedy:
|
| F028 Autotuning fault |
Cause:
Remedy:
|
| F036 Angle setting fault |
Cause: This occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high.
Remedy:
|
| F009 Overbraking |
Cause: Sudden braking or load inertia too high.
Remedy:
|
| F011 Drive overheat |
Cause: Drive temperature too high.
Remedy:
|
| F012 Process overload fault |
Cause: Process overload.
Remedy:
|
| F013 Motor overload |
Cause: Triggered by excessive motor current.
Remedy:
|
| F014 1 Output phase loss |
Cause: Loss of one phase on drive output.
Remedy:
|
| F015 3 Output phases loss |
Cause:
Remedy:
|
| F016 Main overvoltage |
Cause:
Remedy:
|
| F017 Input phase loss |
Cause:
Remedy:
|
| F021 Load short circuit |
Cause:
Remedy:
|
| F022 Modbus interruption |
Cause: Interrupted communication on the Modbus network.
Remedy:
|
| F024 HMI communication |
Cause: Communication interruption with the external display terminal.
Remedy:
|
| F026 PI feedback fault |
Cause: PID feedback below lower limit.
Remedy:
|
| F027 IGBT overheat |
Cause:
Remedy:
|
| F029 Process underload fault |
Cause:
Remedy:
|
| F033 AI1 current loss |
Cause:
Remedy:
|
| F030 Undervoltage |
Cause:
Remedy:
|
| F031 Incorrect configuration |
Cause:
Remedy:
|
| F032 Invalid configuration |
Cause:
Remedy:
|
| F034 Download invalid configuration |
Cause: When save parameter setting or restore to factory setting, the drive detects invalid configuration.
Remedy:
|
|
InIt:
Auto-initialization on start |
Cause:
Remedy: |
|
COM.E (Flashing)
Communication error |
Cause:
Remedy: |
|
A-17 (Flashing)
Key alarm |
Cause:
Remedy: |
|
cLr (Flashing)
Confirm fault reset |
Cause:
This message appears if the STOP key is pressed while the display terminal is displaying a fault. Remedy: |
|
dEU.E (Flashing)
Drive mismatch |
Cause:
Drive type (brand) does not match display terminal type (brand). Remedy: |
|
rOM.E (Flashing)
ROM abnormality |
Cause:
ROM abnormality detected by checksum calculation. Remedy: |
|
rAM.E (Flashing)
RAM abnormality |
Cause:
Display terminal RAM abnormality detected. Remedy: |
|
CPU.E (Flashing)
Other fault |
Cause:
The other detected fault. Remedy: |
How to Read ATV310 Faults & History
Navigating the ATV310 is done via the jog dial. Because the codes are numeric, it is essential to check the “Maintenance” menu for details.
- Active Faults (Fxxx): When the drive trips, the display flashes an F followed by three digits.
- F010 – F018: Typically relate to Current and Motor issues.
- F025 – F030: Typically relate to Mains Voltage issues.
- Fault History (Menu 8.1): To diagnose past issues, go to Menu 800 (Maintenance) → Menu 801 (Fault History).
The drive stores the last few faults, allowing you to see if a specific error (like Overvoltage) is recurring. - Status Codes: If the drive is not faulted, it shows status:
- rdy: Ready (Power on, no run command).
- run: Running (Outputting frequency).
Frequently Asked Questions (FAQ)
Q: What does “F010” (Overcurrent) mean?
A: F010 is the equivalent of the old “OCF” fault. It means the motor is drawing more current than the drive can handle.
Causes:
1. Acceleration ramp (Menu 501.1) is too short.
2. Mechanical blockage at the machine.
3. Wrong motor parameters (Check Menu 300).
Q: How do I fix “F025” (Mains Overvoltage)?
A: This occurs when the DC bus voltage is too high.
Scenario A (While Stopped): The incoming mains voltage is too high (Check grid voltage).
Scenario B (While Decelerating): The
motor is regenerating energy back to the drive. You need to increase
the Deceleration Time (Menu 501.2) or add a braking resistor.
Q: How do I reset the ATV310?
A:
1. Power Cycle: Turn off the drive, wait for the display to turn off completely, then power on.
2. Long Press: In some configurations, holding the STOP/RESET button for 3 seconds clears the fault.
3. Remote Reset: Trigger the Logic Input assigned to “Fault Reset” (Menu 600).