Yaskawa iQPump1000 Drive Fault Codes
Complete guide to Yaskawa iQPump1000 drive fault codes. Learn to troubleshoot Loss of Prime, Low Water alarms, Transducer errors, and access real-time fault logs.
iQPump1000 Fault Codes Reference Table
Below is the complete reference list of faults and alarms. The iQPump1000 display shows the code (e.g., LPo) and a scrolling text description (e.g., “Loss of Prime”), reducing the need to memorize abbreviations.
iQPump1000 Fault Codes Reference Table
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| ACCUM Accumulated Level Fault |
Cause: The accumulated level has exceeded the values set in P6-11 to P6-14. This is only effective when P6-15 (Accumulated Behavior) is set to 2 or 3.
Remedy:
|
| AJF Anti-Jam Fault |
Cause: The drive was not able to clear debris from the impeller in fewer than the number of attempts set in P7-02.
Remedy:
|
| AUXFB PI Aux Lvl Loss (Wire-break detection) |
Cause: The analog input programmed for "PI Aux FB Level" (H3-xx = 27) has dropped below 3 mA or risen above 21 mA for longer than 1 second.
Remedy:
|
| bAT Digital Operator Battery Voltage Low |
Cause: The digital operator battery is low.
Remedy:
|
| boL Braking Transistor Overload Fault |
Cause: The wrong braking resistor is installed.
Remedy:
|
| bUS Option Communication Error |
Cause: No signal was received from the PLC, faulty communications wiring, or communication data error due to noise.
Remedy:
|
| CE MEMOBUS/Modbus Communication Error |
Cause: Control data was not received for the CE detection time set to H5-09. Faulty wiring or noise interference.
Remedy:
|
| CPF11 to CPF14 CPF16 to CPF19 Control Circuit Error |
Cause: There is a self-diagnostic error in the control circuit.
Remedy:
|
| CPF02 A/D Conversion Error |
Cause: Control circuit is damaged (A/D conversion error or control circuit error).
Remedy:
|
| CPF03 Control Board Connection Error |
Cause: Connection error between the control board and the drive.
Remedy:
|
| CPF06 EEPROM Memory Data Error |
Cause: Error in EEPROM control circuit, or power supply was switched off while parameters were being saved.
Remedy:
|
| CPF07 or CPF08 Terminal Board Connection Error |
Cause: Faulty connection between terminal board and control board.
Remedy:
|
| CPF20 or CPF21 Control Circuit Error |
Cause: Hardware is damaged.
Remedy:
|
| CPF22 Hybrid IC Failure |
Cause: Hybrid IC failure on the power board.
Remedy:
|
| CPF23 Control Board Connection Error |
Cause: Hardware is damaged (connection error between control board and drive).
Remedy:
|
| CPF24 Drive Unit Signal Fault |
Cause: Hardware is damaged (drive capacity cannot be detected).
Remedy:
|
| CPF25 Terminal Board Not Connected |
Cause: Terminal board is not connected correctly.
Remedy:
|
| CPF26 to CPF35 CPF40 to CPF43 Control Circuit/CPU Error |
Cause: Hardware is damaged.
Remedy:
|
| DIFF Differential Feedback Detected |
Cause: The difference between PID Feedback and Differential Feedback (H3-xx = 28) exceeded P4-18 level for time set in P4-19.
Remedy:
|
| E5 SI-T3 Watchdog Timer Error |
Cause: The watchdog timed out. Data has not been received from the PLC.
Remedy:
|
| EF0 Option Card External Fault |
Cause: External fault received from PLC (F6-03 not equal to 3), or problem with PLC program.
Remedy:
|
| EF1 to EF8 Pump Fault (Input Terminals S1-S8) |
Cause: An external device tripped an alarm function (Wiring incorrect, Multi-function contact input setting incorrect).
Remedy:
|
| Err EEPROM Write Error |
Cause: Noise corrupted data while writing to EEPROM, or hardware problem.
Remedy:
|
| FAn Internal Fan Fault |
Cause: Internal cooling fan malfunctioned, or fault detected in fan/magnetic contactor to power supply.
Remedy:
|
| FDBKL PID Feedback Loss (Wire Break) |
Cause: The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA.
Remedy:
|
| Flow Rate Limit Drive output speed limited |
Cause: Excessive or insufficient Flow. Drive output speed is being limited due to Flow Rate (U1-83).
Remedy:
|
| GF Ground Fault |
Cause: Motor insulation damaged, damaged motor cable creating short circuit, excessive leakage current, or hardware problem.
