Schneider ATV320 Drive Fault Codes

Complete reference list of Schneider Altivar Machine 320 (ATV320) fault codes. Learn to interpret LED errors like CFF, STO/PRA, and OCF on Compact and Book drives.

This guide provides the most updated reference data for 2026 to help you navigate the specific “Machine” faults and safety interlocks of the ATV320 series.

Schneider ATV320 Fault Codes Reference Table

  Schneider ATV320 Fault Codes Reference Table

Schneider ATV320 Fault Codes Reference Table

Fault Code and Meaning Cause and Remedy
AnF
[Load slipping]
Cause: The difference between the output frequency and the speed feedback is not correct.

Remedy:
  • Check the motor, gain and stability parameters.
  • Add a braking resistor.
  • Check the size of the motor/drive/load.
  • Check the encoder's mechanical coupling and its wiring.
  • Check the setting of parameters.
ASF
[Angle Error]
Cause: This occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high.

Remedy:
  • Check the motor phases and the maximum current allowed by the drive.
bLF
[Brake control]
Cause: Brake release current not reached. Brake engage frequency threshold [Brake engage freq] (bEn) only regulated when brake logic control is assigned.

Remedy:
  • Check the drive/motor connection.
  • Check the motor windings.
  • Check the [Brake release I FW] (Ibr) and [Brake release I Rev] (Ird) settings.
  • Apply the recommended settings for [Brake engage freq] (bEn).
brF
[Brake feedback]
Cause: The brake feedback contact does not match the brake logic control. The brake does not stop the motor quickly enough.

Remedy:
  • Check the feedback circuit and the brake logic control circuit.
  • Check the mechanical state of the brake.
  • Check the brake linings.
CrF1
[Precharge]
Cause: Charging relay control detected fault or charging resistor damaged.

Remedy:
  • Turn the drive off and then turn on again.
  • Check the internal connections.
  • Contact Schneider Electric Product Support.
EEF1
[Control Eeprom]
Cause: Internal memory detected fault, control block.

Remedy:
  • Check the environment (electromagnetic compatibility).
  • Turn off, reset, return to factory settings.
  • Contact Schneider Electric Product Support.
EEF2
[Power Eeprom]
Cause: Internal memory detected fault, power card.

Remedy:
  • Contact Schneider Electric Product Support.
FCF1
[Out. contact. stuck]
Cause: The output contactor remains closed although the opening conditions have been met.

Remedy:
  • Check the contactor and its wiring.
  • Check the feedback circuit.
HdF
[IGBT desaturation]
Cause: Short-circuit or grounding at the drive output.

Remedy:
  • Check the cables connecting the drive to the motor, and the motor insulation.
ILF
[internal com. link]
Cause: Communication interruption between option card and drive.

Remedy:
  • Check the environment (electromagnetic compatibility).
  • Check the connections.
  • Replace the option card.
  • Contact Schneider Electric Product Support.
InF1
[Rating error]
Cause: The power card is different from the card stored.

Remedy:
  • Check the reference of the power card.
InF2
[Incompatible PB]
Cause: The power card is incompatible with the control block.

Remedy:
  • Check the reference of the power card and its compatibility.
InF3
[Internal serial link]
Cause: Communication interruption between the internal cards.

Remedy:
  • Check the internal connections.
  • Contact Schneider Electric Product Support.
InF4
[Internal-mftg zone]
Cause: Internal data inconsistent.

Remedy:
  • Recalibrate the drive (performed by Schneider Electric Product Support).
InF6
[Internal - fault option]
Cause: The option installed in the drive is not recognized.

Remedy:
  • Check the reference and compatibility of the option.
  • Check that the option is well inserted into the ATV320.
InF9
[Internal- I measure]
Cause: The current measurements are incorrect.

Remedy:
  • Replace the current sensors or the power card.
  • Contact Schneider Electric Product Support.
InFA
[Internal-mains circuit]
Cause: The input stage is not operating correctly.

Remedy:
  • Contact Schneider Electric Product Support.
InFb
[Internal- th. sensor]
Cause: The drive temperature sensor is not operating correctly.

Remedy:
  • Replace the drive temperature sensor.
  • Contact Schneider Electric Product Support.
InFE
[internal- CPU]
Cause: Internal microprocessor detected fault.