Remedy:
|
| HFB High Feedback |
Cause: The feedback signal has risen above the level set in P1-11 for the time set in P1-12.
Remedy:
|
| HIAUX High PI Auxiliary Feedback Level |
Cause: PI Aux Feedback has risen above Q6-12 level for longer than time set in Q6-13.
Remedy:
|
| HIFLO High Flow |
Cause: The flow is too high. Measured water flow risen above P6-17 level for time set in P6-18.
Remedy:
|
| HISUC High Section Pressure |
Cause: Suction pressure has risen above Q5-12 level for longer than time set in Q5-13.
Remedy:
|
| HWL High Water Level |
Cause: Low Water Level switch activated or P1-31 (High Water Digital Input) programmed incorrectly.
Remedy:
|
| LF Output Phase Loss |
Cause: The output cable is disconnected. Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
|
| LF3 Power Unit Output Phase Loss 3 |
Cause: The gate drive board in the power unit is damaged. Remedy:
Remedy:
Remedy:
|
| LFB Low Feedback |
Cause: The feedback signal has dropped below the level set in P1-08 for the time set in P1-09. Remedy:
|
| LOAUX Low PI Auxiliary Feedback Level |
Cause: PI Aux Feedback has fallen below the Q6-09 level for longer than the time set in Q6-10. Remedy:
|
| LOP Loss of Prime |
Cause: The pump load (output current, kilowatts, or power) has dropped below the level set in P1-19 for the time set in P1-20. Remedy:
|
| LOSUC Low Suction Pressure |
Cause: The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10. Remedy:
|
| LOWFL Low Flow |
Cause: Insufficient flow. Measured water flow has fallen below P6-06 level for time set in P6-07. Remedy:
|
| LOWWL Low Water Level |
Cause: The water level has fallen below the level set in Q4-09 for the longer than the time set in Q4-10. Remedy:
|
| LWL Low Water Level (Digital Input) |
Cause: The Low Water Level switch is activated, defective, or P1-30 is programmed incorrectly. Remedy:
|
| MSL Net Master Lost |
Cause: The MEMOBUS master has been lost. Network Recovery is set to Fault MSL and no message received within time P9-26. Remedy:
|
| NMS Not Maintaining Setpoint |
Cause: When the feedback deviates from the setpoint at a level greater than P1-15, for a time set in P1-16. Remedy:
|
| nSE Node Setup Error |
Cause: A terminal assigned to the node setup function closed during run, or Run command issued while setup active. Remedy:
|
| oC Overcurrent |
Cause: The motor has been damaged due to overheating or the motor insulation is damaged. Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
Remedy:
|
| oFA00 Option Card Connection Error at Option Port CN5-A Option compatibility error |
Cause: The option card installed into port CN5-A is incompatible with the drive.
Remedy:
|
| oFA01 Option Card Fault at Option Port CN5-A Option not properly connected |
Cause: The option card connection to port CN5-A is faulty.
Remedy:
|
| oFA03 to oFA06 oFA10, oFA11 oFA12 to oFA17 oFA30 to oFA43 Option Card Error Occurred at Option Port CN5-A |
Cause: Option card or hardware is damaged.
Remedy:
|
| oFb00 Option Card Fault at Option Port CN5-B Option compatibility error |
Cause: The option card installed into port CN5-B is incompatible, or a communication option card has been installed in port CN5-B.
Remedy:
|
| oFb01 Option Card Fault at Option Port CN5-B Option not properly connected |
Cause: The option card connection to port CN5-B is faulty.
Remedy:
|
| oFb02 Option Card Fault at Option Port CN5-B Same type of option card is currently connected |
Cause: An option card of the same type is already installed in option port CN5-A.
Remedy:
|
| oFb03 to oFb11 oFb12 to oFb17 Option Card error occurred at Option Port CN5-B |
Cause: Option card or hardware is damaged.
Remedy:
|
| oFC00 Option Card Connection Error at Option Port CN5-C Option compatibility error |
Cause: The option card installed into port CN5-C is incompatible, or a communication card is installed in CN5-C.
Remedy:
|
| oFC01 Option Card Fault at Option Port CN5-C Option not properly connected |
Cause: The option card connection to port CN5-C is faulty.
Remedy:
|
| oFC02 Option Card Fault at Option Port CN5-C Same type of option card is currently connected |
Cause: An option card of the same type is already installed in option port CN5-A or CN5-B.
Remedy:
|
| oFC03 to oFC11 oFC12 to oFC17 Option Card Error Occurred at Option Port CN5-C |
Cause: Option card or hardware is damaged.
Remedy:
|
| oFC50 to oFC55 Option Card Error Occurred at Option Port CN5-C |
Cause: Option card or hardware is damaged.
Remedy:
|
| oH Heatsink Overheat Temperature exceeded pre-alarm level (L8-02) |
Cause: Surrounding temperature is too high or Load is too heavy.
Remedy:
|
| Internal Fan Fault Internal cooling fan is stopped |
Cause: Fan failure or obstruction.
Remedy:
|
| oH1 Overheat 1 (Heatsink Overheat) Temperature exceeded drive overheat level |
Cause: Surrounding temperature is too high or Load is too heavy.
Remedy:
|
| oH4 Motor Overheat Fault (PTC Input) |
Cause: Motor has overheated.
Remedy:
|
| oH5 Motor Overheat (NTC Input) |
Cause: Motor has overheated.
Remedy:
|
| oL1 Motor Overload Electronic motor overload protection tripped |
Cause: Load is too heavy; Cycle times too short; Low speed operation with high load; Output voltage too high; Wrong motor rated current set; Base frequency incorrect.
Remedy:
|
| oL1 (cont) Motor Overload (Additional Causes) |
Cause: Electrical thermal protection mismatch; Relay operating at wrong level; Overexcitation; Speed Search parameters; Power supply loss.
Remedy:
|
| oL2 Drive Overload Thermal sensor triggered overload protection |
Cause: Load too heavy; Accel/decel too short; Output voltage too high; Drive capacity too small; Low speed overload; Excessive torque compensation; Speed search errors; Phase loss.
Remedy:
|
| oL3 Overtorque Detection 1 |
Cause: Parameter settings not appropriate for load; Fault on machine side (locked up).
Remedy:
|
| oL4 Overtorque Detection 2 |
Cause: Parameter settings are not appropriate for the load.
Remedy:
|
| oL7 High Slip Braking oL |
Cause: Output frequency stayed constant longer than time set in n3-04; Excessive load inertia; Motor driven by load; Braking restriction.
Remedy:
|
| oPr External HOA Keypad Connection Fault |
Cause: HOA keypad is not properly connected to the drive.
Remedy:
|
| ov Overvoltage DC bus voltage exceeded level |
Cause: Decel time too short; Fast accel causing overshoot; Excessive braking load; Surge voltage; Ground fault; Speed Search parameters; Input voltage too high; Wiring errors; Noise interference.
Remedy:
|
| PF Input Phase Loss |
Cause: Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 is set 1 (enabled). Remedy:
|
| PoC Pump Over Cycle |
Cause: The pump has exceeded the number of cycles set in P2-10 in the time set in P2-11 and P2-12 is set to 2 (fault). Remedy:
|
| rF Braking Resistor Fault |
Cause: The resistance of the braking resistor is too low. Remedy:
|
| rH Braking Resistor Overheat |
Cause: Braking resistor protection was triggered. Fault detection enabled when L8-01 = 1. Remedy:
|
| rr Dynamic Braking Transistor |
Cause: The built-in dynamic braking transistor failed. Remedy:
|
| SC IGBT Short Circuit or Ground Fault |
Cause: IGBT fault or short circuit detection circuit fault. Remedy:
|
| SEr Too Many Speed Search Restarts |
Cause: The number of Speed Search restarts exceeded the value set to b3-19. Remedy:
|
| SPL Suction Pressure Loss |
Cause: Wire-break detection for suction pressure. Analog input dropped below 3 mA or rose above 21 mA for longer than 1 second. Remedy:
|
| TdE Time Data Error |
Cause: An error has occurred in the Real-Clock Time function of the HOA keypad. Remedy:
|
| THo Thermistor Disconnect |
Cause: The thermistor that detects motor temperature has become disconnected. Remedy:
|
| TIE Time Interval Error |
Cause: An error has occurred in the Real-Clock Time function of the HOA keypad. Remedy:
|
| TIM Time Not Set |
Cause: The Real-Time Clock is not set in parameter o4-17 (first power up or battery low). Remedy:
|
| TLGI Geothermal Input |
Cause: Temperature Lost Geothermal Input. Input signal level dropped below 3mA or rose above 21mA. Remedy:
|
| UL3 Undertorque Detection 1 |
Cause: Current has fallen below minimum value (L6-02) for longer than allowable time (L6-03). Remedy:
|
| UL4 Undertorque Detection 2 |
Cause: Current has fallen below minimum value (L6-05) for longer than allowable time (L6-06). Remedy:
|
| UL6 Motor Underload |
Cause: The load has fallen below the underload curve defined in L6-14. Remedy:
|
| UnbC Current Unbalance |
Cause: The internal current sensor has detected a current unbalance situation. Remedy:
|
| Uv1 DC Bus Undervoltage |
Cause: DC bus voltage fell below detection level (L2-05). Input power phase loss or loose wiring. Remedy:
|
| Uv2 Control Power Supply Voltage Fault |
Cause: Voltage is too low for the control drive input power. Remedy:
|
| Uv3 Undervoltage 3 (Soft-Charge Bypass) |
Cause: The soft-charge bypass circuit failed (relay or contactor damaged). Remedy:
|
| Uv4 Gate Drive Board Undervoltage |
Cause: Voltage drop in the gate drive board circuit. Remedy:
|
| VLTS Volute-Thermostat Fault |
Cause: Digital input assigned to volute/thermostat (H1-xx = 88/89) is active. Remedy:
|
| voF Output Voltage Detection Fault |
Cause: Hardware damaged or internal drive module overheat due to abnormal ambient power. Remedy:
|
| WLL Water Level Loss |
Cause: Analog input for "WaterLvl/Suction" dropped below 3mA or rose above 21mA. Remedy:
|
| ACCUM Accumulated Level Error |
Cause: The accumulated level has exceeded the values set in P6-11 to P6-14. This is only effective when P6-15 (Accumulated Behavior) is set to 1 (alarm).
Remedy:
|
| Accum Lvl Reached Flow Accumulation level reached |
Cause: Accum Behavior P6-15 is set to 5 (Stop, Alarm, & Reset) and the Accumulated Level has been reached.
Remedy:
|
| AnalogFB Lost Analog Feedback Lost |
Cause: Defective or broken analog input source. Analog feedback not detected.
Remedy:
|
| Anti-Jam Active Anti-Jam Alarm |
Cause: The drive was not able to clear debris from the impeller in fewer than the attempts set in P7-02.
Remedy:
|
| AUXFB PI Aux Lvl Loss |
Cause: The analog input programmed for "PI Aux FB Level" (H3-xx = 27) has dropped below 3 mA or risen above 21 mA for longer than 1 second.
Remedy:
|
| Backup FdBk Lost Backup Feedback Device lost |
Cause: Wire-break on Analog Input Terminal programmed for Backup PI Feedback (H3-xx = 24). Backup PI Feedback Transducer is broken.
Remedy:
|
| bAT Digital Operator Battery Voltage Low |
Cause: The digital operator battery is low.
Remedy:
|
| bb Baseblock |
Cause: External baseblock signal was entered via one of the multi-function input terminals (S1 to S8).
Remedy:
|
| boL Braking Transistor Overload Fault |
Cause: The proper braking resistor has not been installed.
Remedy:
|
| bUS Option Communication Error |
Cause: Connection is broken, master controller stopped communicating, or option is damaged. Data error due to noise.
Remedy:
|
| CALL Serial Communication Transmission Error |
Cause: Communications wiring is faulty/shorted, programming error on master side, or communications circuitry is damaged.
Remedy:
|
| CE MEMOBUS/Modbus Communication Error |
Cause: Data error due to noise, incompatible protocol, CE detection time (H5-09) too short, or cable disconnected/damaged.
Remedy:
|
| CE - Comm Loss Drive runs at H5-14 |
Cause: MEMOBUS/Modbus Communicator Error (Drive continues running based on H5-14 setting). Data error due to noise or cable issues.
Remedy:
|
| Current Limit Foldback Current Limit Foldback |
Cause: Drive output speed is being limited due to the output current limit.
Remedy:
|
| De-Scale/De-rag Active De-scale is running |
Cause: De-scale is programmed and enough run-time has been accumulated.
Remedy:
|
| Differential FB Detected Differential Feedback Detected |
Cause: The difference between the PID Feedback and the Differential Feedback (H3-xx = 28) exceeded the P4-18 level for the time set in P4-19.
Remedy:
|
| dnE Drive Disabled |
Cause: "Drive Enable" is set to a multi-function contact input (H1-xx = 6A) and the contact is open.
Remedy:
|
| EF Forward/Reverse Run Command Input Error |
Cause: Sequence error. Both forward run and reverse run closed simultaneously for longer than 0.5 s.
Remedy:
|
| EF0 Option Card External Fault |
Cause: An external fault was received from the PLC (F6-03 set to 3) or PLC program problem.