Remedy:
  • Turn off and reset.
  • Contact Schneider Electric Product Support.
SAFF
[Safety fault]
Cause:
  • Debounce time exceeded.
  • SS1 threshold exceeded.
  • Wrong configuration.
  • SLS type overspeed detected.

Remedy:
  • Check the safety functions configuration.
  • Check the ATV320 Integrated safety Functions manual.
  • Contact Schneider Electric Product Support.
SOF
[Overspeed]
Cause: Instability or driving load too high. Overspeed threshold has been reached.

Remedy:
  • Check the motor, gain and stability parameters.
  • Add a braking resistor.
  • Check the size of the motor/drive/load.
  • Check the parameters settings for the [FREQUENCY METER] (FqF-) function.
  • Verify and close the contacts between the motor and the drive before applying a Run command.
  • Verify the consistency between [Max frequency] (tFr) and [High Speed] (HSP).
SPF
[Speed fdback loss]
Cause: Signal on "Pulse input" missing, or Encoder feedback signal missing.

Remedy:
  • Check the wiring of the input cable and the detector used.
  • Check the configuration parameters of the encoder.
  • Check the wiring between the encoder and the drive.
  • Check the encoder.
CnF
[Com. network]
Cause: Communication interruption on communication card.

Remedy:
  • Check the environment (electromagnetic compatibility).
  • Check the wiring.
  • Check the time-out.
  • Replace the option card.
  • Contact Schneider Electric Product Support.
CoF
[CANopen com.]
Cause: Communication interruption on the CANopen® bus.

Remedy:
  • Check the communication bus.
  • Check the time-out.
  • Refer to the CANopen® User's manual.
EPF1
[External flt-LI/Bit]
Cause: Event triggered by an external device, depending on user.

Remedy:
  • Check the device which caused the triggering and reset.
EPF2
[External fault com.]
Cause: Event triggered by a communication network.

Remedy:
  • Check for the cause of the triggering and reset.
FbES
[FB stop flt.]
Cause: Function blocks have been stopped while motor was running.

Remedy:
  • Check [Stop FB Stop motor] (FbSM) configuration.
FCF2
[Out. contact. open.]
Cause: The output contactor remains open although the closing conditions have been met.

Remedy:
  • Check the contactor and its wiring.
  • Check the feedback circuit.
LCF
[input contactor]
Cause: The drive is not turned on even though [Mains V. time out] (LCt) has elapsed.

Remedy:
  • Check the contactor and its wiring.
  • Check the time-out.
  • Check the supply mains/contactor/drive connection.
LFF3
[AI3 4-20mA loss]
Cause: Loss of the 4-20 mA reference on analog input AI3.

Remedy:
  • Check the connection on the analog inputs.
ObF
[Overbraking]
Cause: Braking too sudden or driving load too high. Supply voltage too high.

Remedy:
  • Increase the deceleration time.
  • Install a braking resistor if necessary.
  • Activate the [Dec ramp adapt.] (brA) function if compatible.
  • Check the supply voltage.
OCF
[Overcurrent]
Cause:
  • Parameters in [SETTINGS] and [MOTOR CONTROL] menus are not correct.
  • Inertia or load too high.
  • Mechanical locking.

Remedy:
  • Check the parameters.
  • Check the size of the motor/drive/load.
  • Check the state of the mechanism.
  • Decrease [Current limitation] (CLI).
  • Increase the switching frequency.
OHF
[Drive overheat]
Cause: Drive temperature too high.

Remedy:
  • Check the motor load, the drive ventilation and the ambient temperature.
  • Wait for the drive to cool down before restarting.
OLC
[Proc. overload flt]
Cause: Process overload.

Remedy:
  • Check and remove the cause of the overload.
  • Check the parameters of the [PROCESS OVERLOAD] (oLd-) function.
OLF
[Motor overload]
Cause: Triggered by excessive motor current.

Remedy:
  • Check the setting of the motor thermal protection, check the motor load.
  • Wait for the motor to cool down before restarting.
OPF1
[1 output phase loss]
Cause: Loss of one phase at drive output.

Remedy:
  • Check the connections from the drive to the motor.
OPF2
[3 motor phase loss]
Cause:
  • Motor not connected or motor power too low.
  • Output contactor open.
  • Instantaneous instability in the motor current.