Remedy:
|
| EF1 - EF8 Pump Fault / External Fault (Terminals S1-S8) |
Cause: External fault at multi-function input terminal (S1 through S8). An external device has tripped an alarm function. Wiring is incorrect.
Remedy:
|
| EoF Emergency Override Forward Run |
Cause: The multi-function digital input for EmergOverrideFWD (H1-xx = AF) has been closed.
Remedy:
|
| Eor Emergency Override Reverse Run |
Cause: The multi-function digital input for EmergOverrideREV (H1-xx = B0) has been closed.
Remedy:
|
| E5 SI-T3 Watchdog Timer Error |
Cause: The watchdog timed out. Data has not been received from the PLC.
Remedy:
|
| FAn Internal Fan Error |
Cause: Internal cooling fan has malfunctioned or magnetic contactor failure.
Remedy:
|
| Feedback Loss Go To Freq. PI Feedback Loss |
Cause: PI feedback source is incorrectly installed or not working. (Effective when b5-12 is set to 3).
Remedy:
|
| Feedback Loss Wire Break PI Feedback Loss |
Cause: The analog input programmed for PID feedback has gone above 21 mA or fallen below 3 mA.
Remedy:
|
| Freq. Ref Pump Min (P1-06) Minimum Pump Frequency Reference |
Cause:
The frequency reference is set lower than P1-06. The frequency reference is internally set to the P1-06 value during this time. This will only be active when the drive is NOT in PI Mode and Minimum Pump Frequency is enabled (P1-06 > 0.00).
Remedy:
|
| Freq. Ref Thrust (P4-12) Thrust Frequency Reference |
Cause:
The fixed frequency reference is set to a value lower than the P4-12 (Thrust Frequency) setting. This will only be active when the drive is NOT in PI Mode and Thrust bearing is enabled (P4-12 > 0.00).
Remedy:
|
| Geo Params Chk Q2-05 to Q2-08 Geothermal Mode Parameters |
Cause:
The temperature parameter values are set incorrectly. The drive is running at the level set in Q2-03 due to an incorrect setting.
Remedy:
|
| HCA Current Alarm |
Cause:
Drive current exceeded overcurrent warning level (150% of the rated current).
Remedy:
|
| HIAUX High PI Aux Lvl High PI Auxiliary Feedback Level |
Cause:
PI Aux Feedback has risen above the Q6-12 level for longer than the time set in Q6-13 and the drive is running in AUTO.
Remedy:
|
| HIFLO High Flow Error |
Cause:
The meter has detected a high flow condition. The flow is too high or measured water flow has risen above P6-17 level for time set in P6-18.
Remedy:
|
| High Feedback High FB Sensed High Feedback Level Alarm |
Cause:
The feedback signal is too high (risen above P1-11 level).
Remedy:
|
| HISUC High Suction High Section Pressure |
Cause:
The suction pressure has risen above the level set in Q5-12.
Remedy:
|
| LOAUX Low PI Aux Lvl Low PI Auxiliary Feedback Level |
Cause:
PI Aux Feedback has fallen below the Q6-09 level for longer than the time set in Q6-10.
Remedy:
|
| LOP Loss of Prime |
Cause:
The pump has lost its prime (P1-22 is set to 1). Measured quantity dropped below P1-19 level for time set in P1-20.
Remedy:
|
| LOSUC Low Suction Low Section Pressure |
Cause:
The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10.
Remedy:
|
| Low City Pressure |
Cause:
Insufficient pressure is present on the inlet to the pump. (P4-24 logic applies).
Remedy:
|
| Low Feedback Low FB Sensed Low Feedback Level Alarm |
Cause:
The feedback signal is too low (dropped below level set in P1-08).
Remedy:
|
| Low Suction Pressure |
Cause:
Insufficient suction pressure is present. (Specific to P4-24 logic settings).
Remedy:
|
| Low Water in Tank |
Cause:
Insufficient pressure is present on the inlet to the pump (Shown when P4-24 = 2).
Remedy:
|
| Low WL/SP/PI-Aux Drive Disabled Low Water Level / Suction Pressure / Aux PI Feedback Disabled |
Cause:
Drive is not allowed to run in MEMOBUS multiplex. Water Level or Suction Pressure is below the Q4-06/Q5-06/Q6-06 setting.
Remedy:
|
| LT-1 Cooling Fan Maintenance Time |
Cause:
The cooling fan has reached 90% of its expected performance life.
Remedy:
|
| LT-2 Capacitor Maintenance Time |
Cause:
The main circuit and control circuit capacitors have reached 90% of their expected performance lives.
Remedy:
|
| LT-3 Soft Charge Bypass Relay Maintenance Time |
Cause:
The DC bus soft charge relay has reached 90% of expected performance life.
Remedy:
|
| LT-4 IGBT Maintenance Time (50%) |
Cause:
IGBTs have reached 50% of their expected performance life.
Remedy:
|
| Main FdBk Lost Using Backup FB Main Feedback Device (H3-xx = B) lost |
Cause:
Wire-break on Analog Input Terminal programmed for Primary PI Feedback or Transducer is broken.
Remedy:
|
| Net Flow Meter Lost, Chk Source Net Flow Meter Loss |
Cause:
The flow meter function has not received a valid flow rate from another drive (when P1-01 = 3, P6-01 > 0, P9-40 = 3).
Remedy:
|
| NETSCAN Waiting for Master |
Cause:
Drive is waiting for a message from the master. No message received within time set in P9-28.
Remedy:
|
| NMS Not Maintaining Setpoint |
Cause:
The setpoint cannot be maintained and P1-17 is set to 1. Feedback deviates from setpoint > P1-15 level.
Remedy:
|
| oH Heatsink Overheat |
Cause:
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02. Surrounding temp too high, fan stopped, or airflow restricted.
Remedy:
|
| oH2 Drive Overheat Warning |
Cause:
An external device triggered an overheat warning in the drive (Input S1 through S8).
Remedy:
|
| oH3 Motor Overheat |
Cause:
Motor overheat signal entered to multi-function analog input terminal exceeded alarm level.
Remedy:
|
| oH5 Motor Overheat (NTC Input) |
Cause:
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2). Remedy:
|
| oL1 Motor Overload |
Cause:
The electronic motor overload protection tripped. Possible causes include:
Remedy:
|
| oL2 Drive Overload |
Cause:
The thermal sensor of the drive triggered overload protection.
Remedy:
|
| oL3 Overtorque Detection 1 |
Cause:
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Remedy:
|
| oL4 Overtorque Detection 2 |
Cause:
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06). Remedy:
|
| ov DC Bus Overvoltage |
Cause:
The DC bus voltage exceeded the trip point.
Remedy:
|
| PoC Pump Over Cycle |
Cause:
The pump has exceeded the number of cycles set in P2-10 in the time set in P2-11 and P2-12 is set to 1 (alarm). Remedy:
|
| R-DNE-S Remote Drive Disable |
Cause:
Terminal S□ (H1-0□ = 95) has been closed for the time set in P4-26, Remote Drive Disable On-Delay. Remedy:
|
| rUn Motor Switch during Run |
Cause:
A motor switch command was entered during run. Remedy:
|
| SE MEMOBUS/Modbus Communication Test Mode Error |
Cause:
A digital input set to 67H (MEMOBUS/Modbus test) was closed while the drive was running. Remedy:
|
| SPL Suction Pressure Loss |
Cause:
Wire-break detection for suction pressure. An analog input programmed for setting 23 "WaterLvl/Suction" has dropped below 3 mA or risen above 21 mA for longer than 1 second. Remedy:
|
| THo Thermistor Disconnect |
Cause:
The thermistor used to detect motor temperature has become disconnected. Remedy:
|
| TrPC IGBT Maintenance Time (90%) |
Cause:
IGBTs have reached 90% of their expected performance life. Remedy:
|
| UL3 Undertorque Detection 1 |
Cause:
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Remedy:
|
| UL4 Undertorque Detection 2 |
Cause:
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06). Remedy:
|
| UL6 Motor Underload |
Cause:
The load has fallen below the underload curve defined in L6-14. The output current has fallen below the motor underload curve for longer than the time set to L6-03. Remedy:
|
| Uv Undervoltage |
Cause:
DC bus voltage dropped below the level specified in L2-05 while the drive was stopped and a Run command was entered.
Remedy:
|
| voF Output Voltage Detection Error |
Cause:
Problem detected with the voltage on the output side of the drive. Hardware is damaged or internal drive module MC/FAN overheat. Remedy:
|
| WLL Water Level Loss |
Cause:
An analog input programmed for setting 23 "WaterLvl/Suction" has dropped below 3 mA or risen above 21 mA for longer than 1 second. Remedy:
|
| WL/SP/PIAux Lost Analog Input Lost |
Cause:
Network Water Level/Suction Pressure/Aux PI Feedback is being used because a wire-break was detected with the analog signal.