Remedy:
  • Check the connections from the drive to the motor.
  • If an output contactor is being used, set [Output Phase Loss] (OPL) to [Output cut] (OAC).
  • Test on a low power motor or without a motor (configure OPL).
  • Check and optimize parameters: [IR compensation] (UFr), [Rated motor volt.] (UnS), [Rated mot. current] (nCr), and perform [Auto tuning] (tUn).
OSF
[Mains overvoltage]
Cause: Supply voltage too high. Disturbed mains supply.

Remedy:
  • Check the supply voltage.
OtFL
[LI6=PTC overheat]
Cause: Overheating of PTC probes detected on input LI6.

Remedy:
  • Check the motor load and motor size.
  • Check the motor ventilation.
  • Wait for the motor to cool before restarting.
  • Check the type and state of the PTC probes.
PtFL
[LI6=PTC probe]
Cause: PTC probe on input LI6 open or short-circuited.

Remedy:
  • Check the PTC probe and the wiring between it and the motor/drive.
SCF1
[Motor short circuit]
Cause: Short-circuit or grounding at the drive output.

Remedy:
  • Check the cables connecting the drive to the motor, and the motor insulation.
  • Reduce the switching frequency.
  • Connect chokes in series with the motor.
  • Check the adjustment of speed loop and brake.
  • Increase the [Time to restart] (ttr).
SCF3
[Ground short circuit]
Cause: Significant earth leakage current at the drive output if several motors are connected in parallel.

Remedy:
  • Check the cables connecting the drive to the motor, and the motor insulation.
  • Reduce the switching frequency.
  • Connect chokes in series with the motor.
  • Check the adjustment of speed loop and brake.
  • Increase the [Time to restart] (ttr).
SCF4
[IGBT short circuit]
Cause: Power component detected fault.

Remedy:
  • Contact Schneider Electric Product Support.
SCF5
[Motor short circuit]
Cause: Short-circuit at drive output.

Remedy:
  • Check the cables connecting the drive to the motor, and the motor's insulation.
  • Contact Schneider Electric Product Support.
SLF1
[Modbus com.]
Cause: Communication interruption on the Modbus bus.

Remedy:
  • Check the communication bus.
  • Check the time-out.
  • Refer to the Modbus User's manual.
SLF2
[PC com.]
Cause: Communication interruption with PC Software.

Remedy:
  • Check the PC Software connecting cable.
  • Check the time-out.
SLF3
[HMI com.]
Cause: Communication interruption with the graphic display terminal or remote display terminal.

Remedy:
  • Check the terminal connection.
  • Check the time-out.
SSF
[Torque/current lim]
Cause: Switch to torque or current limitation.

Remedy:
  • Check if there are any mechanical problems.
  • Check the parameters of [TORQUE LIMITATION] (tOL-) and [TORQUE OR I LIM. DETECT.] (tId-).
tJF
[IGBT overheat]
Cause: Drive overheated.

Remedy:
  • Check the size of the load/motor/drive.
  • Reduce the switching frequency.
  • Wait for the motor to cool before restarting.
tnF
[Auto-tuning]
Cause: Special motor, motor power unsuitable, not connected, or not stopped.

Remedy:
  • Check that the motor/drive are compatible.
  • Check that the motor is present during auto-tuning.
  • If an output contactor is being used, close it during auto-tuning.
  • Check that the motor is stopped during tune operation.
ULF
[Proc. underload Flt]
Cause: Process underload.

Remedy:
  • Check and remove the cause of the underload.
  • Check the parameters of the [PROCESS UNDERLOAD] (Uld-) function.
CFF
[Incorrect config.]
Cause: Option card changed or removed. Control block replaced by a control block configured on a drive with a different rating.

Remedy:
  • Check that there are no card errors.
  • Return to factory settings or retrieve the backup configuration, if it is valid.
CFI
[Invalid config.]
Cause: Invalid configuration. The configuration loaded is inconsistent.

Remedy:
  • Check the configuration loaded previously.
  • Load a compatible configuration.
CFI2
[Download invalid]
Cause: Interruption of download operation.

Remedy:
  • Check connection.
  • Restart download or restore factory setting.
CSF
[Ch. Sw. fault]
Cause: Switch to not valid channels.

Remedy:
  • Check the function parameters.
dLF
[Dynamic load fault]
Cause: Abnormal load variation.