Remedy:
|
| WrUn Waiting for Run |
Cause:
The Run command has been applied and the b1-11 Back Spin Timer is active. Remedy:
|
| oPE01 Drive Capacity Setting Fault |
Cause: The drive model selection (o2-04) and the actual capacity of the drive are not the same. Remedy:
|
| oPE02 Parameter Range Setting Error |
Cause: Parameters were set outside the possible setting range. (Use U1-18 to find parameters set outside the range). Remedy:
|
| oPE03 Multi-Function Input Selection Error |
Cause: A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.
Remedy:
|
| oPE04 Initialization Required, Term <-> Ctrl Chg |
Cause: The drive, control board, or terminal board have been replaced and the parameter settings between the control board and the terminal board no longer match. Remedy:
|
| oPE05 Run Command/Frequency Reference Source Selection Error |
Cause:
Remedy:
|
| oPE07 Multi-Function Analog Input Selection Error |
Cause: A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06 and PID functions conflict. At least two analog input terminals are set to the same function. Remedy:
|
| (No Code Displayed) PID Feedback/Pulse Train Conflict |
Cause: The following simultaneous contradictory settings:
Remedy:
|
| oPE09 PID Control Selection Fault |
Cause: PID control function selection is incorrect (Requires b5-01 = 1 to 4).
Remedy:
|
| oPE10 V/f Data Setting Error |
Cause: V/f pattern setting error. One of the following setting errors has occurred: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Remedy:
|
| oPE11 Carrier Frequency Setting Error |
Cause: The following simultaneous contradictory settings have occurred:
Remedy:
|
| oPE18 Online Tuning Parameter Setting Error |
Cause: One of the following errors occurred while online tuning was enabled in OLV (A1-02 = 2):
Remedy:
|
| oPE28 Sequence Timer Error |
Cause: One or more of the sequence timers is not set in the correct order. Contradictory settings:
Remedy:
|
| oPE29 Geothermal Set Error |
Cause: P1-01 parameter selection is not compatible with Geothermal Mode (b1-01 = 5). Remedy:
|
| oPE30 Flow Meter Input Error |
Cause:
Remedy:
|
| oPE31 Water Level/Suction Pressure/PI Aux |
Cause: One or both of the following conditions are present:
Remedy:
|
| oPE32 Incompatible Network Water Level/Suction Pressure Mode |
Cause: Low Water Level or Suction Pressure Turn-Off Method (P9-51) is restricted to Water Level Source of Analog Only (P9-50 = 0). Remedy:
|
| oPE33 Parameter selection is incompatible with the selected network P9-99 |
Cause: When P1-01 = 3 (MEMOBUS Networking) and P9-99 = 0, one of the following parameters has been set:
Remedy:
|
| oPE34 De-Scale Setting Error |
Cause: The De-scale function is not allowed while Anti-Jam or MEMOBUS Multiplex is enabled. Remedy:
|
| End1 Excessive V/f Setting |
Cause: The torque reference exceeded 20% during Auto-Tuning OR The results from Auto-Tuning the no-load current exceeded 80%. Remedy:
|
| End2 Motor Iron-Core Saturation Coefficient |
Cause: Motor data entered during Auto-Tuning was incorrect OR Results from Auto-Tuning are outside the parameter setting range. Remedy:
|
| End3 Rated Current Setting Alarm |
Cause: The correct current rating printed on the motor nameplate was not entered into T1-04. Remedy:
|
| End4 Adjusted Slip Calculation Error |
Cause: The calculated slip is outside the allowable range. Remedy:
|
| End5 Resistance Tuning Error |
Cause: The calculated resistance value is outside the allowable range. Remedy:
|
| End6 Leakage Inductance Alarm |
Cause: The calculated leakage inductance value is outside the allowable range. Remedy:
|
| End7 No-Load Current Alarm |
Cause: The entered no-load current value was outside the allowable range OR Auto-Tuning results were less than 5% of the motor rated current. Remedy:
|
| Er-01 Motor Data Error |
Cause: Motor data entered during Auto-Tuning was incorrect, Motor output power and settings do not match, or Motor rated current and detected no-load current are inconsistent. Remedy:
|
| Er-02 Minor Fault |
Cause: An alarm was triggered during Auto-Tuning. Remedy:
|
| Er-03 STOP Button Input |
Cause: Auto-Tuning canceled by pressing STOP button. Remedy:
|
| Er-04 Line-to-Line Resistance Error |
Cause: Motor data entered incorrect, Results outside parameter range, or Faulty motor cable connection. Remedy:
|
| Er-05 No-Load Current Error |