Remedy:
  • Check that the load is not blocked by an obstacle.
  • Removal of a run command causes a reset.
FbE
[FB fault]
Cause: Function blocks error.

Remedy:
  • See [FB Fault] (FbFt) for more details.
HCF
[Cards pairing]
Cause: The [CARDS PAIRING] (PPI-) function has been configured and a drive card has been changed.

Remedy:
  • In the event of a card error, reinsert the original card.
  • Confirm the configuration by entering the [Pairing password] (PPI) if the card was changed deliberately.
PHF
[Input phase loss]
Cause: Drive incorrectly supplied, fuse blown, phase missing, or unbalanced load.

Remedy:
  • Check the power connection and the fuses.
  • Use a 3-phase supply mains.
  • Disable the detected fault by [Input phase loss] (IPL).
USF
[Undervoltage]
Cause: Supply mains too low. Transient voltage dip.

Remedy:
  • Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-).
InIt
[Initialization in progress]
Description: The microcontroller is initializing. Search underway for communication configuration.
Com.E (Flashing)
[Communication error]
Description: Time out detected fault (50 ms). This message is displayed after 20 attempts at communication.
A-17 (Flashing)
[Alarm button]
Description: A key has been held down for more than 10 seconds. The keypad is disconnected or woke up while a key is pressed.
cLr (Flashing)
[Confirmation of detected fault reset]
Description: This is displayed when the STOP key is pressed once if the active command channel is the remote display terminal.
dEU.E (Flashing)
[Drive disparity]
Description: The drive brand does not match that of the remote display terminal.
rOM.E (Flashing)
[ROM anomaly]
Description: The remote display terminal detects a ROM anomaly on the basis of checksum calculation.
rAM.E (Flashing)
[RAM anomaly]
Description: The remote display terminal detects a RAM anomaly.
CPU.E (Flashing)
[Other detected faults]
Description: Other detected faults.

How to Read ATV320 Faults & History

Navigating the ATV320 with the integrated “Jog Dial” can be tricky. Here is how to find critical diagnostics:

  • Safety Status (STO / PRA): The most common “issue” calls are actually safety statuses.
    • STO: Safe Torque Off. The drive is healthy but the safety circuit is open.
    • PRA: Power Removal Active. This is the legacy code for STO found on older firmware versions.
  • Fault History: Unlike older drives, the integrated LED display does not show a full fault history list by default.
    Best Practice for 2026: Use the Schneider SoMove software (via USB-C or Modbus) or plug in a remote Graphic Display Terminal (VW3A1111) to view the “Error History” log with timestamps.
  • Active Faults: Active faults flash on the screen. Press the ENT (Jog Dial) to view the “Error Code” (e.g., OCF) and press it again to potentially see the “Sub-code” if applicable.

Frequently Asked Questions (FAQ)

Q: What is “CFF” (Incorrect Configuration)?

A: This typically appears when a drive is replaced or an option module is removed.
Cause: The configuration saved in the drive’s memory does not match the connected hardware (Power board or Option Card).
Fix:
1. Go to CONF → FCS- (Factory Settings).
2. Select FrY- (Parameter Group List) and set to ALL.
3. Select GFS (General Factory Settings) and set to YES (Hold for 2 seconds).
Warning: This wipes all programming.

Q: The drive flashes “SS1” or “SLS”. What does this mean?

A: These are Safety Functions.
SS1: Safe Stop 1 (Monitored Deceleration).
SLS: Safely Limited Speed.
The drive is not faulted, but it is restricting operation because a safety condition has been triggered. Check your safety PLC or safety inputs (logic settings in the Sjt menu).

Q: How do I fix “OCF” (Overcurrent) on an ATV320?

A:
1. Motor Data: Ensure the nPr (Rated Power) and nCr (Rated Current) in the drC- menu match the motor nameplate exactly.
2. Control Law: If using “Ctt = Std” (Standard V/f), try switching to “Perf” (Vector Control) and performing an Autotune (tUn).
3. Mechanical: Check for a jammed load or a brake that hasn’t released.

 

 

Comments

Popular posts from this blog

Allen Bradley Kinetix 5500 Drive Fault Codes List

Danfoss VACON 100 FLOW Drive Fault Codes List

ABB ACH580 Drive Fault Codes List