Cause: Motor data entered incorrect, Results outside parameter range, or The load was too high during Rotational Auto-tuning. Remedy:
|
| Er-08 Rated Slip Error |
Cause: Motor data entered incorrect, Results outside parameter range, or The load was too high during rotational Auto-tuning. Remedy:
|
| Er-09 Acceleration Error |
Cause: Motor did not accelerate for the specified time, Torque limit too low, or Load too high. Remedy:
|
| Er-11 Motor Speed Fault |
Cause: Torque reference is too high. Remedy:
|
| Er-12 Current Detection Error |
Cause: One of the motor phases is missing, Current exceeded rating, Current too low, or Attempted Auto-Tuning without motor connected. Remedy:
|
| Er-13 Leakage Inductance Error |
Cause: Drive was unable to complete tuning for leakage inductance within 300 seconds. Remedy:
|
| Er-17 Reverse Prohibited Error |
Cause: Drive is prohibited from rotating the motor in reverse while attempting to perform Inertia Tuning. Remedy:
|
| CoPy Writing Parameter Settings (flashing) |
Cause: Parameters are being written to the drive. Remedy:
|
| CPyE Error Writing Data |
Cause: Failed writing parameters. Remedy:
|
| CSEr Copy Unit Error |
Cause: Hardware fault. Remedy:
|
| dFPS Drive Model Mismatch |
Cause: The drives used in the copy and write process are not the same model. Remedy:
|
| End Task Complete |
Cause: Finished reading, writing, or verifying parameters. Remedy:
|
| iFEr Communication Error |
Cause: A communication error occurred between the drive and the HOA keypad/USB unit OR Non-compatible cable used. Remedy:
|
| ndAT Model, Voltage Class, Capacity Mismatch |
Cause: Drives have different electrical specifications/capacities OR Device used to write is blank. Remedy:
|
| rdEr Error Reading Data |
Cause: Failed while attempting to read parameter settings from the drive. Remedy:
|
| rEAd Reading Parameter Settings (flashing) |
Cause: Displayed while the parameter settings are being read onto the USB Copy Unit. Remedy:
|
| vAEr Voltage Class, Capacity Mismatch |
Cause: The drive from which the parameters were copied and the drive on which the Verify mode is being performed have different specifications. Remedy:
|
| vFyE Parameter settings mismatch |
Cause: Indicates that parameter settings that have been Read and loaded onto the Copy Unit or HOA keypad are different. Remedy:
|
| vrFy Comparing Parameter Settings (flashing) |
Cause: The Verify mode has confirmed that parameters settings on the drive and parameters read to the copy device are identical. Remedy:
|
How to Read iQPump1000 Faults via Keypad & PC
In 2026, troubleshooting an industrial pump station requires looking at the system history, not just the current error. The iQPump1000 offers several ways to do this:
- Real-Time Clock (RTC) Logs: Unlike smaller drives, the iQPump1000 stamps faults with the actual Date and Time (provided the battery is active). Navigate to Monitor > Fault History to see exactly when the pump tripped (e.g., “LPo at 2026-06-15 14:30”).
- U2 Fault Trace: Access the “Black Box” data directly on the keypad:
- U2-01: Current Fault.
- U2-02: Previous Fault.
- U2-13/14 (Terminal Status): Crucial for seeing if a “Low Level Float Switch” or “Flow Switch” was open at the moment of the trip.
- DriveWizard Industrial: Connect via USB to view the Pump Curve Monitor. This allows you to graph Pressure (PSI) vs. Frequency (Hz) to determine if the pump is mechanically worn or if the PID settings are unstable.
Frequently Asked Questions (FAQ)
Q: What is the difference between an Alarm and a Fault on the iQPump1000?
A:
- Alarm (Flashing ‘ALM’ LED): The drive detects a warning (like “High Pressure” or “Sleep Mode”) but continues to regulate the system.
- Fault (Solid ‘ALM’ LED): The drive trips to protect the pump or motor. The output stops, and the system pressure will drop.
Q: How do I reset a Yaskawa iQPump1000 fault?
A: Once the water supply is verified:
- Press the RESET key on the keypad.
- If using the “Hand-Off-Auto” keypad, switching to OFF and back to AUTO often resets the fault.
- Cycle the main power disconnect.
Q: What does “oPr” mean?
A: “oPr” stands for Minimum Pressure (Open Transducer). This usually means the 4-20mA pressure transducer signal has been lost (wire broken) or the system pressure has dropped below the safety threshold set in parameter P1-15, indicating a pipe break.
Comments
Post a Comment